A3 · Lesson 21 · Conjugates and power
The mirror image that turns phasors into power
A motor draws 10 A from a 120 V outlet, yet the power company's meter says it uses far less than 1200 W. Nothing is broken. Part of the current is out of step with the voltage, and the out-of-step part delivers no energy on average. Working out how much power really flows takes one more operation on complex numbers: the conjugate.
Play
- In the first picture, is the mirror image of in the real axis. The third arrow is their product, . Move anywhere: where does the product always land?
- In the second picture, the voltage and current have the same frequency, with the current lagging by Δφ. The red curve is the power, voltage times current, at each instant, and the dashed line is its average.
- Slide Δφ from 0° to 90°. What happens to the average power?
Predict
The current lags the voltage by 90°. What is the average power delivered?
Zero. At 90° apart, the power is positive for a quarter cycle and negative for the next: energy goes into the load and comes straight back. That's what a capacitor or an ideal inductor does. The average power depends on the cosine of the phase difference, and .
Name it
The conjugate
The conjugate of flips the sign of its imaginary part:
It's the mirror image in the real axis. Three facts make it useful:
- Magnitude: . Multiplying by the conjugate gives a real number, the length squared. In polar form, the lengths multiply and the angles θ and −θ cancel.
- Parts: and , so .
- Dividing in rectangular form: multiply the top and bottom by the conjugate of the bottom, which makes the bottom real:
Power
With and , the instantaneous power wobbles at twice the frequency (that's the product-to-sum identity from A2), and its average is
The conjugate does the subtracting of the angles: has length and angle , and the real part keeps the cosine.
- is the power factor. In phase, it's 1 and all the current does work. At 90°, it's 0 and none does.
- The imaginary part, , is the reactive power: energy that sloshes back and forth each cycle without being used up.
- With RMS phasors the ½ disappears: . That's the form power engineers use.
Worked example
Find for .
Show the solution
- Multiply.
- What it means. That's : the cross terms cancel and the product is always real. It's why multiplying by the conjugate is the way to make a bottom real.
Answer , which is .
Worked example
A load has V and A (amplitudes). Find its average and reactive power.
Show the solution
- Complex power. With amplitudes,
- Average power.
- Reactive power.
- Why the conjugate. The conjugate on the current is what makes the angle come out as the voltage minus the current's angle, the angle that sets the power factor.
Answer the average power is 736 W and the reactive power is 425 var.
Worked example
A load has V and A, as amplitudes. Find its complex power .
Show the solution
- Conjugate the current. The conjugate flips the current's angle:
- Multiply.
- Rectangular form. The load takes 216.5 W of real power and 125 var of reactive power.
- Angle. The angle of is the angle between voltage and current, 30°.
Answer VA: 216.5 W of real power and 125 var of reactive power.
Check
What is for ?
Check
Divide by multiplying the top and bottom by the conjugate of the bottom.
(a)
What is the real part of the result?
(b)
And the imaginary part?
Check
A load has a voltage of amplitude 28 V and a current of amplitude 1.3 A, lagging the voltage by 60°. What average power does it take?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A motor's current lags its voltage by 60°. What is its power factor, and what does it mean?
Check
A load has voltage V and current A (amplitudes). Its complex power is .
(a)
What is the real power?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
(b)
What is the reactive power?
(c)
What is the apparent power ?
Check
Derive what a number and its conjugate give together, for .
Step 1
Multiply .
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
Add .
Step 3
Subtract .
Explain why
Why does a current that's 90° out of phase with the voltage deliver no power on average?
Power at each instant is voltage times current. When they're 90° apart, for a quarter of each cycle they have the same sign and the power is positive, and for the next quarter they have opposite signs and the power is negative, with exactly the same shape. Energy flows into the load and then back out again, so over a whole cycle the total is zero. Mathematically, the average is .
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.