title: Conjugates, magnitude, and why power uses them
heading: The mirror image that turns phasors into power
eyebrow: A3 · Lesson 21 · Conjugates and power
xp: 40
---

::: hook
A motor draws 10 A from a 120 V outlet, yet the power company's meter says it uses far less than 1200 W. Nothing is broken. Part of the current is out of step with the voltage, and the out-of-step part delivers no energy on average. Working out how much power really flows takes one more operation on complex numbers: the conjugate.

::: play
- In the first picture, $z^*$ is the mirror image of $z$ in the real axis. The third arrow is their product, $zz^*$. Move $z$ anywhere: where does the product always land?
- In the second picture, the voltage and current have the same frequency, with the current lagging by Δφ. The red curve is the power, voltage times current, at each instant, and the dashed line is its average.
- Slide Δφ from 0° to 90°. What happens to the average power?
:::
:::

```sim plot
view: complex
range: 8
slider: a = -3..3 step 0.1 = 2
slider: b = -3..3 step 0.1 = 1.5
arrow: a + j*b | label: z
arrow: a - j*b | dashed | color: ch2 | label: z*
arrow: (a + j*b)*(a - j*b) | color: ch3 | label: zz*
readout: zz* = a^2 + b^2
readout: |z|² = abs(a + j*b)^2
```

::: predict
## The current lags the voltage by 90°. What is the average power delivered?

- [ ] Half the peak power
- [ ] The full product of the amplitudes
- [x] Zero
- [ ] It depends on the frequency

::: reveal
Zero. At 90° apart, the power is positive for a quarter cycle and negative for the next: energy goes into the load and comes straight back. That's what a capacitor or an ideal inductor does. The average power depends on the cosine of the phase difference, and $\cos 90° = 0$.
:::
:::

::: nameit
## The conjugate

The **conjugate** of $z = a + jb$ flips the sign of its imaginary part:

$$z^* = a - jb \qquad\text{so in polar form}\qquad (r\angle\theta)^* = r\angle{-\theta}$$

It's the mirror image in the real axis. Three facts make it useful:

- **Magnitude:** $zz^* = (a + jb)(a - jb) = a^2 + b^2 = |z|^2$. Multiplying by the conjugate gives a real number, the length squared. In polar form, the lengths multiply and the angles θ and −θ cancel.
- **Parts:** $z + z^* = 2a$ and $z - z^* = j2b$, so $\operatorname{Re}(z) = (z + z^*)/2$.
- **Dividing in rectangular form:** multiply the top and bottom by the conjugate of the bottom, which makes the bottom real:

$$\frac{a + jb}{c + jd} = \frac{(a + jb)(c - jd)}{c^2 + d^2}$$

## Power

With $v = V_m\cos(\omega t + \varphi_v)$ and $i = I_m\cos(\omega t + \varphi_i)$, the instantaneous power $p = vi$ wobbles at twice the frequency (that's the product-to-sum identity from A2), and its average is

$$P = \tfrac12 V_m I_m \cos(\varphi_v - \varphi_i) = \tfrac12\operatorname{Re}\left(\mathbf{V}\mathbf{I}^*\right)$$

The conjugate does the subtracting of the angles: $\mathbf{V}\mathbf{I}^*$ has length $V_m I_m$ and angle $\varphi_v - \varphi_i$, and the real part keeps the cosine.

- $\cos(\varphi_v - \varphi_i)$ is the **power factor**. In phase, it's 1 and all the current does work. At 90°, it's 0 and none does.
- The imaginary part, $Q = \tfrac12\operatorname{Im}(\mathbf{V}\mathbf{I}^*)$, is the **reactive power**: energy that sloshes back and forth each cycle without being used up.
- With RMS phasors the ½ disappears: $P = \operatorname{Re}(\mathbf{V}_\text{rms}\mathbf{I}^*_\text{rms})$. That's the form power engineers use.

```sim plot
view: graph
x: t = 0..20m s
y: y = -12..12
slider: dp = 0..180 step 5 = 30 °
plot: 3*cos(2*pi*100*t) | color: ch1 | label: v (V)
plot: 2*cos(2*pi*100*t - dp°) | color: ch2 | label: i (A)
plot: 3*cos(2*pi*100*t)*2*cos(2*pi*100*t - dp°) | color: ch3 | label: p (W)
plot: 0.5*3*2*cos(dp°) | dashed | color: ch3 | label: average
readout: average power = 0.5*3*2*cos(dp°) W
readout: power factor = cos(dp°)
```
:::

::: example
## Find $zz^*$ for $z = 3 + 4j$.

::: solution
1. **Multiply.**
   $$\begin{aligned} &(3 + 4j)(3 - 4j) \\ &= 9 - 12j + 12j - 16j^2 \\ &= 9 + 16 \\ &= 25 \end{aligned}$$
2. **What it means.** That's $|z|^2$: the cross terms cancel and the product is always real. It's why multiplying by the conjugate is the way to make a bottom real.

**Answer:** $zz^* = 25$, which is $|z|^2$.
:::
:::

::: example
## A load has $V = 170\angle 0°$ V and $I = 10\angle{-30°}$ A (amplitudes). Find its average and reactive power.

::: solution
1. **Complex power.** With amplitudes,
   $$\begin{aligned} S &= \tfrac{1}{2}VI^* \\ &= \tfrac{1}{2} \times 170\angle 0° \times 10\angle 30° \\ &= 850\angle 30°\ \text{VA} \end{aligned}$$
2. **Average power.**
   $$\begin{aligned} P &= 850\cos 30° \\ &= 736\ \text{W} \end{aligned}$$
3. **Reactive power.**
   $$\begin{aligned} Q &= 850\sin 30° \\ &= 425\ \text{var} \end{aligned}$$
4. **Why the conjugate.** The conjugate on the current is what makes the angle come out as the voltage minus the current's angle, the angle that sets the power factor.

**Answer:** the average power is 736 W and the reactive power is 425 var.
:::
:::

::: example
## A load has $V = 100\angle 20°$ V and $I = 5\angle{-10°}$ A, as amplitudes. Find its complex power $S = \tfrac12 VI^*$.

::: solution
1. **Conjugate the current.** The conjugate flips the current's angle:
   $$I^* = 5\angle 10°$$
2. **Multiply.**
   $$\begin{aligned} S &= \tfrac12 \times 100 \times 5\angle(20° + 10°) \\ &= 250\angle 30°\ \text{VA} \end{aligned}$$
3. **Rectangular form.**
   $$S = 216.5 + j125$$
   The load takes 216.5 W of real power and 125 var of reactive power.
4. **Angle.** The angle of $S$ is the angle between voltage and current, 30°.

**Answer:** $S = 250\angle 30°$ VA: 216.5 W of real power and 125 var of reactive power.
:::
:::

::: check
given: a = -9..9 int; b = 2..9 int
answer: a^2 + b^2
tolerance: 0.001

## What is $zz^*$ for $z = \given{a} + j\given{b}$?

::: right
Right. $(\given{a} + j\given{b})(\given{a} - j\given{b}) = \given{a}^2 + \given{b}^2$, a real number: the length squared.
:::

::: misses
- [a^2 - b^2] $j\given{b} \times (-j\given{b}) = -j^2\given{b}^2 = +\given{b}^2$, so the parts add.
- [sqrt(a^2 + b^2)] That's $|z|$. $zz^*$ is its square.
- [any] Not yet. Multiply out, remembering $j^2 = -1$.
:::
:::

::: check
kind: parts
given: a = 1 | 3 | 5 | 7 | 9; b = 2 | 4 | 6 | 8; c = 2 | 4; d = 1 | 3

## Divide $\dfrac{\given{a} + j\given{b}}{\given{c} + j\given{d}}$ by multiplying the top and bottom by the conjugate of the bottom.

::: part
answer: (a*c + b*d)/(c^2 + d^2)
tolerance: 0.5%

### What is the real part of the result?

::: misses
- [(a*c - b*d)/(c^2 + d^2)] Multiply by $\given{c} - j\given{d}$: the $j\given{b} \times (-j\given{d})$ term is $+\given{b}\given{d}$.
- [a/c] Complex division doesn't divide the parts separately.
- [any] The top becomes $(\given{a} + j\given{b})(\given{c} - j\given{d})$ and the bottom $\given{c}^2 + \given{d}^2$.
:::
:::

::: part
answer: (b*c - a*d)/(c^2 + d^2)
tolerance: 0.5%

### And the imaginary part?

::: misses
- [(b*c + a*d)/(c^2 + d^2)] The cross term $\given{a} \times (-j\given{d})$ is negative.
- [b/d] Complex division doesn't divide the parts separately.
- [any] Collect the terms with $j$ in $(\given{a} + j\given{b})(\given{c} - j\given{d})$, then divide by $\given{c}^2 + \given{d}^2$.
:::
:::

::: right
Right. Multiplying by the conjugate turns the bottom into the real number $c^2 + d^2$.
:::
:::

::: check
given: Vm = 10..170 sig 2; Im = 1..10 sig 2; dp = 20 | 37 | 60 | 75
answer: 0.5*Vm*Im*cos(dp°)
unit: W
tolerance: 1%

## A load has a voltage of amplitude {Vm} V and a current of amplitude {Im} A, lagging the voltage by {dp}°. What average power does it take?

::: right
Right. $P = \tfrac12 V_m I_m\cos\Delta\varphi$ = {answer}.
:::

::: misses
- [Vm*Im*cos(dp°)] With amplitude phasors there's a factor of ½: the average of $\cos^2$ is ½.
- [0.5*Vm*Im] That's the power if they were in phase. The phase difference reduces it by $\cos\Delta\varphi$.
- [0.5*Vm*Im*sin(dp°)] That's the reactive power. The average power uses the cosine.
- [any] Not yet. Use $P = \tfrac12 V_m I_m\cos(\varphi_v - \varphi_i)$.
:::
:::

::: check
kind: choice

## A motor's current lags its voltage by 60°. What is its power factor, and what does it mean?

- [ ] 0.87: the motor uses 87% of its current's capacity
- [x] 0.5: only half of $\tfrac12 V_m I_m$ is delivered as average power
- [ ] 60%: the current is 60% efficient
- [ ] −0.5: the motor sends power back

::: right
Right. The power factor is $\cos 60° = 0.5$: the average power is half of what the same voltage and current would deliver in phase.
:::

::: misses
- [1] That's $\sin 60°$. The power factor is the cosine of the phase difference.
- [3] The power factor is $\cos\Delta\varphi$, a number from 0 to 1, not the angle itself.
- [4] $\cos 60°$ is positive. Power flows back on average only beyond 90°.
:::
:::

::: check
kind: parts
given: Vm = 170 | 325; Im = 2 | 8; pa = 30 | 45; pb = -20 | 10

## A load has voltage $\given{Vm}\angle\given{pa}°$ V and current $\given{Im}\angle\given{pb}°$ A (amplitudes). Its complex power is $S = \tfrac12 VI^*$.

::: part
answer: 0.5*Vm*Im*cos((pa - pb)°)
unit: W
tolerance: 0.5%

### What is the real power?

::: misses
- [0.5*Vm*Im*cos((pa + pb)°)] The conjugate subtracts the current's angle.
- [Vm*Im*cos((pa - pb)°)] With amplitudes, the power has a ½.
- [any] The real part of $S$.
:::
:::

::: part
answer: 0.5*Vm*Im*sin((pa - pb)°)
unit: var
tolerance: 0.5%

### What is the reactive power?

::: misses
- [any] The imaginary part of $S$.
:::
:::

::: part
answer: 0.5*Vm*Im
unit: VA
tolerance: 0.5%

### What is the apparent power $|S|$?

::: misses
- [Vm*Im] With amplitudes, the power has a ½.
- [any] $\tfrac12|V||I|$.
:::
:::
:::

::: check
kind: derivation
vars: a = -3..3, b = -3..3

## Derive what a number and its conjugate give together, for $z = a + jb$.

::: step
answer: a^2 + b^2

### Multiply $z z^*$.
:::

::: step
answer: 2*a

### Add $z + z^*$.
:::

::: step
answer: 2*j*b

### Subtract $z - z^*$.
:::

::: right
Right. $zz^* = |z|^2$, $z + z^* = 2\,\text{Re}\,z$ and $z - z^* = 2j\,\text{Im}\,z$. The first is why $VI^*$ gives power.
:::
:::

::: explain
## Why does a current that's 90° out of phase with the voltage deliver no power on average?

::: model
Power at each instant is voltage times current. When they're 90° apart, for a quarter of each cycle they have the same sign and the power is positive, and for the next quarter they have opposite signs and the power is negative, with exactly the same shape. Energy flows into the load and then back out again, so over a whole cycle the total is zero. Mathematically, the average is $\tfrac12 V_m I_m\cos 90° = 0$.
:::
:::

::: practice

::: check
given: a = 1..9 int; b = 1..9 int
answer: -b
tolerance: 0.001

## What is the imaginary part of $(\given{a} + j\given{b})^*$?

::: misses
- [b] The conjugate flips the sign of the imaginary part.
- [any] $(a + jb)^* = a - jb$.
:::
:::

::: check
given: r = 1..9 int; t = 10..80 step 10
answer: -t
unit: °
tolerance: 0.001

## What is the angle of $(\given{r}\angle\given{t}°)^*$?

::: misses
- [t] The conjugate is the mirror image, so the angle flips sign.
- [any] $(r\angle\theta)^* = r\angle{-\theta}$.
:::
:::

::: check
given: r = 2..9 int
answer: r^2
tolerance: 0.001

## For any $z$ with $|z|$ = {r}, what is $zz^*$?

::: misses
- [r] $zz^*$ is the length squared.
- [any] $zz^* = |z|^2$.
:::
:::

::: check
given: V = 100..240 step 10; I = 1..15 sig 2; pf = 0.5..0.95 sig 2
answer: V*I*pf
unit: W
tolerance: 1%

## A load draws {I} A RMS from {V} V RMS with a power factor of {pf}. What average power does it take?

::: misses
- [0.5*V*I*pf] With RMS values there's no ½.
- [V*I] Multiply by the power factor too.
- [any] With RMS values, $P = V I \cos\Delta\varphi$.
:::
:::

::: check
given: Vm = 10..170 sig 2; Im = 1..10 sig 2; dp = 20 | 30 | 60 | 80
answer: 0.5*Vm*Im*sin(dp°)
tolerance: 1%

## Voltage amplitude {Vm} V, current amplitude {Im} A, current lagging by {dp}°. What is the reactive power $Q$, in VAR?

::: misses
- [0.5*Vm*Im*cos(dp°)] That's the average (real) power. Reactive power uses the sine.
- [any] $Q = \tfrac12 V_m I_m\sin\Delta\varphi$.
:::
:::
:::