A3 Complex numbers and phasors · Practice
Lab: AC power in Python
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
0 solved
0 in a row
0 of 4 kinds solid
Check
A 5 kW load at power factor 0.7 is on 230 V RMS, 60 Hz. What capacitance corrects it to unity?
Write units the way you normally would: 1.5 F, 1500 mF and 0.0015 kF are the same answer.
Check
A signal is 5 V DC plus 1 V amplitude at 1 kHz plus 3 V amplitude at 3 kHz. What is its RMS value?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
Correction capacitor, in farads: 2.6 kW at pf 0.55, 360 V RMS, 60 Hz?
Write units the way you normally would: 1.5 F, 1500 mF and 0.0015 kF are the same answer.
Check
RMS of 7.2 V DC + 0.16 V and 2.2 V amplitude at two frequencies?
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to the lesson · Practice every topic in A3