A3 · Lesson 23 · Three-phase arithmetic
Why 120 V phases make 208 V between them
Commercial buildings in the US get three-phase power: each phase is 120 V from neutral, yet between any two phases you measure 208 V, not 240 V. The phases are three sinusoids a third of a cycle apart, so the voltage between two of them is the difference of two phasors at 120° to each other. Three-phase power runs nearly every motor, generator and transmission line in the world, and its arithmetic is phasor arithmetic with one special number.
Play
- The three arrows are the phase voltages , and , 120° apart. The long arrow is the line voltage .
- Read and compare it with the phase voltage. What's the ratio?
- Change phase c's size with . The small arrow is the sum of all three. When is it zero?
Predict
Two 120 V phases are 120° apart. How big is the voltage between them?
208 V, which is . The difference of two equal arrows 120° apart is an arrow times as long, at 30° to the first. The phases would only give 240 V if they were 180° apart, as in a US home's split-phase supply.
Name it
The operator
Three-phase arithmetic uses one special number, the unit arrow at 120°:
Multiplying by turns a phasor 120° counterclockwise; by , 120° clockwise. Since is a cube root of 1 (lesson 8), and
Phase and line voltages
The three phase voltages (each line to neutral), in the usual order, are
The line voltage between two phases is their difference:
So line voltages are times the phase voltage and lead it by 30°. Common systems: 120/208 V in US commercial buildings, 277/480 V in US industry, 230/400 V in Europe.
Balanced and unbalanced
In a balanced system the three currents are equal in size and 120° apart, so they add to zero: . That's why a balanced load needs no neutral current, and why three-phase lines can carry power with three wires instead of six.
If the loads differ, the neutral carries the sum , worked out with phasors. For currents of sizes at the three phase angles, its size is
Power. The total real power of a balanced load is , with and the line voltage and current and the power factor.
Worked example
Show that the line voltage of a 120 V system is 207.8 V at 30°.
Show the solution
- Phase voltages in rectangular form. , and
- Line voltage.
- Its size.
- Its angle.
Answer , which is 207.8 V at 30.0°.
Worked example
The three phases of a building carry 10 A, 8 A and 6 A, each in phase with its own voltage. What current flows in the neutral?
Show the solution
- Add the phase currents. So A.
- Check with the formula.
- Compare with the phases. Even with this much imbalance, the neutral carries far less than any one phase.
Answer 3.46 A flows in the neutral.
Worked example
A balanced three-phase motor on 480 V (line, RMS) draws 50 A per line at a power factor of 0.85. What real power does it take?
Show the solution
- Use the balanced-load formula.
- Where the comes from. It comes from the line voltage being times each phase voltage, so per phase the motor sees 50 A and
- Check per phase. Three phases give the same total:
Answer the motor takes 35.3 kW of real power.
Check
The phase voltage of a three-phase system is 230 V. What is the line voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A three-phase system has a line voltage of 400 V. What is the voltage from each phase to neutral?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
The three phases carry 15 A, 8 A and 9 A, each in phase with its voltage. What is the neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A balanced three-phase motor draws 10 A per line at 400 V line voltage with a power factor of 0.9. What real power does it take?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
. What is the real part of ?
Check
What is , with ?
Check
A balanced three-phase load on 400 V (line, RMS) draws 10 A per line at a power factor of 0.9, lagging.
(a)
What is the phase voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
(b)
What real power does it take?
(c)
What reactive power does it take?
Check
Derive the line voltage between two phases, and .
Step 1
What is the real part of ?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What is its imaginary part?
Step 3
What is its length?
Explain why
Why can three-phase power be delivered with three wires, when three separate single-phase circuits would need six?
Each single-phase circuit needs a return wire. In a balanced three-phase system, the three return currents would be equal in size and 120° apart, so their phasors add to zero. A shared return wire would carry nothing, so it can be left out (or made small, to carry only the imbalance), and the three phase wires serve as each other's return.
Practice