A3 · Lesson 23 · Three-phase arithmetic

Why 120 V phases make 208 V between them

Commercial buildings in the US get three-phase power: each phase is 120 V from neutral, yet between any two phases you measure 208 V, not 240 V. The phases are three sinusoids a third of a cycle apart, so the voltage between two of them is the difference of two phasors at 120° to each other. Three-phase power runs nearly every motor, generator and transmission line in the world, and its arithmetic is phasor arithmetic with one special number.

Play

  • The three arrows are the phase voltages Va, Vb and Vc, 120° apart. The long arrow is the line voltage Vab=Va−Vb.
  • Read |Vab| and compare it with the phase voltage. What's the ratio?
  • Change phase c's size with k. The small arrow is the sum of all three. When is it zero?

Predict

Two 120 V phases are 120° apart. How big is the voltage between them?

Name it

The operator a

Three-phase arithmetic uses one special number, the unit arrow at 120°:

a=1∠120°=−12+j32

Multiplying by a turns a phasor 120° counterclockwise; by a2=1∠240°=1∠−120°, 120° clockwise. Since a is a cube root of 1 (lesson 8), a3=1 and

1+a+a2=0

Phase and line voltages

The three phase voltages (each line to neutral), in the usual order, are

Va=Vp∠0°Vb=Vp∠−120°=a2VaVc=Vp∠120°=aVa

The line voltage between two phases is their difference:

Vab=Va−Vb=Vp(1−a2)=3Vp∠30°

So line voltages are 3 times the phase voltage and lead it by 30°. Common systems: 120/208 V in US commercial buildings, 277/480 V in US industry, 230/400 V in Europe.

Balanced and unbalanced

In a balanced system the three currents are equal in size and 120° apart, so they add to zero: I(1+a+a2)=0. That's why a balanced load needs no neutral current, and why three-phase lines can carry power with three wires instead of six.

If the loads differ, the neutral carries the sum In=Ia+Ib+Ic, worked out with phasors. For currents of sizes I1,I2,I3 at the three phase angles, its size is

|In|=I12+I22+I32−I1I2−I2I3−I3I1

Power. The total real power of a balanced load is 3VLILcos⁡φ, with VL and IL the line voltage and current and cos⁡φ the power factor.

Worked example

Show that the line voltage of a 120 V system is 207.8 V at 30°.

Show the solution
  1. Phase voltages in rectangular form. Va=120, and Vb=120∠−120°=120(−0.5−j0.866)=−60−j103.9
  2. Line voltage. Vab=120−(−60−j103.9)=180+j103.9
  3. Its size. |Vab|=1802+103.92=207.8V
  4. Its angle. tan−1⁡(103.9/180)=30.0°

Answer Vab=180+j103.9, which is 207.8 V at 30.0°.

Worked example

The three phases of a building carry 10 A, 8 A and 6 A, each in phase with its own voltage. What current flows in the neutral?

Show the solution
  1. Add the phase currents. In=10+8∠−120°+6∠120°=10+(−4−j6.928)+(−3+j5.196)=3−j1.732 So |In|=3.46 A.
  2. Check with the formula. 100+64+36−80−48−60=12=3.46A
  3. Compare with the phases. Even with this much imbalance, the neutral carries far less than any one phase.

Answer 3.46 A flows in the neutral.

Worked example

A balanced three-phase motor on 480 V (line, RMS) draws 50 A per line at a power factor of 0.85. What real power does it take?

Show the solution
  1. Use the balanced-load formula. P=3VLILcos⁡φ=1.732×480×50×0.85=35.3kW
  2. Where the 3 comes from. It comes from the line voltage being 3 times each phase voltage, so per phase the motor sees 50 A and 480/3=277V
  3. Check per phase. Three phases give the same total: 3×277×50×0.85W=35.3kW

Answer the motor takes 35.3 kW of real power.

Check

The phase voltage of a three-phase system is 230 V. What is the line voltage?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

Check

A three-phase system has a line voltage of 400 V. What is the voltage from each phase to neutral?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

Check

The three phases carry 15 A, 8 A and 9 A, each in phase with its voltage. What is the neutral current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A balanced three-phase motor draws 10 A per line at 400 V line voltage with a power factor of 0.9. What real power does it take?

Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.

Check

a=1∠120°. What is the real part of a4?

Check

What is 1+a+a2, with a=1∠120°?

Check

A balanced three-phase load on 400 V (line, RMS) draws 10 A per line at a power factor of 0.9, lagging.

(a)

What is the phase voltage?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

(b)

What real power does it take?

(c)

What reactive power does it take?

Check

Derive the line voltage between two phases, V∠0° and V∠−120°.

Step 1

What is the real part of V∠0°−V∠−120°?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why can three-phase power be delivered with three wires, when three separate single-phase circuits would need six?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.