title: Three-phase arithmetic
heading: Why 120 V phases make 208 V between them
eyebrow: A3 · Lesson 23 · Three-phase arithmetic
xp: 40
---

::: hook
Commercial buildings in the US get three-phase power: each phase is 120 V from neutral, yet between any two phases you measure 208 V, not 240 V. The phases are three sinusoids a third of a cycle apart, so the voltage between two of them is the difference of two phasors at 120° to each other. Three-phase power runs nearly every motor, generator and transmission line in the world, and its arithmetic is phasor arithmetic with one special number.

::: play
- The three arrows are the phase voltages $V_a$, $V_b$ and $V_c$, 120° apart. The long arrow is the line voltage $V_{ab} = V_a - V_b$.
- Read $|V_{ab}|$ and compare it with the phase voltage. What's the ratio?
- Change phase c's size with $k$. The small arrow is the sum of all three. When is it zero?
:::
:::

```sim plot
view: complex
range: 260
slider: Vp = 100..280 = 120 V
slider: k = 0.5..1.5 step 0.05 = 1
arrow: Vp∠0 | label: Va
arrow: Vp∠-120 | color: ch2 | label: Vb
arrow: (k*Vp)∠120 | color: ch3 | label: Vc
arrow: Vp∠0 - Vp∠-120 | from: Vp∠-120 | label: Vab
arrow: Vp∠0 + Vp∠-120 + (k*Vp)∠120 | color: ch2 | label: sum
readout: |Vab| = abs(Vp∠0 - Vp∠-120) V | digits: 4
readout: |Vab| ÷ Vp = abs(Vp∠0 - Vp∠-120)/Vp | digits: 4
readout: |Va + Vb + Vc| = abs(Vp∠0 + Vp∠-120 + (k*Vp)∠120) V | digits: 3
```

::: predict
## Two 120 V phases are 120° apart. How big is the voltage between them?

- [ ] 240 V
- [ ] 120 V
- [x] 208 V
- [ ] 170 V

::: reveal
208 V, which is $120 \times \sqrt3$. The difference of two equal arrows 120° apart is an arrow $\sqrt3$ times as long, at 30° to the first. The phases would only give 240 V if they were 180° apart, as in a US home's split-phase supply.
:::
:::

::: nameit
## The operator $a$

Three-phase arithmetic uses one special number, the unit arrow at 120°:

$$a = 1\angle 120° = -\frac{1}{2} + j\frac{\sqrt3}{2}$$

Multiplying by $a$ turns a phasor 120° counterclockwise; by $a^2 = 1\angle 240° = 1\angle{-120°}$, 120° clockwise. Since $a$ is a cube root of 1 (lesson 8), $a^3 = 1$ and

$$1 + a + a^2 = 0$$

## Phase and line voltages

The three **phase voltages** (each line to neutral), in the usual order, are

$$V_a = V_p\angle 0° \qquad V_b = V_p\angle{-120°} = a^2V_a \qquad V_c = V_p\angle 120° = aV_a$$

The **line voltage** between two phases is their difference:

$$V_{ab} = V_a - V_b = V_p\big(1 - a^2\big) = \sqrt3\,V_p\angle 30°$$

So line voltages are $\sqrt3$ times the phase voltage and lead it by 30°. Common systems: 120/208 V in US commercial buildings, 277/480 V in US industry, 230/400 V in Europe.

## Balanced and unbalanced

In a **balanced** system the three currents are equal in size and 120° apart, so they add to zero: $I(1 + a + a^2) = 0$. That's why a balanced load needs no neutral current, and why three-phase lines can carry power with three wires instead of six.

If the loads differ, the neutral carries the sum $I_n = I_a + I_b + I_c$, worked out with phasors. For currents of sizes $I_1, I_2, I_3$ at the three phase angles, its size is

$$|I_n| = \sqrt{I_1^2 + I_2^2 + I_3^2 - I_1I_2 - I_2I_3 - I_3I_1}$$

**Power.** The total real power of a balanced load is $\sqrt3\,V_LI_L\cos\varphi$, with $V_L$ and $I_L$ the line voltage and current and $\cos\varphi$ the power factor.
:::

::: example
## Show that the line voltage of a 120 V system is 207.8 V at 30°.

::: solution
1. **Phase voltages in rectangular form.** $V_a = 120$, and
   $$\begin{aligned} V_b &= 120\angle{-120°} \\ &= 120(-0.5 - j0.866) \\ &= -60 - j103.9 \end{aligned}$$
2. **Line voltage.**
   $$\begin{aligned} V_{ab} &= 120 - (-60 - j103.9) \\ &= 180 + j103.9 \end{aligned}$$
3. **Its size.**
   $$\begin{aligned} |V_{ab}| &= \sqrt{180^2 + 103.9^2} \\ &= 207.8\ \text{V} \end{aligned}$$
4. **Its angle.**
   $$\tan^{-1}(103.9/180) = 30.0°$$

**Answer:** $V_{ab} = 180 + j103.9$, which is 207.8 V at 30.0°.
:::
:::

::: example
## The three phases of a building carry 10 A, 8 A and 6 A, each in phase with its own voltage. What current flows in the neutral?

::: solution
1. **Add the phase currents.**
   $$\begin{aligned} I_n &= 10 + 8\angle{-120°} + 6\angle 120° \\ &= 10 + (-4 - j6.928) \\ &\quad + (-3 + j5.196) \\ &= 3 - j1.732 \end{aligned}$$
   So $|I_n| = 3.46$ A.
2. **Check with the formula.**
   $$\begin{aligned} &\sqrt{100 + 64 + 36 - 80 - 48 - 60} \\ &= \sqrt{12} \\ &= 3.46\ \text{A} \end{aligned}$$
3. **Compare with the phases.** Even with this much imbalance, the neutral carries far less than any one phase.

**Answer:** 3.46 A flows in the neutral.
:::
:::

::: example
## A balanced three-phase motor on 480 V (line, RMS) draws 50 A per line at a power factor of 0.85. What real power does it take?

::: solution
1. **Use the balanced-load formula.**
   $$\begin{aligned} P &= \sqrt{3}V_LI_L\cos\varphi \\ &= 1.732 \times 480 \times 50 \times 0.85 \\ &= 35.3\ \text{kW} \end{aligned}$$
2. **Where the $\sqrt{3}$ comes from.** It comes from the line voltage being $\sqrt{3}$ times each phase voltage, so per phase the motor sees 50 A and
   $$480/\sqrt{3} = 277\ \text{V}$$
3. **Check per phase.** Three phases give the same total:
   $$\begin{aligned} &3 \times 277 \times 50 \times 0.85\ \text{W} \\ &= 35.3\ \text{kW} \end{aligned}$$

**Answer:** the motor takes 35.3 kW of real power.
:::
:::

::: check
given: Vp = 120 | 230 | 277
answer: sqrt(3)*Vp
unit: V

## The phase voltage of a three-phase system is {Vp} V. What is the line voltage?

::: right
Right. $\sqrt3 \times \given{Vp}$ = {answer}.
:::

::: misses
- [2*Vp] That's for phases 180° apart. Three-phase phases are 120° apart.
- [Vp/sqrt(3)] Line voltage is the bigger one.
- [any] Not yet. $V_L = \sqrt3\,V_p$.
:::
:::

::: check
given: VL = 208 | 400 | 480
answer: VL/sqrt(3)
unit: V

## A three-phase system has a line voltage of {VL} V. What is the voltage from each phase to neutral?

::: right
Right. $V_L/\sqrt3$ = {answer}.
:::

::: misses
- [VL/2] Divide by $\sqrt3$, not 2.
- [VL*sqrt(3)] Phase voltage is the smaller one.
- [any] Not yet. $V_p = V_L/\sqrt3$.
:::
:::

::: check
given: I1 = 10 | 15 | 20; I2 = 8 | 12; I3 = 4 | 9
answer: sqrt(I1^2 + I2^2 + I3^2 - I1*I2 - I2*I3 - I3*I1)
unit: A

## The three phases carry {I1} A, {I2} A and {I3} A, each in phase with its voltage. What is the neutral current?

::: right
Right. Adding the three phasors gives {answer}.
:::

::: misses
- [I1 + I2 + I3] They're 120° apart, so they mostly cancel. Add them as phasors.
- [0] Only a balanced load cancels completely.
- [any] Not yet. Add $\given{I1}\angle 0° + \given{I2}\angle{-120°} + \given{I3}\angle 120°$.
:::
:::

::: check
given: VL = 208 | 400 | 480; IL = 10 | 25 | 50; pf = 0.8 | 0.9
answer: sqrt(3)*VL*IL*pf
unit: W

## A balanced three-phase motor draws {IL} A per line at {VL} V line voltage with a power factor of {pf}. What real power does it take?

::: right
Right. $\sqrt3\,V_LI_L\cos\varphi$ = {answer}.
:::

::: misses
- [3*VL*IL*pf] With line voltages, the factor is $\sqrt3$, not 3.
- [sqrt(3)*VL*IL] Multiply by the power factor for real power.
- [any] Not yet. $P = \sqrt3\,V_LI_L\cos\varphi$.
:::
:::

::: check
given: n = 2 | 4 | 5 | 7
answer: cos(n*2*pi/3)
tolerance: 0.5%

## $a = 1\angle 120°$. What is the real part of $a^{\given{n}}$?

::: right
Right. $a^{\given{n}} = 1\angle(\given{n} \times 120°)$, with real part {answer}.
:::

::: misses
- [n*cos(2*pi/3)] Powers multiply the angle, not the real part.
- [any] Not yet. Multiply the angle by {n} and reduce by 360°.
:::
:::

::: check
kind: choice

## What is $1 + a + a^2$, with $a = 1\angle 120°$?

- [x] 0
- [ ] 3
- [ ] 1
- [ ] $\sqrt3$

::: right
Right. Three equal arrows 120° apart close into a triangle: they're the cube roots of 1, which add to zero.
:::

::: misses
- [any] Draw the three unit arrows at 0°, 120° and 240° tip to tail.
:::
:::

::: check
kind: parts
given: VL = 208 | 400 | 480; IL = 10 | 25; pf = 0.8 | 0.9

## A balanced three-phase load on {VL} V (line, RMS) draws {IL} A per line at a power factor of {pf}, lagging.

::: part
answer: VL/sqrt(3)
unit: V
tolerance: 0.5%

### What is the phase voltage?

::: misses
- [VL*sqrt(3)] The phase voltage is smaller than the line voltage.
- [any] $V_L/\sqrt{3}$.
:::
:::

::: part
answer: sqrt(3)*VL*IL*pf
unit: W
tolerance: 0.5%

### What real power does it take?

::: misses
- [3*VL*IL*pf] With line voltage, the factor is $\sqrt{3}$, not 3.
- [any] $\sqrt{3}V_LI_L\cos\varphi$.
:::
:::

::: part
answer: sqrt(3)*VL*IL*sqrt(1 - pf^2)
unit: var
tolerance: 0.5%

### What reactive power does it take?

::: misses
- [sqrt(3)*VL*IL*(1 - pf)] Use $\sin\varphi = \sqrt{1 - \cos^2\varphi}$.
- [any] $\sqrt{3}V_LI_L\sin\varphi$.
:::
:::
:::

::: check
kind: derivation
vars: V = 50..400

## Derive the line voltage between two phases, $V\angle 0°$ and $V\angle{-120°}$.

::: step
answer: 1.5*V

### What is the real part of $V\angle 0° - V\angle{-120°}$?
:::

::: step
answer: sqrt(3)*V/2

### What is its imaginary part?
:::

::: step
answer: sqrt(3)*V

### What is its length?
:::

::: right
Right. The line voltage is $\sqrt{3}V$ at 30°: 120 V phases give 208 V between lines.
:::
:::

::: explain
## Why can three-phase power be delivered with three wires, when three separate single-phase circuits would need six?

::: model
Each single-phase circuit needs a return wire. In a balanced three-phase system, the three return currents would be equal in size and 120° apart, so their phasors add to zero. A shared return wire would carry nothing, so it can be left out (or made small, to carry only the imbalance), and the three phase wires serve as each other's return.
:::
:::

::: practice

::: check
given: Vp = 127 | 240 | 347
answer: sqrt(3)*Vp
unit: V

## What line voltage goes with a {Vp} V phase voltage?

::: misses
- [2*Vp] Use $\sqrt3$.
- [any] $\sqrt3 V_p$.
:::
:::

::: check
given: I = 10 | 20; d = 2 | 5
answer: d
unit: A

## Phases a and b carry {I} A and phase c carries {I} A plus {d} A, all in phase with their voltages. What is the neutral current?

::: misses
- [0] The extra {d} A doesn't cancel.
- [any] The three equal parts cancel.
:::
:::

::: check
given: VL = 400 | 480; P = 10 | 50 | 100; pf = 0.85 | 0.95
answer: P*1000/(sqrt(3)*VL*pf)
unit: A

## A balanced {P} kW three-phase load at {VL} V line voltage has a power factor of {pf}. What line current does it draw?

::: misses
- [P*1000/(3*VL*pf)] The factor is $\sqrt3$ with line voltage.
- [P*1000/(sqrt(3)*VL)] Include the power factor.
- [any] $I_L = P/(\sqrt3 V_L\cos\varphi)$.
:::
:::

::: check
given: n = 3 | 6 | 8
answer: sin(n*2*pi/3)
tolerance: 0.01

## What is the imaginary part of $a^{\given{n}}$, with $a = 1\angle 120°$?

::: misses
- [any] Reduce $\given{n} \times 120°$ by whole turns.
:::
:::
:::