B150 of 56
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

B1 · Lesson 50 · Fluid flow

Continuity, Bernoulli, viscosity, and cooling airflow

A server pulls in cool air at the front and blows warm air out the back. How much air must its fans move to carry away 200 W without the air warming more than 10 °C? Water speeds up where a pipe narrows and its pressure drops, which is how a venturi flow meter works. And flow through a thin tube obeys a law that looks exactly like Ohm's: pressure difference equals flow times a resistance. Fluid flow is the physics behind every cooling system an electronics designer specifies.

  • Electronics dissipating power P are cooled by air flowing through their enclosure. The curve is how much the air warms on its way through, against the airflow.
  • Halve the airflow and the temperature rise doubles: the same heat goes into half as much air.
  • The readout converts the flow to cubic feet per minute (CFM), the unit fans are rated in.

Predict

Water flows at 2 m/s in a 4 cm pipe that narrows to 2 cm. How fast does it flow in the narrow part?

Name it

Continuity

For an incompressible fluid, the volume flow rate Q=Av is the same through every cross-section of a pipe:

A1v1=A2v2

Narrow sections run faster. This is the fluid version of Kirchhoff's current law: what flows in must flow out.

Bernoulli's equation

Along a streamline of steady flow, with no friction,

P+12ρv2+ρgh=constant

It's energy conservation per unit volume. Where the fluid speeds up, its pressure falls: the principle of venturi flow meters, airplane wings and the pressure drop across a fan's inlet.

Viscosity and pipe flow

Real fluids have viscosity η: water about 1.0×10−3 Pa·s, air about 1.8×10−5 Pa·s. Slow, smooth (laminar) flow through a tube of radius r and length L obeys Poiseuille's law:

Q=πr48ηLΔP⟺ΔP=RhQ,Rh=8ηLπr4

That's Ohm's law with pressure for voltage, flow for current and a hydraulic resistance that falls steeply with radius: halving the radius cuts the flow 16-fold. Hydraulic resistances add in series and combine like resistors in parallel, which is how cooling-plate channels and heat-sink fins are analyzed. Fast flow becomes turbulent, and then the pressure drop grows roughly with Q2.

Cooling with airflow

Air carrying away power P warms by

ΔT=PρcpQ

with ρcp≈1.2×1005=1210 J/(m³·K) for air near room conditions. Fans are rated in CFM: 1 CFM = 0.472 L/s. A fan delivers less than its free-air rating once the enclosure's resistance builds up back pressure; the operating point is where the fan curve meets the system's pressure-drop curve, just like a source driving a load.

Worked example

Electronics dissipate 200 W. How much airflow keeps the air's temperature rise to 10 °C?

Show the solution
  1. Airflow. Q=PρcpΔT=2001.2×1005×10=0.0166m3/s which is 16.6 L/s or 35 CFM.
  2. In practice. You'd pick fans rated well above that, since back pressure reduces their delivered flow.

Answer 0.0166 m³/s, which is 16.6 L/s or 35 CFM.

Worked example

Water at a 10 kPa pressure difference flows through a 1 m tube of 1 mm radius. What flow results, and what if the radius were 0.5 mm?

Show the solution
  1. Hydraulic resistance. Rh=8×10−3×1π(10−3)4=2.55×109Pa·s/m3
  2. Flow. Q=1042.55×109=3.9×10−6m3/s about 236 mL per minute.
  3. Half the radius. Halving the radius multiplies Rh by 16, leaving 15 mL per minute.

Answer about 236 mL per minute, and only 15 mL per minute with a 0.5 mm radius.

Worked example

A Venturi meter narrows a water pipe to a quarter of its area, and the pressure drops by 2 kPa in the throat. How fast is the water moving in the pipe?

Show the solution
  1. Continuity. A quarter of the area makes the throat speed 4v.
  2. Bernoulli. ΔP=12ρ((4v)2−v2)=152ρv2
  3. Solve for the speed. v=2×20001000×15=0.516m/s
  4. Using the meter. It has no moving parts: a pressure sensor across it measures flow. The square root means the reading's resolution worsens at low flow, where the pressure difference becomes tiny.

Answer the water moves at 0.516 m/s in the pipe.

Check

Water at 1 m/s in a 4 cm pipe flows into a 3 cm section. How fast does it move there?

Write units the way you normally would: 1.5 m/s, 1500 mm/s and 0.0015 km/s are the same answer.

Check

Level water speeds up from 1 m/s to 4 m/s through a narrowing. How much does its pressure drop?

Write units the way you normally would: 1.5 kPa, 1500 Pa and 0.0015 MPa are the same answer.

Check

Equipment dissipates 300 W. What airflow keeps the air's temperature rise to 5 °C?

Write units the way you normally would: 1.5 L/s and 1500 mL/s are the same answer.

Check

A fan pushes 10 L/s through an enclosure dissipating 150 W. How much does the air warm?

Check

A tube's radius is multiplied by 0.8, with the same length and pressure difference. By what factor does laminar flow change?

Check

Water (η = 10⁻³ Pa·s) flows through a tube 0.5 m long with radius 1 mm under a 5 kPa pressure difference. How many milliliters flow per minute?

Write units the way you normally would: 1.5 mL, 1500 µL and 0.0015 L are the same answer.

Check

A Venturi meter on a 5 cm water pipe narrows the area by a factor 2, and the pressure drops 1 kPa.

(a)

How fast does water move in the pipe?

Write units the way you normally would: 1.5 m/s, 1500 mm/s and 0.0015 km/s are the same answer.

(b)

What is the flow, in L/s?

Check

Water drains from a tank through a small hole a depth h below the surface.

Step 1

How fast does it leave (Torricelli)?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

How is laminar pipe flow like current through a resistor?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.