B4 · Lesson 12 · Electrical safety
Current through the body, grounding and ground-fault protection
"It's the current that matters, not the voltage" is half right. What harms the body is current through it, especially across the chest, but the current is set by the voltage and the body's resistance, which ranges from about 100 kΩ for dry skin to around 1 kΩ for wet. That spread is why 120 V can be a tingle or a killer. Every safety device in a building, from the third pin on a plug to the test button on a bathroom outlet, exists to keep that current small or to cut it off within milliseconds.
- The line is the current through a body touching a voltage, for the body resistance on the slider. The dashed lines mark rough thresholds for 50 to 60 Hz current: about 1 mA is felt, about 10 mA can make it impossible to let go, and around 100 mA can stop the heart.
- Drop the resistance from dry (100 kΩ) to wet (1 kΩ). Where does mains voltage land now?
- These are rough guides; actual harm depends on the current's path and how long it lasts.
Predict
A person with wet hands grips a 120 V conductor and a grounded pipe; their body resistance is about 1 kΩ. Roughly what current flows?
About 120 mA: , hand to hand across the chest, well into the range that can cause ventricular fibrillation. With dry skin, around 100 kΩ, the same contact gives about 1.2 mA, a tingle. Water lowers skin resistance enormously, which is why codes require ground-fault protection near sinks and outdoors.
Name it
The body as a resistor
Current through the body follows Ohm's law, . Most of the resistance is in the skin: roughly 100 kΩ dry, down to about 1 kΩ wet or broken; the inside of the body is only a few hundred ohms. Rough effects of 50 to 60 Hz current, for a second or so, hand to hand:
| Current | Effect |
|---|---|
| about 1 mA | just felt |
| about 10 mA | muscles clamp; may be unable to let go |
| about 100 mA | can trigger ventricular fibrillation |
Higher frequencies are felt less; DC is somewhat less likely to cause fibrillation but causes burns and clamping too.
Grounding
A metal appliance case is bonded to the ground pin. If a live wire touches the case, the fault current flows through a low-resistance path to ground, large enough to blow the fuse or trip the breaker at once, instead of waiting for a person to complete the circuit.
Ground-fault interrupters
A GFCI (or residual-current device, RCD) compares the current going out on the hot wire with the current returning on neutral. Normally they're equal. If some current takes another path, through a person to ground, the difference trips it, typically at about 5 mA in North America (30 mA is common for RCDs elsewhere) within tens of milliseconds. It protects even when the person touches only one wire, which a fuse can't do.
Stored energy
Capacitors stay charged after power is removed. Equipment adds a bleeder resistor so the voltage decays as ; check with a meter before touching.
Worked example
A GFCI sees 10.000 A leaving on the hot wire and 9.994 A returning on neutral. What does it do?
Show the solution
- Find the missing current. The missing 6 mA is flowing some other way, perhaps through a person.
- Compare with the trip threshold. That's above a 5 mA trip threshold, so it opens the circuit, typically within a few tens of milliseconds.
- A breaker. A 15 A breaker would never notice: 6 mA is 0.04% of its rating.
Answer it opens the circuit, typically within a few tens of milliseconds.
Worked example
A 100 µF capacitor in a power supply is charged to 400 V. How much energy does it hold, and how long does a 100 kΩ bleeder take to bring it below 50 V?
Show the solution
- Stored energy. enough for a dangerous shock.
- Time constant.
- Time to fall to 50 V.
Answer the capacitor holds 8 J, and the bleeder takes 21 s to bring it below 50 V.
Check
A body with 1 kΩ of resistance contacts 120 V. What current flows?
Write units the way you normally would: 1.5 mA, 1500 µA and 0.0015 A are the same answer.
Check
A circuit's hot wire carries 10 A out, and the neutral returns 10 A minus 3 mA. How much current is leaking another way?
Write units the way you normally would: 1.5 mA, 1500 µA and 0.0015 A are the same answer.
Check
A 47 µF capacitor is charged to 170 V. How much energy does it hold?
Write units the way you normally would: 1.5 J, 1500 mJ and 0.0015 kJ are the same answer.
Check
A 47 µF capacitor at 400 V discharges through a 47 kΩ bleeder. How long until it's below 50 V?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A live wire touches a grounded metal case; the fault path has 0.1 Ω in total. What fault current flows from the 120 V supply?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Why does a GFCI protect someone who touches only the hot wire while standing on the ground, when a fuse wouldn't?
Explain why
Why is a grounded metal case safer than an ungrounded one when a fault occurs?
If a live wire touches an ungrounded metal case, the case sits at mains voltage, harmlessly until someone touches it and a grounded object at the same time; then the current flows through them. With the case bonded to ground, the same fault drives a huge current through the low-resistance ground path, which blows the fuse or trips the breaker almost immediately. The case is held near ground during the brief fault, and then the supply is cut off before anyone touches it.
Practice
Keep practicing
8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.