title: Electrical safety
heading: Current through the body, grounding and ground-fault protection
eyebrow: B4 · Lesson 12 · Electrical safety
xp: 40
---

::: hook
"It's the current that matters, not the voltage" is half right. What harms the body is current through it, especially across the chest, but the current is set by the voltage and the body's resistance, which ranges from about 100 kΩ for dry skin to around 1 kΩ for wet. That spread is why 120 V can be a tingle or a killer. Every safety device in a building, from the third pin on a plug to the test button on a bathroom outlet, exists to keep that current small or to cut it off within milliseconds.
:::

::: play
- The line is the current through a body touching a voltage, for the body resistance on the slider. The dashed lines mark rough thresholds for 50 to 60 Hz current: about 1 mA is felt, about 10 mA can make it impossible to let go, and around 100 mA can stop the heart.
- Drop the resistance from dry (100 kΩ) to wet (1 kΩ). Where does mains voltage land now?
- These are rough guides; actual harm depends on the current's path and how long it lasts.
:::
:::

```sim plot
view: graph
x: V = 0..250 V
y: I = 0.1..1000 mA log
slider: R = 1..100 = 10 kΩ log
slider: V0 = 0..250 step 5 = 120 V
plot: V/R | label: body current
plot: 1 + 0*V | label: felt, about 1 mA | dashed | color: ch2
plot: 10 + 0*V | label: can't let go, about 10 mA | dashed | color: ch3
plot: 100 + 0*V | label: heart danger, about 100 mA | dashed | color: ch4
marker: x = V0 | label: voltage
readout: current at that voltage, mA = V0/R | digits: 3
```

::: predict
## A person with wet hands grips a 120 V conductor and a grounded pipe; their body resistance is about 1 kΩ. Roughly what current flows?

- [ ] 1 mA, barely felt
- [ ] 12 mA
- [x] About 120 mA, in the range that can stop the heart
- [ ] 120 A

::: reveal
About 120 mA: $\frac{120\text{ V}}{1\text{ kΩ}}$, hand to hand across the chest, well into the range that can cause ventricular fibrillation. With dry skin, around 100 kΩ, the same contact gives about 1.2 mA, a tingle. Water lowers skin resistance enormously, which is why codes require ground-fault protection near sinks and outdoors.
:::
:::

::: nameit
## The body as a resistor

Current through the body follows Ohm's law, $I = \frac{V}{R_\text{body}}$. Most of the resistance is in the skin: roughly 100 kΩ dry, down to about 1 kΩ wet or broken; the inside of the body is only a few hundred ohms. Rough effects of 50 to 60 Hz current, for a second or so, hand to hand:

| Current | Effect |
|---|---|
| about 1 mA | just felt |
| about 10 mA | muscles clamp; may be unable to let go |
| about 100 mA | can trigger ventricular fibrillation |

Higher frequencies are felt less; DC is somewhat less likely to cause fibrillation but causes burns and clamping too.

## Grounding

A metal appliance case is bonded to the ground pin. If a live wire touches the case, the fault current flows through a low-resistance path to ground, large enough to blow the fuse or trip the breaker at once, instead of waiting for a person to complete the circuit.

## Ground-fault interrupters

A **GFCI** (or residual-current device, RCD) compares the current going out on the hot wire with the current returning on neutral. Normally they're equal. If some current takes another path, through a person to ground, the difference trips it, typically at about 5 mA in North America (30 mA is common for RCDs elsewhere) within tens of milliseconds. It protects even when the person touches only one wire, which a fuse can't do.

## Stored energy

Capacitors stay charged after power is removed. Equipment adds a **bleeder resistor** so the voltage decays as $V_0e^{-t/RC}$; check with a meter before touching.
:::

::: example
## A GFCI sees 10.000 A leaving on the hot wire and 9.994 A returning on neutral. What does it do?

::: solution
1. **Find the missing current.**
   $$10.000 - 9.994 = 0.006\ \text{A}$$
   The missing 6 mA is flowing some other way, perhaps through a person.
2. **Compare with the trip threshold.** That's above a 5 mA trip threshold, so it opens the circuit, typically within a few tens of milliseconds.
3. **A breaker.** A 15 A breaker would never notice: 6 mA is 0.04% of its rating.

**Answer:** it opens the circuit, typically within a few tens of milliseconds.
:::
:::

::: example
## A 100 µF capacitor in a power supply is charged to 400 V. How much energy does it hold, and how long does a 100 kΩ bleeder take to bring it below 50 V?

::: solution
1. **Stored energy.**
   $$\begin{aligned} W &= \frac12CV^2 \\ &= \frac12 \times 10^{-4} \times 400^2 \\ &= 8\ \text{J} \end{aligned}$$
   enough for a dangerous shock.
2. **Time constant.**
   $$\begin{aligned} \tau &= RC \\ &= 10\ \text{s} \end{aligned}$$
3. **Time to fall to 50 V.**
   $$\begin{aligned} t &= \tau\ln\frac{400}{50} \\ &= 21\ \text{s} \end{aligned}$$

**Answer:** the capacitor holds 8 J, and the bleeder takes 21 s to bring it below 50 V.
:::
:::

::: check
given: V = 24 | 120 | 230; R = 1 | 10 | 100
answer: V/R
unit: mA
tolerance: 0.5%

## A body with {R} kΩ of resistance contacts {V} V. What current flows?

::: right
Right. $V/R$ = {answer}.
:::

::: misses
- [V/(R*1000)] Keep the units straight: volts over kilohms gives milliamps.
- [any] Not yet. Ohm's law.
:::
:::

::: check
given: Ih = 5 | 10 | 15; d = 3 | 8
answer: d
unit: mA
tolerance: 0.5%

## A circuit's hot wire carries {Ih} A out, and the neutral returns {Ih} A minus {d} mA. How much current is leaking another way?

::: right
Right. The difference, {answer}; a 5 mA GFCI would trip if it's above that.
:::

::: misses
- [any] Not yet. Out minus back.
:::
:::

::: check
given: C = 47 | 470; V = 170 | 400
answer: 0.5*C*1e-6*V^2
unit: J
tolerance: 0.5%

## A {C} µF capacitor is charged to {V} V. How much energy does it hold?

::: right
Right. $\frac12CV^2$ = {answer}.
:::

::: misses
- [C*1e-6*V^2] Include the $\frac12$.
- [any] Not yet. $\frac12CV^2$.
:::
:::

::: check
given: C = 47 | 470; R = 47 | 220; V0 = 200 | 400; Vs = 30 | 50
answer: R*1000*C*1e-6*ln(V0/Vs)
unit: s
tolerance: 0.5%

## A {C} µF capacitor at {V0} V discharges through a {R} kΩ bleeder. How long until it's below {Vs} V?

::: right
Right. $RC\ln\frac{V_0}{V}$ = {answer}.
:::

::: misses
- [R*1000*C*1e-6] One time constant only reaches 37%.
- [any] Not yet. Solve $V_0e^{-t/RC} = V$.
:::
:::

::: check
given: V = 120 | 230; R = 0.1 | 0.5
answer: V/R
unit: A
tolerance: 0.5%

## A live wire touches a grounded metal case; the fault path has {R} Ω in total. What fault current flows from the {V} V supply?

::: right
Right. {answer}: far above any breaker rating, so it trips at once.
:::

::: misses
- [any] Not yet. $V/R$ around the fault loop.
:::
:::

::: check
kind: choice

## Why does a GFCI protect someone who touches only the hot wire while standing on the ground, when a fuse wouldn't?

- [x] It trips on a few milliamps of imbalance between hot and neutral, far below what blows a fuse
- [ ] It limits the voltage to a safe level
- [ ] It disconnects the ground wire
- [ ] Fuses only work on DC

::: right
Right. The current through the person never returns on neutral, so the GFCI sees the imbalance; a fuse only sees total current, which barely changes.
:::

::: misses
- [2] It doesn't change the voltage; it cuts the circuit off.
- [3] Disconnecting ground would make things less safe.
- [4] Fuses work on AC and DC alike; they just need far more current to blow.
:::
:::

::: explain
## Why is a grounded metal case safer than an ungrounded one when a fault occurs?

::: model
If a live wire touches an ungrounded metal case, the case sits at mains voltage, harmlessly until someone touches it and a grounded object at the same time; then the current flows through them. With the case bonded to ground, the same fault drives a huge current through the low-resistance ground path, which blows the fuse or trips the breaker almost immediately. The case is held near ground during the brief fault, and then the supply is cut off before anyone touches it.
:::
:::

::: practice

::: check
given: I = 1 | 5 | 10 | 20 | 30 | 50 | 100
answer: 120/(I/1000)/1000
unit: kΩ
tolerance: 0.5%

## What body resistance would let {I} mA flow from 120 V?

::: misses
- [any] $R = V/I$.
:::
:::

::: check
given: R = 10 | 47; C = 100 | 220
answer: R*1000*C*1e-6
unit: s
tolerance: 0.5%

## What time constant does a {R} kΩ bleeder give a {C} µF capacitor?

::: misses
- [any] $\tau = RC$.
:::
:::

::: check
given: V0 = 50 | 100 | 300 | 400 | 600 | 1000
answer: V0*exp(-3)
unit: V
tolerance: 0.5%

## A capacitor at {V0} V bleeds down for three time constants. What voltage is left?

::: misses
- [any] $V_0e^{-3}$.
:::
:::
:::