B4 · Lesson 4 · Non-uniform resistance
Tapers, leakage through insulation, and ground rods
works for a straight wire. But current leaking through a cable's insulation flows outward, through ever-wider shells. Current from a lightning-protection ground rod spreads into the soil in all directions, and the ground near the rod rises to a dangerous voltage during a fault: a cow standing nearby can be killed by the difference between its front and back legs. These need the same idea as continuous charge did: cut the conductor into thin slices along the current's path, and add up their resistances.
- A fault current flows into the soil through a hemispherical ground electrode of radius . The curve is the ground's voltage against distance from the electrode's center.
- The voltage falls fastest near the electrode. The readouts give the electrode's resistance to "remote earth" and the step voltage between two points 1 m apart, 2 m and 3 m out.
- Make the soil wetter (lower ρ): what happens to the electrode's voltage and to the step voltage?
Predict
Current leaks radially from the inner conductor of a coax to its shield, through the insulation. Which layer of insulation contributes the most resistance?
The shells near the inner conductor. Every shell has the same thickness for a given step in radius, but near the center its area, , is smallest, so the current is squeezed through a small cross-section there. That's why the result has : resistance piles up near the inner conductor and grows only slowly with the outer radius.
Name it
Slicing along the current
Cut the conductor into slices perpendicular to the current, each of thickness and area . The slices are in series, so
This works when the current spreads in a known pattern: along a taper, outward from a cylinder, outward from a sphere.
| Shape | Resistance |
|---|---|
| cone frustum, length , end radii and | |
| between coaxial cylinders, radii , length (leakage) | |
| from a buried hemisphere of radius to far away |
Capacitance and resistance share a shape
For the same pair of electrodes, a capacitor filled with permittivity ε and a resistor filled with resistivity ρ have the same geometry factor, so
The leakage time constant depends only on the material. Coax insulation with Ω·m holds charge for hours.
Ground electrodes
Current entering soil of resistivity ρ through a hemisphere spreads radially, and the potential at distance is
During a fault the whole electrode rises to , and the ground surface carries a falling voltage gradient. The step voltage between two feet a pace apart, and the touch voltage between a grounded object and the ground where someone stands, are what electrical codes limit. Lower soil resistivity, longer rods, and grids of buried conductors all reduce them.
Worked example
A 100 m coax has polyethylene insulation ( Ω·m) between radii of 0.45 mm and 1.47 mm. What is its leakage resistance?
Show the solution
- Leakage resistance.
- Longer cables. Leakage resistance falls as the cable gets longer, since more insulation is in parallel.
Answer the leakage resistance is about Ω.
Worked example
A hemispherical ground electrode of radius 0.5 m sits in 100 Ω·m soil. A 100 A fault flows. Find the electrode's resistance and voltage, and the step voltage between 2 m and 3 m from its center.
Show the solution
- Electrode resistance.
- Electrode voltage.
- Step voltage. enough to be dangerous.
Answer the electrode has 31.8 Ω and rises to 3180 V, and the step voltage between 2 m and 3 m is 265 V.
Check
A 100 m cable's insulation (ρ = 1 × 10¹⁴ Ω·m) fills the space between radii 0.3 mm and 2 mm. What is its leakage resistance, in teraohms?
Write units the way you normally would: 1.5 TΩ, 1500 GΩ and 0.0015 PΩ are the same answer.
Check
A hemispherical ground electrode of radius 0.3 m sits in soil of 100 Ω·m. What is its resistance to remote earth?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A fault puts 20 A into soil of 50 Ω·m through a ground electrode. What is the ground's voltage 5 m from the electrode's center?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
For the same fault (20 A into 50 Ω·m soil), what is the step voltage between points 2 m and 1 m farther from the electrode?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A tapered conductor 1 cm long narrows from radius 2 mm to 0.5 mm, with resistivity 1.72 × 10⁻⁸ Ω·m. What is its resistance?
Write units the way you normally would: 1.5 mΩ, 1500 µΩ and 0.0015 Ω are the same answer.
Check
A capacitor's dielectric has = 2.25 and resistivity 1 × 10¹³ Ω·m. Charged and left alone, what is its self-discharge time constant, in hours?
Explain why
Why does a ground rod's resistance come mostly from the soil close to it?
Current leaving the electrode spreads through hemispherical shells of soil, and each shell's resistance is its thickness times ρ divided by its area. Close to the electrode the shells are small, so the current is crowded and each shell resists a lot. Far away the shells are enormous and contribute almost nothing. Adding them up, half the total resistance lies within twice the electrode's radius. That's why improving the soil right around a rod, or using a bigger electrode, lowers the resistance so much.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.