B4 · Lesson 9 · Wire sizing and fuses
Choosing a wire that won't sag or overheat, and the fuse that protects it
A 12 V LED strip draws 5 A, five meters from its supply. Wire it with thin 18-gauge cable and the far end dims: the wire alone eats about 9% of the voltage, and turns 5 W into heat. Every power cable is a resistor in series with the load, and choosing one means balancing two limits: the voltage it drops, and the heat it can shed before its insulation suffers. Then a fuse or breaker is sized to open before the wire overheats in a fault.
- A load draws current from a supply , at the end of a cable run of length (so of copper, out and back).
- The curve is the voltage drop, as a percentage of the supply, against wire gauge. Higher AWG numbers are thinner wires.
- The dashed line is a common design limit, 3%. Which is the thinnest gauge that stays under it?
Predict
A 5 A load sits 5 m from a 12 V supply, wired in 18 AWG (21 Ω per km). About what fraction of the voltage does the cable drop?
About 9%. The current runs out and back, through 10 m of wire: Ω, which drops V out of 12. Low-voltage, high-current wiring is where voltage drop bites hardest; the same load at 120 V would draw a tenth the current and lose under 1%.
Name it
Voltage drop
A cable run of length has of conductor, out and back. With cross-section :
The cable also dissipates as heat. Designs commonly keep the drop below 3 to 5% of the supply.
Wire gauges
American Wire Gauge numbers run backward: bigger numbers are thinner. The diameter of gauge is
Every 6 gauges halves the diameter; every 3 gauges halves the area and doubles the resistance.
| AWG | Diameter | Area | Copper resistance |
|---|---|---|---|
| 10 | 2.59 mm | 5.26 mm² | 3.3 Ω/km |
| 12 | 2.05 mm | 3.31 mm² | 5.2 Ω/km |
| 14 | 1.63 mm | 2.08 mm² | 8.3 Ω/km |
| 18 | 1.02 mm | 0.82 mm² | 21 Ω/km |
| 22 | 0.64 mm | 0.33 mm² | 53 Ω/km |
Heating and ampacity
A wire's temperature rises until it sheds its heat as fast as it makes it. How much current it can carry, its ampacity, depends on the insulation's temperature rating, bundling, and airflow; electrical codes tabulate it. The heat per meter goes as , so the current a wire can carry grows more slowly than its area.
Fuses and breakers
A fuse is a deliberately weak link that melts when its current is too high for too long. Its melting depends on (its "I²t"), so a brief inrush passes but a sustained overload doesn't. The rule: the fuse protects the wire, so it's rated at or below the wire's ampacity, and must open faster than the wire's insulation can be damaged.
Worked example
The 12 V, 5 A load 5 m away: compare 18 AWG with 14 AWG.
Show the solution
- 18 AWG. 10 m at 21 Ω/km is 0.21 Ω, dropping 1.05 V (8.7%) and wasting 5.2 W.
- 14 AWG. 10 m at 8.3 Ω/km is 0.083 Ω, dropping 0.41 V (3.4%) and wasting 2.1 W.
- Compare. Going up four gauges cut the loss by 60%.
Answer 18 AWG drops 1.05 V (8.7%) and wastes 5.2 W; 14 AWG drops 0.41 V (3.4%) and wastes 2.1 W, 60% less.
Worked example
What diameter does 12 AWG have, and how much resistance does 30 m of it have?
Show the solution
- Diameter.
- Area. mm².
- Resistance of 30 m.
Answer 12 AWG is 2.05 mm across, and 30 m of it has 0.156 Ω.
Check
A load draws 2 A at the end of a 3 m run of copper cable with 2.08 mm² conductors. What voltage does the cable drop?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
What is the diameter of 16 AWG wire?
Write units the way you normally would: 1.5 mm, 1500 µm and 0.0015 m are the same answer.
Check
A wire is replaced by one 5 gauges thinner. By what factor does its resistance per meter grow?
Check
A cable of 0.05 Ω total carries 3 A. How much heat does it dissipate?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A 24 V load draws 5 A at the end of a 10 m run. What copper cross-section keeps the drop to 5%?
Check
A wire's current rises from 10 A to 2 times that. By what factor does its heating per meter grow?
Explain why
Why does a fuse protect the wire rather than the device plugged into it?
A fault, such as a short inside an appliance, can draw far more current than the wiring was sized for. The wire then heats as , and its insulation can melt or start a fire long before anything else gives way. The fuse is rated for what the wire can carry safely, so it opens before the wire overheats, whatever is plugged in. Protecting a particular device takes its own, smaller fuse inside it, matched to that device's current.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.