title: Wire sizing, voltage drop and fuses
heading: Choosing a wire that won't sag or overheat, and the fuse that protects it
eyebrow: B4 · Lesson 9 · Wire sizing and fuses
xp: 40
---

::: hook
A 12 V LED strip draws 5 A, five meters from its supply. Wire it with thin 18-gauge cable and the far end dims: the wire alone eats about 9% of the voltage, and turns 5 W into heat. Every power cable is a resistor in series with the load, and choosing one means balancing two limits: the voltage it drops, and the heat it can shed before its insulation suffers. Then a fuse or breaker is sized to open before the wire overheats in a fault.
:::

::: play
- A load draws current $I$ from a supply $V$, at the end of a cable run of length $L$ (so $2L$ of copper, out and back).
- The curve is the voltage drop, as a percentage of the supply, against wire gauge. Higher AWG numbers are thinner wires.
- The dashed line is a common design limit, 3%. Which is the thinnest gauge that stays under it?
:::
:::

```sim plot
view: graph
x: n = 8..26
y: d = 0..30 %
slider: I = 0.5..20 step 0.5 = 5 A
slider: L = 1..20 step 0.5 = 5 m
slider: V = 5..48 step 1 = 12 V
slider: n0 = 8..26 step 1 = 18
plot: 100*I*1.72e-8*2*L/(pi*(0.127e-3*92^((36 - n)/39)/2)^2)/V | label: voltage drop
plot: 3 + 0*n | label: 3% limit | dashed | color: ch2
marker: x = n0 | label: gauge
readout: wire diameter, mm = 0.127*92^((36 - n0)/39) | digits: 3
readout: drop at that gauge, % = 100*I*1.72e-8*2*L/(pi*(0.127e-3*92^((36 - n0)/39)/2)^2)/V | digits: 3
readout: heat in the wire, W = I^2*1.72e-8*2*L/(pi*(0.127e-3*92^((36 - n0)/39)/2)^2) | digits: 3
```

::: predict
## A 5 A load sits 5 m from a 12 V supply, wired in 18 AWG (21 Ω per km). About what fraction of the voltage does the cable drop?

- [ ] 1%
- [ ] 4%
- [x] 9%
- [ ] 20%

::: reveal
About 9%. The current runs out and back, through 10 m of wire: $0.021 \times 10 = 0.21$ Ω, which drops $5 \times 0.21 = 1.05$ V out of 12. Low-voltage, high-current wiring is where voltage drop bites hardest; the same load at 120 V would draw a tenth the current and lose under 1%.
:::
:::

::: nameit
## Voltage drop

A cable run of length $L$ has $2L$ of conductor, out and back. With cross-section $A$:

$$R_\text{cable} = \frac{2\rho L}{A} \qquad V_\text{drop} = IR_\text{cable}$$

The cable also dissipates $I^2R_\text{cable}$ as heat. Designs commonly keep the drop below 3 to 5% of the supply.

## Wire gauges

American Wire Gauge numbers run backward: bigger numbers are thinner. The diameter of gauge $n$ is

$$d_n = 0.127\text{ mm} \times 92^{(36 - n)/39}$$

Every 6 gauges halves the diameter; every 3 gauges halves the area and doubles the resistance.

| AWG | Diameter | Area | Copper resistance |
|---|---|---|---|
| 10 | 2.59 mm | 5.26 mm² | 3.3 Ω/km |
| 12 | 2.05 mm | 3.31 mm² | 5.2 Ω/km |
| 14 | 1.63 mm | 2.08 mm² | 8.3 Ω/km |
| 18 | 1.02 mm | 0.82 mm² | 21 Ω/km |
| 22 | 0.64 mm | 0.33 mm² | 53 Ω/km |

## Heating and ampacity

A wire's temperature rises until it sheds its $I^2R$ heat as fast as it makes it. How much current it can carry, its **ampacity**, depends on the insulation's temperature rating, bundling, and airflow; electrical codes tabulate it. The heat per meter goes as $I^2/A$, so the current a wire can carry grows more slowly than its area.

## Fuses and breakers

A fuse is a deliberately weak link that melts when its current is too high for too long. Its melting depends on $\int i^2\,dt$ (its "I²t"), so a brief inrush passes but a sustained overload doesn't. The rule: **the fuse protects the wire**, so it's rated at or below the wire's ampacity, and must open faster than the wire's insulation can be damaged.
:::

::: example
## The 12 V, 5 A load 5 m away: compare 18 AWG with 14 AWG.

::: solution
1. **18 AWG.** 10 m at 21 Ω/km is 0.21 Ω, dropping 1.05 V (8.7%) and wasting 5.2 W.
2. **14 AWG.** 10 m at 8.3 Ω/km is 0.083 Ω, dropping 0.41 V (3.4%) and wasting 2.1 W.
3. **Compare.** Going up four gauges cut the loss by 60%.

**Answer:** 18 AWG drops 1.05 V (8.7%) and wastes 5.2 W; 14 AWG drops 0.41 V (3.4%) and wastes 2.1 W, 60% less.
:::
:::

::: example
## What diameter does 12 AWG have, and how much resistance does 30 m of it have?

::: solution
1. **Diameter.**
   $$\begin{aligned} d &= 0.127 \times 92^{24/39} \\ &= 2.05\ \text{mm} \end{aligned}$$
2. **Area.** $A = 3.31$ mm².
3. **Resistance of 30 m.**
   $$\begin{aligned} R &= \frac{1.72 \times 10^{-8} \times 30}{3.31 \times 10^{-6}} \\ &= 0.156\ \Omega \end{aligned}$$

**Answer:** 12 AWG is 2.05 mm across, and 30 m of it has 0.156 Ω.
:::
:::

::: check
given: I = 2 | 10; L = 3 | 10; A = 0.82 | 2.08
answer: I*1.72e-8*2*L/(A*1e-6)
unit: V
tolerance: 0.5%

## A load draws {I} A at the end of a {L} m run of copper cable with {A} mm² conductors. What voltage does the cable drop?

::: right
Right. $I\frac{2\rho L}{A}$ = {answer}.
:::

::: misses
- [I*1.72e-8*L/(A*1e-6)] The current goes out and back: $2L$.
- [any] Not yet. Cable resistance times current.
:::
:::

::: check
given: n = 10 | 16 | 22
answer: 0.127*92^((36 - n)/39)
unit: mm
tolerance: 0.5%

## What is the diameter of {n} AWG wire?

::: right
Right. $0.127 \times 92^{(36 - n)/39}$ = {answer}.
:::

::: misses
- [any] Not yet. $d_n = 0.127\text{ mm} \times 92^{(36 - n)/39}$.
:::
:::

::: check
given: k = 1..12 int
answer: 2^(k/3)
tolerance: 0.5%

## A wire is replaced by one {k} gauges thinner. By what factor does its resistance per meter grow?

::: right
Right. Every 3 gauges doubles it: {answer}.
:::

::: misses
- [2^(k/6)] Every 6 gauges halves the diameter, which quarters the area.
- [any] Not yet. Area halves every 3 gauges.
:::
:::

::: check
given: I = 3 | 8; R = 0.05 | 0.2
answer: I^2*R
unit: W
tolerance: 0.5%

## A cable of {R} Ω total carries {I} A. How much heat does it dissipate?

::: right
Right. $I^2R$ = {answer}.
:::

::: misses
- [I*R] That's the voltage drop.
- [any] Not yet. $P = I^2R$.
:::
:::

::: check
given: V = 12 | 24 | 48; I = 5 | 10; L = 5 | 10; p = 3 | 5
answer: 2*1.72e-8*L*I/(p/100*V)*1e6
unit: mm²
tolerance: 0.5%

## A {V} V load draws {I} A at the end of a {L} m run. What copper cross-section keeps the drop to {p}%?

::: right
Right. $A = \frac{2\rho LI}{(p/100)V}$ = {answer}.
:::

::: misses
- [1.72e-8*L*I/(p/100*V)*1e6] Count both conductors: $2L$.
- [any] Not yet. Set $I\frac{2\rho L}{A} = \frac{p}{100}V$.
:::
:::

::: check
given: I1 = 10 | 20; k = 2 | 3
answer: k^2
tolerance: 0.5%

## A wire's current rises from {I1} A to {k} times that. By what factor does its heating per meter grow?

::: right
Right. Heat goes as $I^2$: {answer}.
:::

::: misses
- [k] Heat is $I^2R$, not $IR$.
- [any] Not yet. $P \propto I^2$.
:::
:::

::: explain
## Why does a fuse protect the wire rather than the device plugged into it?

::: model
A fault, such as a short inside an appliance, can draw far more current than the wiring was sized for. The wire then heats as $I^2R$, and its insulation can melt or start a fire long before anything else gives way. The fuse is rated for what the wire can carry safely, so it opens before the wire overheats, whatever is plugged in. Protecting a particular device takes its own, smaller fuse inside it, matched to that device's current.
:::
:::

::: practice

::: check
given: L = 10 | 50; A = 1.5 | 2.5
answer: 1.72e-8*L/(A*1e-6)
unit: Ω
tolerance: 0.5%

## What is the resistance of {L} m of copper wire with {A} mm² cross-section?

::: misses
- [any] $\rho L/A$.
:::
:::

::: check
given: Vd = 0.3 | 0.8; V = 12 | 24
answer: 100*Vd/V
tolerance: 0.5%

## A cable drops {Vd} V from a {V} V supply. What percentage is that?

::: misses
- [any] Drop over supply.
:::
:::

::: check
given: d = 0.5 | 0.8 | 1 | 1.3 | 1.6 | 2
answer: d/2
unit: mm
tolerance: 0.5%

## A wire is {d} mm across. What is the diameter of a wire 6 gauges thinner?

::: misses
- [any] Six gauges halves the diameter.
:::
:::
:::