B6 · Lesson 10 · Mutual inductance and transformers

Two coils sharing one magnetic field

Wind two coils on the same iron core. Alternating current in the first makes a changing flux in the core, and that same flux threads the second coil, inducing a voltage there, with no electrical connection between them. Change the number of turns and you change the voltage: up for transmission, down for your phone charger. Transformers are why the grid uses AC, and why a power supply can be safely isolated from the mains.

Play

  • A sine wave drives the primary coil of N1 turns; the secondary has N2 turns. The graph shows both voltages.
  • Make N2 larger than N1. What happens to the secondary voltage? Make it smaller.
  • The readout gives the secondary current for a load of RL. How does it compare with the primary current?

Predict

A transformer steps 230 V down to 23 V. If the secondary delivers 2 A, roughly what current does the primary draw (ignoring losses)?

Name it

Mutual inductance

Coupled coils. Current i1 in one coil makes flux that partly threads a second coil. The mutual inductance M says how much: the voltage induced in coil 2 is

v2=Mdi1dt

and it works the same way back, from coil 2 to coil 1. How much of one coil's flux reaches the other is the coupling coefficient k, with M=kL1L2 and 0≤k≤1. Coils on a shared iron core reach k>0.99; coils that just sit near each other might have k of a few percent.

The ideal transformer

With perfect coupling, the same changing flux Φ threads every turn of both coils, so each turn has the same voltage dΦ/dt induced in it:

V2V1=N2N1

With no losses, power in equals power out, V1I1=V2I2, so

I2I1=N1N2

A load RL on the secondary looks, from the primary, like a resistance (N1/N2)2RL. Audio output transformers and RF baluns use this impedance transformation to match a load to a source.

Only AC. A transformer needs a changing flux. Feed DC into its primary and nothing appears at the secondary (after the switch-on transient), while the primary current climbs until something overheats.

Real transformers lose a few percent: resistance in the windings (copper loss), hysteresis and eddy currents in the core (iron loss, kept down by laminating the core into thin insulated sheets), and imperfect coupling (leakage inductance). Large power transformers are over 99% efficient.

Isolation. The secondary has no electrical connection to the primary, only a magnetic one. That's what makes a mains adapter safe to touch at its output.

Worked example

A transformer steps 230 V down to 12 V. What turns ratio does it need, and what primary current flows when the secondary supplies 2 A?

Show the solution
  1. Turns ratio. NpNs=23012=19.2
  2. Primary current. Power in equals power out for an ideal transformer: Ip=2×12230=0.10A

Answer the transformer needs a turns ratio of 19.2, and 0.10 A flows in the primary.

Worked example

An 8 Ω speaker is driven through a 10:1 transformer. What resistance does the amplifier see?

Show the solution
  1. Reflected resistance. R′=8×102=800Ω
  2. Why the square. Transformers match loads to sources by the square of their turns ratio.

Answer the amplifier sees 800 Ω.

Check

A transformer with 200 primary turns and 70 secondary turns is fed 230 V. What does the secondary give?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

Check

An ideal transformer steps 230 V down to 5 V and delivers 5 A. What current does its primary draw?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A transformer with a turns ratio N1:N2 = 5:1 has a 4 Ω load on its secondary. What resistance does the primary see?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

Two coils of 1 mH and 16 mH have a coupling coefficient of 0.5. What is their mutual inductance?

Write units the way you normally would: 1.5 mH, 1500 µH and 0.0015 H are the same answer.

Check

A transformer's primary is connected to a 12 V battery. After the first instant, what does the secondary show?

Check

A transformer has 500 primary and 100 secondary turns, 120 V on the primary and a 16 Ω load.

(a)

What is the secondary voltage?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

(b)

What resistance does the primary see?

Explain why

Why does an ideal transformer's secondary current go down when its voltage goes up?

Practice

Keep practicing

8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.