title: Bridges and resistive sensors
heading: Measuring tiny changes in resistance with a Wheatstone bridge
eyebrow: C1 · Lesson 22 · Bridges and sensors
xp: 40
---

::: hook
A strain gauge glued to a steel beam changes its resistance by 0.2% when the beam stretches a thousandth of its length. Measured directly, that's 0.7 Ω out of 350, hard to see against the gauge's own tolerance and its drift with temperature. Put the gauge in a Wheatstone bridge and the 350 Ω disappears: the bridge's output is zero at rest and responds only to the change. Bathroom scales, load cells, pressure sensors and precision thermometers all work this way.
:::

::: play
- Output voltage against strain for a bridge from $V_s$ with gauges of gauge factor GF. The three lines are a **quarter** bridge (one active gauge), a **half** bridge (two, one stretched and one squeezed) and a **full** bridge (four).
- Each step doubles the output. The quarter bridge also bends slightly: its output isn't quite proportional to strain.
- The readouts give each output at the marked strain.
:::
:::

```sim plot
view: graph
x: e = -2000..2000 µε
y: V = -25..25 mV
slider: Vs = 1..10 step 0.5 = 5 V
slider: GF = 1.8..2.2 step 0.01 = 2
slider: e0 = -2000..2000 step 50 = 1000 µε
plot: 1000*Vs*(GF*e*1e-6)/(2*(2 + GF*e*1e-6)) | label: quarter bridge
plot: 1000*Vs*(GF*e*1e-6)/2 | label: half bridge | color: ch2
plot: 1000*Vs*(GF*e*1e-6) | label: full bridge | color: ch3
marker: x = e0 | label: strain
readout: quarter bridge output, mV = 1000*Vs*(GF*e0*1e-6)/(2*(2 + GF*e0*1e-6)) | digits: 4
readout: full bridge output, mV = 1000*Vs*(GF*e0*1e-6) | digits: 4
```

::: predict
## A 350 Ω strain gauge (gauge factor 2) in a quarter bridge from 5 V sees 1000 µε of strain. About what voltage appears across the bridge?

- [ ] 5 V
- [ ] 0.7 V
- [x] 2.5 mV
- [ ] 2.5 µV

::: reveal
About 2.5 mV. The gauge changes by $\text{GF} \times \varepsilon = 2 \times 10^{-3}$, 0.2%. A quarter bridge turns a small fractional change $x$ into about $V_s\frac{x}{4}$: $5 \times \frac{0.002}{4} = 2.5$ mV, zero at rest. Small, but an amplifier can boost it a thousandfold without the 2.5 V common to both sides getting in the way (C6).
:::
:::

::: nameit
## The Wheatstone bridge

Two dividers from the same supply $V_s$: $R_1$ over $R_3$ to node $a$, and $R_2$ over $R_4$ to node $b$. The output is the difference between their midpoints:

$$V_\text{out} = V_a - V_b = V_s\left(\frac{R_3}{R_1 + R_3} - \frac{R_4}{R_2 + R_4}\right)$$

It's zero when the bridge is **balanced**, $R_1/R_3 = R_2/R_4$ (lesson 11). Any arm that changes unbalances it.

## Sensitivity

With all four arms equal to $R$ at rest and active arms changing by a fraction $x$:

| Bridge | Active arms | Output |
|---|---|---|
| quarter | one, $R(1 + x)$ | $V_s\frac{x}{2(2 + x)} \approx V_s\frac x4$ |
| half | two, $R(1 + x)$ and $R(1 - x)$ on the same side | $V_s\frac x2$ |
| full | four, alternating | $V_sx$ |

The half and full bridges are exactly linear, and they cancel temperature: a temperature change affects every gauge alike, which leaves the bridge balanced.

## Resistive sensors

- **Strain gauges:** a fine metal foil whose resistance changes by $\frac{\Delta R}{R} = \text{GF}\cdot\varepsilon$, with gauge factor about 2 and strain ε in parts per million (µε).
- **RTDs:** platinum, $R = R_0(1 + \alpha T)$ with $R_0$ = 100 Ω (Pt100) and α = 0.00385 per °C.
- **Thermistors** and light-dependent resistors change much more, but less linearly (lesson 28).

## Null measurement

The oldest use: put an unknown resistor in one arm and adjust a calibrated one until the output is zero, then $R_x = R_dR_2/R_1$ from the balance condition. The reading doesn't depend on the supply voltage or the meter's calibration, only on the reference resistors.
:::

::: example
## A 350 Ω gauge (GF = 2.0) sees 1000 µε in a quarter bridge from 5 V. What are the resistance change and the output?

::: solution
1. **Resistance change.**
   $$\begin{aligned} \Delta R &= 350 \times 2.0 \times 10^{-3} \\ &= 0.70\ \Omega \end{aligned}$$
2. **Exact output.**
   $$\begin{aligned} V_\text{out} &= 5 \times \frac{0.002}{2 \times 2.002} \\ &= 2.4975\ \text{mV} \end{aligned}$$
3. **The approximation.** $V_s\frac x4$ gives 2.5 mV, 0.1% high.

**Answer:** the resistance changes by 0.70 Ω, and the bridge outputs 2.4975 mV.
:::
:::

::: example
## A Pt100 RTD at 100 °C sits in a bridge with three 100 Ω resistors, from 5 V. What does it output?

::: solution
1. **RTD resistance.**
   $$\begin{aligned} R &= 100(1 + 0.00385 \times 100) \\ &= 138.5\ \Omega \end{aligned}$$
2. **Bridge output.** With the RTD as $R_3$:
   $$\begin{aligned} V_\text{out} &= 5\left(\frac{138.5}{238.5} - \frac12\right) \\ &= 0.404\ \text{V} \end{aligned}$$
3. **Linearity.** A change this large is well into the nonlinear range, so RTD bridges are usually linearized in software.

**Answer:** the bridge outputs 0.404 V.
:::
:::

::: example
## An NTC thermistor (10 kΩ at 25 °C, β = 3950 K) sits on top of a fixed 10 kΩ, from 3.3 V. What does the divider output at 0 °C, 25 °C and 50 °C?

::: solution
1. **Thermistor resistance.** With T in kelvin,
   $$R(T) = 10\ \text{k}\Omega \times e^{\beta(1/T - 1/298.15)}$$
   which gives 33.6 kΩ at 0 °C, 10 kΩ at 25 °C and 3.59 kΩ at 50 °C.
2. **Output.** The output is across the fixed resistor:
   $$v = 3.3 \times \frac{10}{10 + R(T)}$$
3. **At each temperature.**
   $$\begin{aligned} v(0\ \text{°C}) &= 0.757\ \text{V} \\ v(25\ \text{°C}) &= 1.650\ \text{V} \\ v(50\ \text{°C}) &= 2.429\ \text{V} \end{aligned}$$
4. **Compare the ranges.** The thermistor's resistance changes by a factor of 9.4, but the output only by 3.2, and much more evenly: a fixed resistor equal to the thermistor's mid-range value linearizes it over the range that matters.

**Answer:** the divider outputs 0.757 V at 0 °C, 1.650 V at 25 °C and 2.429 V at 50 °C.
:::
:::

::: check
given: R = 120 | 350 | 1000; GF = 2 | 2.1; e = 200 | 1500
answer: R*GF*e*1e-6*1000
unit: mΩ
tolerance: 0.5%

## A {R} Ω strain gauge with gauge factor {GF} sees {e} µε. By how much does its resistance change?

::: right
Right. $R\cdot\text{GF}\cdot\varepsilon$ = {answer}.
:::

::: misses
- [R*e*1e-6*1000] Multiply by the gauge factor.
- [any] Not yet. $\Delta R = R\cdot\text{GF}\cdot\varepsilon$.
:::
:::

::: check
given: Vs = 2.5 | 5 | 10; GF = 2 | 2.1; e = 500 | 2000
answer: Vs*GF*e*1e-6/4*1000
unit: mV
tolerance: 1%

## A quarter bridge from {Vs} V has one gauge (GF = {GF}) at {e} µε. Using the small-change approximation, what is its output?

::: right
Right. $V_s\frac{\text{GF}\cdot\varepsilon}{4}$ = {answer}.
:::

::: misses
- [Vs*GF*e*1e-6/2*1000] That's a half bridge; one active arm gives a quarter.
- [Vs*GF*e*1e-6*1000] That's a full bridge.
- [any] Not yet. $V_s x/4$.
:::
:::

::: check
given: Vs = 5 | 10; R1 = 1000 | 1200; R3 = 1050 | 1100
answer: Vs*(R3/(R1 + R3) - 0.5)*1000
unit: mV
tolerance: 0.5%

## A bridge from {Vs} V has $R_1$ = {R1} Ω over $R_3$ = {R3} Ω on one side and 1 kΩ over 1 kΩ on the other. What is $V_a - V_b$?

::: right
Right. $V_s\left(\frac{R_3}{R_1 + R_3} - \frac12\right)$ = {answer}.
:::

::: misses
- [Vs*(R1/(R1 + R3) - 0.5)*1000] $V_a$ is taken across the lower resistor, $R_3$.
- [any] Not yet. Subtract the two midpoint voltages.
:::
:::

::: check
given: T = -40 | 25 | 150
answer: 100*(1 + 0.00385*T)
unit: Ω
tolerance: 0.1%

## What is a Pt100 RTD's resistance at {T} °C, with α = 0.00385 per °C?

::: right
Right. $100(1 + \alpha T)$ = {answer}.
:::

::: misses
- [any] Not yet. $R = R_0(1 + \alpha T)$.
:::
:::

::: check
given: Vs = 3.3 | 5 | 10; GF = 2 | 2.15; e = 100 | 800
answer: Vs*GF*e*1e-6*1000
unit: mV
tolerance: 0.5%

## A full bridge of four gauges (GF = {GF}) from {Vs} V measures {e} µε. What is its output?

::: right
Right. $V_s\cdot\text{GF}\cdot\varepsilon$ = {answer}.
:::

::: misses
- [Vs*GF*e*1e-6/4*1000] Four active arms give four times the quarter bridge.
- [any] Not yet. A full bridge gives $V_sx$.
:::
:::

::: check
given: Rd = 470 | 1234 | 5600; R1 = 100 | 1000; R2 = 200 | 10000
answer: Rd*R2/R1
unit: Ω
tolerance: 0.5%

## A bridge balances with the decade box at {Rd} Ω, with ratio arms $R_1$ = {R1} Ω and $R_2$ = {R2} Ω. Using $R_x = R_dR_2/R_1$, what is the unknown?

::: right
Right. {answer}.
:::

::: misses
- [Rd*R1/R2] The ratio is $R_2/R_1$.
- [any] Not yet. Apply the balance condition.
:::
:::

::: check
kind: parts
given: T = 0 | 40 | 70; B = 3435 | 3950

## An NTC thermistor (10 kΩ at 25 °C, β = {B} K) sits above a fixed 10 kΩ, from 3.3 V, at {T} °C.

::: part
answer: 10*exp(B*(1/(T + 273.15) - 1/298.15))
unit: kΩ
tolerance: 0.5%

### What's its resistance?

::: misses
- [any] $R_0e^{\beta(1/T - 1/T_0)}$, in kelvin.
:::
:::

::: part
answer: 3.3*10/(10 + 10*exp(B*(1/(T + 273.15) - 1/298.15)))
unit: V
tolerance: 0.5%

### What does the divider output across the fixed resistor?

::: misses
- [any] $3.3\frac{10}{10 + R(T)}$.
:::
:::
:::

::: check
kind: derivation
vars: V = 0.1..20, x = -0.2..0.2

## A bridge from V has one arm changed by a fraction x; the other three are equal.

::: step
answer: V*x/(2*(2 + x))

### What's the exact output?
:::

::: step
answer: V*x/4

### What's the small-change approximation?
:::

::: step
answer: 2/(2 + x)

### What's the ratio of exact to approximate?
:::

::: right
Right. The approximation is off by about x/2: 1% for a 2% change.
:::
:::

::: explain
## Why is a half bridge with one gauge stretched and one squeezed better than a quarter bridge, beyond doubling the output?

::: model
In a half bridge both gauges sit in the same half of the bridge, one stretched and one squeezed, so their resistance changes are equal and opposite and the output becomes exactly proportional to strain, removing the quarter bridge's slight curve. Both gauges are also the same type at the same temperature, so when the temperature changes they drift together, and a common change in two arms of the same divider leaves its ratio, and the output, unchanged. The half bridge cancels the thermal drift that would otherwise look like strain.
:::
:::

::: practice

::: check
given: e = 500 | 1000; GF = 2 | 2.1
answer: GF*e*1e-6*100
tolerance: 0.5%

## A gauge with GF = {GF} sees {e} µε. By what percentage does its resistance change?

::: misses
- [any] $\text{GF}\cdot\varepsilon$.
:::
:::

::: check
given: R = 110 | 120 | 138.5
answer: (R/100 - 1)/0.00385
unit: °C
tolerance: 0.5%

## A Pt100 reads {R} Ω. What temperature is that?

::: misses
- [any] Solve $R = 100(1 + 0.00385T)$.
:::
:::

::: check
given: Vs = 5 | 10; x = 0.001 | 0.004
answer: Vs*x/2*1000
unit: mV
tolerance: 0.5%

## A half bridge from {Vs} V has two arms changing by ±{x} (as fractions). What is its output?

::: misses