title: Problem set 3
heading: "Problem set 3: spectra, networks, power, noise and grounding"
eyebrow: C11 · Problem set 3
type: problems
---

::: hook
These problems use lessons 13 to 18: spectrum analyzers and decibels, network analyzers, measuring power, noise, averaging and lock-in detection, grounding and differential measurement, and low-level measurements. Room temperature is 300 K, where kT is 4.14 × 10⁻²¹ J and the thermal noise floor is −174 dBm/Hz.
:::

::: pool
pick: 12

::: check
kind: parts
given: NF = 6 | 12 | 20; RBW = 100 | 3000 | 100000

## An analyzer with a {NF} dB noise figure is set to {RBW} Hz RBW.

::: part
answer: -174 + NF + 10*log(RBW)
unit: dBm
tolerance: 0.5%

### What noise floor does it show?

::: misses
- [any] $-174 + NF + 10\log_{10}\text{RBW}$.
:::
:::

::: part
answer: -174 + NF + 10*log(RBW/10)
unit: dBm
tolerance: 0.5%

### What would it show at a tenth of that RBW?

::: misses
- [any] 10 dB lower.
:::
:::
:::

::: check
kind: parts
given: S = 0.5 | 10 | 200; R = 0.1 | 1 | 10

## A swept analyzer covers {S} MHz at {R} kHz RBW (k = 2).

::: part
answer: 2*S*1e6/(R*1e3)^2
unit: s
tolerance: 0.5%

### About how long is a sweep?

::: misses
- [any] $k \cdot \text{span}/\text{RBW}^2$.
:::
:::

::: part
answer: 2*S*1e6/(R*3e3)^2
unit: s
tolerance: 0.5%

### How long at three times the RBW?

::: misses
- [any] Nine times faster.
:::
:::
:::

::: check
kind: parts
given: Pc = 3 | 13; H2 = -40 | -55; H3 = -48 | -60

## A carrier is at {Pc} dBm, its second harmonic at {H2} dBm and its third at {H3} dBm.

::: part
answer: H2 - Pc
unit: dB
tolerance: 0.5%

### What is the second harmonic in dBc?

::: misses
- [any] Harmonic minus carrier.
:::
:::

::: part
answer: 10^(Pc/10)
unit: mW
tolerance: 0.5%

### What is the carrier's power in milliwatts?

::: misses
- [any] $10^{P/10}$.
:::
:::
:::

::: check
kind: parts
given: N = 16 | 100 | 4096; s = 5 | 40

## A repeating signal with {s} mV of random noise is averaged over {N} sweeps.

::: part
answer: s/sqrt(N)
unit: mV
tolerance: 0.5%

### What noise is left?

::: misses
- [any] $s/\sqrt N$.
:::
:::

::: part
answer: 10*log(N)
unit: dB
tolerance: 0.5%

### By how many dB has the SNR improved?

::: misses
- [any] $10\log_{10}N$.
:::
:::
:::

::: check
kind: parts
given: tau = 0.03 | 1 | 10; en = 5 | 30

## A lock-in with time constant {tau} s measures a source with {en} nV/√Hz of noise.

::: part
answer: 1/(4*tau)
unit: Hz
tolerance: 0.5%

### What is its noise bandwidth?

::: misses
- [any] $1/(4\tau)$.
:::
:::

::: part
answer: en*sqrt(1/(4*tau))
unit: nV
tolerance: 0.5%

### What noise does it see?

::: misses
- [any] $e_n\sqrt{\text{ENBW}}$.
:::
:::
:::

::: check
kind: parts
given: R = 50 | 10000 | 1e6; B = 1 | 10000

## A resistor of {R} Ω at 300 K is measured over {B} Hz.

::: part
answer: sqrt(4*1.380649e-23*300*R*B)*1e9
unit: nV
tolerance: 0.5%

### What is its thermal noise?

::: misses
- [any] $\sqrt{4kTRB}$.
:::
:::

::: part
answer: sqrt(4*1.380649e-23*300*R)*1e9
unit: nV/√Hz
tolerance: 0.5%

### What is its noise density, in nV/√Hz?

::: misses
- [any] $\sqrt{4kTR}$.
:::
:::
:::

::: check
kind: parts
given: Vcm = 0.5 | 5 | 50; C = 50 | 80 | 110

## A differential amplifier with {C} dB CMRR sees {Vcm} V of common mode.

::: part
answer: Vcm*10^(-C/20)*1e6
unit: µV
tolerance: 0.5%

### What input-referred error results?

::: misses
- [any] $V_{cm}10^{-\text{CMRR}/20}$.
:::
:::

::: part
answer: C + 20
unit: dB
tolerance: 0.5%

### What CMRR would cut that error tenfold?

::: misses
- [any] Ten times is 20 dB.
:::
:::
:::

::: check
kind: parts
given: f = 50 | 60; B = 0.5 | 3; A = 5 | 50

## A loop of {A} cm² sits in a {B} mT field at {f} Hz.

::: part
answer: 2*pi*f*B*1e-3*A*1e-4*1e6
unit: µV
tolerance: 0.5%

### What does it pick up?

::: misses
- [any] $2\pi fBA$.
:::
:::

::: part
answer: 2*pi*f*B*1e-3*A*1e-4*1e6/10
unit: µV
tolerance: 0.5%

### What would twisting the wires to cut the effective area tenfold leave?

::: misses
- [any] A tenth.
:::
:::
:::

::: check
kind: parts
given: m = 0.2 | 2; Vcm = 1 | 12

## Two probes and A − B math measure a floating node with {Vcm} V of common mode; the channels' gains differ by {m}%.

::: part
answer: 20*log(100/m)
unit: dB
tolerance: 0.5%

### What CMRR does that give?

::: misses
- [any] $20\log_{10}(1/\text{mismatch})$.
:::
:::

::: part
answer: Vcm*m/100*1000
unit: mV
tolerance: 0.5%

### What error appears on the difference?

::: misses
- [any] The mismatch fraction of the common mode.
:::
:::
:::

::: check
kind: parts
given: S = -60 | -100; NF = 4 | 10; RBW = 10 | 1000

## A {S} dBm tone is measured on an analyzer with {NF} dB noise figure at {RBW} Hz RBW.

::: part
answer: S - (-174 + NF + 10*log(RBW))
unit: dB
tolerance: 0.5%

### What SNR does the display show?

::: misses
- [any] Signal minus floor.
:::
:::

::: part
answer: 10^(S/10)*1e9
unit: pW
tolerance: 0.5%

### What is the tone's power in picowatts?

::: misses
- [any] $10^{P/10}$ mW.
:::
:::
:::

::: check
kind: parts
given: X = 13 | 20 | 33

## A measurement needs {X} dB more SNR.

::: part
answer: 10^(X/10)
tolerance: 0.5%

### How many sweeps must be averaged?

::: misses
- [any] $10^{X/10}$.
:::
:::

::: part
answer: 10^(X/10)
tolerance: 0.5%

### By what factor must a lock-in's time constant grow instead (noise bandwidth shrinking in proportion)?

::: misses
- [any] Noise power goes as bandwidth, so the same factor.
:::
:::
:::

::: check
kind: parts
given: I = 20 | 300; R = 0.01 | 0.2; S = 1 | 10

## A ground loop drives {I} mA through a {R} Ω shield; the signal is {S} mV.

::: part
answer: I*R
unit: mV
tolerance: 0.5%

### How much hum does a single-ended measurement show?

::: misses
- [any] $IR$.
:::
:::

::: part
answer: 20*log(S/(I*R))
unit: dB
tolerance: 0.5%

### What is the signal-to-hum ratio, in dB?

::: misses
- [any] $20\log_{10}$ of signal over hum.
:::
:::
:::

::: check
kind: parts
given: g = 0.03 | 0.1 | 0.3; d = 30 | 46

## A VNA with {d} dB directivity measures |Γ| = {g}.

::: part
answer: 10^(-d/20)
tolerance: 0.5%

### What stray reflection does the directivity add?

::: misses
- [any] $10^{-d/20}$.
:::
:::

::: part
answer: 10^(-d/20)/g*100
unit: %
tolerance: 0.5%

### What is that as a percentage of the reading?

::: misses
- [any] D/|Γ|.
:::
:::
:::

::: check
kind: parts
given: P = 3 | 20 | 33; p = 0.5 | 0.9

## A meter reads apparent power of {P} kVA on a load with power factor {p}.

::: part
answer: P*p
unit: kW
tolerance: 0.5%

### What is the real power?

::: misses
- [any] Apparent × PF.
:::
:::

::: part
answer: P*(1 - p)
unit: kW
tolerance: 0.5%

### By how much does the apparent power overstate it?

::: misses
- [any] The difference.
:::
:::
:::

::: check
kind: parts
given: A = 0 | 17 | 27; R = 6 | 10 | 13

## A signal averages {A} dBm with {R} dB PAPR.

::: part
answer: A + R
unit: dBm
tolerance: 0.5%

### What is its peak power in dBm?

::: misses
- [any] Average + PAPR.
:::
:::

::: part
answer: 10^((A + R)/10)
unit: mW
tolerance: 0.5%

### In milliwatts?

::: misses
- [any] $10^{P/10}$.
:::
:::
:::

::: check
kind: parts
given: Vp = 112 | 230 | 515; Vm = -88 | -190 | -485; V = 10 | 50; R = 10 | 100

## A low-level setup reads {Vp} µV forward and {Vm} µV reversed; elsewhere, a {V} V node is insulated by {R} GΩ.

::: part
answer: (Vp - Vm)/2
unit: µV
tolerance: 0.5%

### What's the true signal?

::: misses
- [(Vp + Vm)/2] That's the thermal offset.
- [any] Not yet. $(V_+ - V_-)/2$.
:::
:::

::: part
answer: V/(R*1e9)*1e12
unit: pA
tolerance: 0.5%

### How much current leaks through the insulation, unguarded?

::: misses
- [V/R] Convert gigaohms to ohms.
- [any] Not yet. $V/R$.
:::
:::

::: right
Right. Reversal removes offsets; guarding removes leakage.
:::
:::
:::