title: Real, reactive and apparent power; power factor
heading: Power that does work, and power that only sloshes
eyebrow: C3 · Lesson 16 · AC power
xp: 50
---

::: hook
Multiply the RMS voltage and current of a motor and you get a number in volt-amperes, but the electricity meter charges for less than that. Part of the current flows into the motor's magnetic field and back out again each cycle, doing no work but still heating the wires. Utilities care about that sloshing power, called reactive power, because their cables and transformers must carry it. The ratio of useful power to the total is the **power factor**.

::: play
- The curves are a voltage, a current lagging it by φ, and their product, the instantaneous power p(t). The dashed line is p's average.
- At φ = 0, is p(t) ever negative? Now raise φ toward 90°. What happens to the average, and to the parts where p dips below zero?
- The readouts give the real power P, the reactive power Q and the apparent power S.
:::
:::

```sim plot
view: graph
x: t = 0..33.3 ms
y: v = -2..2
slider: phi = -90..90 step 5 = 30 °
slider: Vrms = 100..240 step 10 = 120 V
slider: Irms = 1..20 step 1 = 10 A
plot: sqrt(2)*cos(2*pi*60*t/1000) | label: v ÷ V rms
plot: sqrt(2)*cos(2*pi*60*t/1000 - phi*pi/180) | color: ch2 | label: i ÷ I rms
plot: 2*cos(2*pi*60*t/1000)*cos(2*pi*60*t/1000 - phi*pi/180) | color: ch3 | label: p ÷ S
plot: cos(phi*pi/180) | dashed | color: ch3 | label: average ÷ S
readout: real power P in W = Vrms*Irms*cos(phi*pi/180)
readout: reactive power Q in VAR = Vrms*Irms*sin(phi*pi/180)
readout: apparent power S in VA = Vrms*Irms
readout: power factor = cos(phi*pi/180)
```

::: predict
## A 120 V supply drives an ideal inductor, drawing 5 A RMS. What average power does it consume?

- [ ] 600 W
- [ ] 300 W
- [x] 0 W
- [ ] 424 W

::: reveal
0 W. With the current a quarter cycle behind the voltage, p(t) is positive for one quarter cycle and equally negative for the next: the inductor stores energy, then returns it. The 600 VA of apparent power is entirely reactive. The wires still carry 5 A and still heat up, which is why utilities penalize loads with a poor power factor.
:::
:::

::: nameit
## Power in AC circuits

**Instantaneous power.** With $v = \sqrt2V\cos\omega t$ and $i = \sqrt2I\cos(\omega t - \phi)$ (V and I are RMS values, φ the angle of the load's impedance):

$$p(t) = vi = VI\cos\phi + VI\cos(2\omega t - \phi)$$

a constant plus a part at twice the frequency that averages to zero.

**Three powers:**

| | Formula | Unit | Meaning |
|---|---|---|---|
| real (active) power P | $VI\cos\phi$ | W | average power doing work or making heat |
| reactive power Q | $VI\sin\phi$ | VAR | power sloshing into fields and back |
| apparent power S | $VI$ | VA | what the wires and transformers must carry |

They form the **power triangle**: $S^2 = P^2 + Q^2$. In complex form, $\mathbf S = P + jQ = \mathbf V\mathbf I^*$ (A3.21), using RMS phasors.

**For a load of impedance $R + jX$:** $P = I^2R$ and $Q = I^2X$. Inductive loads (motors, transformers) have $Q > 0$; capacitive ones have $Q < 0$.

**Power factor.** $\text{pf} = P/S = \cos\phi$, described as lagging (inductive) or leading (capacitive). A motor might run at 0.8 lagging; a resistive heater at 1.

**Correction.** A capacitor across an inductive load supplies the reactive power locally, so the line carries less current for the same real power. To cancel $Q$ at voltage $V$ (RMS) and frequency $f$:

$$C = \frac{Q}{2\pi fV^2}$$

Factories install banks of capacitors for exactly this.
:::

::: example
## A load draws 5 A from 230 V with the current lagging by 30°. Find P, Q and S.

::: solution
1. **Apparent power.**
   $$\begin{aligned} S &= 230 \times 5 \\ &= 1150\ \text{VA} \end{aligned}$$
2. **Real power.**
   $$\begin{aligned} P &= S\cos 30° \\ &= 996\ \text{W} \end{aligned}$$
3. **Reactive power.**
   $$\begin{aligned} Q &= S\sin 30° \\ &= 575\ \text{VAR} \end{aligned}$$
4. **Power factor.** The power factor is $\cos 30°$, or 0.87.

**Answer:** P = 996 W, Q = 575 VAR and S = 1150 VA, at a power factor of 0.87.
:::
:::

::: example
## A 30 + j40 Ω load is connected to 100 V. Find the current and the powers.

::: solution
1. **Impedance magnitude.**
   $$\begin{aligned} |Z| &= \sqrt{30^2 + 40^2} \\ &= 50\ \Omega \end{aligned}$$
2. **Current.**
   $$\begin{aligned} I &= \frac{100}{50} \\ &= 2\ \text{A} \end{aligned}$$
3. **Real power.**
   $$\begin{aligned} P &= I^2R \\ &= 2^2 \times 30 \\ &= 120\ \text{W} \end{aligned}$$
4. **Reactive power.**
   $$\begin{aligned} Q &= I^2X \\ &= 2^2 \times 40 \\ &= 160\ \text{VAR} \end{aligned}$$
5. **Power factor.**
   $$\begin{aligned} \text{pf} &= \frac{R}{|Z|} \\ &= 0.6 \end{aligned}$$

**Answer:** 2 A flows, with P = 120 W, Q = 160 VAR and a power factor of 0.6.
:::
:::

::: example
## A wattmeter reads 720 W on a load drawing 8 A from 120 V. What are its power factor and reactive power?

::: solution
1. **Apparent power.**
   $$\begin{aligned} S &= VI \\ &= 960\ \text{VA} \end{aligned}$$
2. **Power factor.**
   $$\begin{aligned} \text{pf} &= \frac{P}{S} \\ &= \frac{720}{960} \\ &= 0.75 \end{aligned}$$
3. **Reactive power.**
   $$\begin{aligned} Q &= \sqrt{S^2 - P^2} \\ &= \sqrt{960^2 - 720^2} \\ &= 635\ \text{var} \end{aligned}$$
4. **What the meters give.** A wattmeter and an ammeter and voltmeter together are all you need to find a load's whole power triangle.
5. **What they can't tell.** They don't show whether the load is inductive or capacitive; that takes a phase measurement.

**Answer:** a power factor of 0.75 and 635 var of reactive power.
:::
:::

::: check
given: V = 120 | 230; I = 5 | 10 | 20; phi = 20 | 37 | 60
answer: V*I*cos(phi*pi/180)
unit: W
tolerance: 0.5%

## A load draws {I} A RMS from {V} V RMS, with the current lagging by {phi}°. How much real power does it consume?

::: right
Right. $P = VI\cos\phi$ = {answer}.
:::

::: misses
- [V*I] That's the apparent power, in VA. Multiply by cos φ.
- [V*I*sin(phi*pi/180)] That's the reactive power.
- [any] Not yet. $P = VI\cos\phi$.
:::
:::

::: check
given: V = 120 | 230; I = 5 | 10 | 20; phi = 20 | 37 | 60
answer: V*I*sin(phi*pi/180)
unit: VAR
tolerance: 0.5%

## Same load: {V} V, {I} A, lagging by {phi}°. What is its reactive power?

::: right
Right. $Q = VI\sin\phi$ = {answer}.
:::

::: misses
- [V*I*cos(phi*pi/180)] That's the real power.
- [any] Not yet. $Q = VI\sin\phi$.
:::
:::

::: check
given: P = 3 | 8 | 15; Q = 4 | 6
answer: P/sqrt(P^2 + Q^2)
tolerance: 0.5%

## A load takes {P} kW of real power and {Q} kVAR of reactive power. What is its power factor?

::: right
Right. $P/S = P/\sqrt{P^2 + Q^2}$ = {answer}.
:::

::: misses
- [P/(P + Q)] S comes from the power triangle: $\sqrt{P^2 + Q^2}$.
- [Q/sqrt(P^2 + Q^2)] That's sin φ. Power factor is P/S.
- [any] Not yet. $\text{pf} = P/S$.
:::
:::

::: check
given: I = 2 | 5 | 10; R = 10 | 20; X = 15 | 30
answer: I^2*R
unit: W
tolerance: 0.5%

## A load of {R} + j{X} Ω carries {I} A RMS. How much real power does it consume?

::: right
Right. Only the resistance dissipates: $I^2R$ = {answer}.
:::

::: misses
- [I^2*sqrt(R^2 + X^2)] That's the apparent power. Only R dissipates.
- [I^2*X] That's the reactive power.
- [any] Not yet. $P = I^2R$.
:::
:::

::: check
given: Q = 1 | 2 | 5; V = 120 | 230; f = 50 | 60
answer: Q*1e3/(2*pi*f*V^2)*1e6
unit: µF
tolerance: 0.5%

## A motor on a {V} V, {f} Hz supply draws {Q} kVAR of reactive power. What capacitor across it would cancel that?

::: right
Right. $C = Q/(2\pi fV^2)$ = {answer}.
:::

::: misses
- [Q*1e3/(f*V^2)*1e6] Include 2π.
- [Q*1e3/(2*pi*f*V)*1e6] The capacitor's reactive power goes as $V^2$.
- [any] Not yet. A capacitor supplies $Q = V^2\omega C$.
:::
:::

::: check
kind: parts
given: V = 120 | 230; I = 2 | 8; P = 0.5 | 0.8

## A load draws {I} A from {V} V, and a wattmeter reads {P} of the volt-amperes.

::: part
answer: V*I*P
unit: W
tolerance: 0.5%

### What real power does it take?

::: misses
- [any] Power factor times VI.
:::
:::

::: part
answer: V*I*sqrt(1 - P^2)
unit: var
tolerance: 0.5%

### What's its reactive power?

::: misses
- [any] $\sqrt{S^2 - P^2}$.
:::
:::
:::

::: check
kind: derivation
vars: V = 1..1000, I = 0.01..100, p = 0..1.5

## A load at voltage V draws current I lagging by angle p (radians).

::: step
answer: V*I

### What's its apparent power?
:::

::: step
answer: V*I*cos(p)

### Real power?
:::

::: step
answer: V*I*sin(p)

### Reactive power?
:::

::: right
Right. $S^2 = P^2 + Q^2$.
:::
:::

::: explain
## Why does an inductive load draw more current from the supply than its real power alone would need, and how does a capacitor help?

::: model
An inductive load's current lags the voltage, so for part of each cycle it's absorbing energy into its magnetic field and for part it's returning it. That back-and-forth reactive power does no work, but the current carrying it still flows through the supply wires, so the total current is larger than the real power requires. A capacitor nearby has the opposite phase: it absorbs energy when the inductor returns it and gives it back when the inductor wants it. The reactive power then circulates locally between the two, and the supply only delivers the real power, at a lower current.
:::
:::

::: practice

::: check
given: V = 100 | 200; I = 2 | 3
answer: V*I
unit: VA
tolerance: 0.5%

## {V} V RMS, {I} A RMS. Apparent power?

::: misses
- [any] $S = VI$.
:::
:::

::: check
given: S = 10 | 20; pf = 0.6 | 0.8
answer: S*pf
unit: kW
tolerance: 0.5%

## {S} kVA at power factor {pf}. Real power?

::: misses
- [S] Multiply by the power factor.
- [any] $P = S \cdot \text{pf}$.
:::
:::

::: check
given: P = 3 | 6; Q = 4 | 8
answer: sqrt(P^2 + Q^2)
unit: kVA
tolerance: 0.5%

## {P} kW and {Q} kVAR. Apparent power?

::: misses
- [P + Q] Use the power triangle.
- [any] $\sqrt{P^2 + Q^2}$.
:::
:::
:::