title: Coupled coils and transformers in circuits
heading: Mutual inductance, the dot convention and reflected impedance
eyebrow: C3 · Lesson 14 · Coupled coils and transformers
xp: 40
---

::: hook
Lesson 1 introduced the transformer as a voltage changer: turns ratio in, voltage ratio out. In a circuit it does more. A load on the secondary shows up at the primary multiplied by the turns ratio squared, which is how an audio transformer lets a tube amplifier drive an 8 Ω speaker, and how a radio front end matches an antenna. Real transformers also draw magnetizing current and leak some flux, and coils that merely sit near each other couple partly. All of this is captured by one idea, mutual inductance.
:::

::: play
- A transformer with primary inductance $L_1$, turns ratio $N_2/N_1$ and coupling $k$ drives a resistive load. The curve is the impedance seen at the primary against frequency.
- At high frequency, with $k$ near 1, it settles at the load times $(N_1/N_2)^2$: the reflected load. At low frequency the primary's own inductance shunts it.
- Lower $k$ and watch leakage spoil the reflection at high frequency.
:::
:::

```sim plot
view: graph
x: f = 10..100000 Hz log
y: Z = 1..10000 Ω log
slider: L1 = 1..1000 = 100 mH log
slider: n = 0.05..2 = 0.1 log
slider: k = 0.5..0.999 step 0.001 = 0.99
slider: RL = 1..1000 = 8 Ω log
plot: abs(j*2*pi*f*L1*1e-3 + (2*pi*f*k*n*L1*1e-3)^2/(j*2*pi*f*n^2*L1*1e-3 + RL)) | label: input impedance | samples: 600
plot: RL/n^2 + 0*f | label: ideal reflected load | dashed | color: ch2
readout: ideal reflected load, Ω = RL/n^2 | digits: 4
readout: mutual inductance, mH = k*n*L1 | digits: 4
```

::: predict
## An 8 Ω speaker is connected through a transformer with 10 primary turns for every secondary turn. What load does the amplifier see?

- [ ] 0.08 Ω
- [ ] 80 Ω
- [x] 800 Ω
- [ ] 8 Ω

::: reveal
800 Ω. The transformer steps the voltage down by 10 and the current up by 10, so at the primary the ratio of voltage to current is $10 \times 10 = 100$ times the load's: $8 \times 100 = 800$ Ω. Impedance transforms by the turns ratio squared.
:::
:::

::: nameit
## Mutual inductance

Two coils whose fields link each other have, besides their self-inductances $L_1$ and $L_2$, a **mutual inductance** $M$: a changing current in one induces a voltage in the other. In phasor form,

$$V_1 = j\omega L_1I_1 + j\omega MI_2 \qquad V_2 = j\omega MI_1 + j\omega L_2I_2$$

with currents entering the **dotted** ends of the windings counted positive; the dots mark which ends rise together. The **coupling coefficient** $k = \frac{M}{\sqrt{L_1L_2}}$ runs from 0 (no linkage) to 1 (perfect). Coils in series add or subtract their mutual inductance: $L = L_1 + L_2 \pm 2M$, aiding or opposing.

## Reflected impedance

With a load $Z_L$ on coil 2, solving the two equations gives the impedance seen at coil 1:

$$Z_\text{in} = j\omega L_1 + \frac{(\omega M)^2}{j\omega L_2 + Z_L}$$

## The ideal transformer

For tight coupling ($k \to 1$) and inductances so large that $\omega L$ dwarfs the load, with $L_2/L_1 = (N_2/N_1)^2$, this becomes

$$Z_\text{in} = Z_L\left(\frac{N_1}{N_2}\right)^2$$

To match a load $R_L$ to a source $R_S$, choose $\frac{N_1}{N_2} = \sqrt{\frac{R_S}{R_L}}$.

## Real transformers

A practical model adds, around an ideal transformer: the **magnetizing inductance** (the primary's own inductance, which draws a magnetizing current $V/\omega L_m$ even with no load), **leakage inductances** (the flux that misses the other winding, $k < 1$), winding resistances and core losses. Magnetizing current sets a low-frequency limit; leakage, a high-frequency one.
:::

::: example
## A 10 mH coil and a 40 mH coil are wound together with k = 0.9. Find M, and the total inductance in series, aiding and opposing.

::: solution
1. **Mutual inductance.**
   $$\begin{aligned} M &= k\sqrt{L_1 L_2} \\ &= 0.9\sqrt{10 \times 40} \\ &= 18\ \text{mH} \end{aligned}$$
2. **Series aiding.** The mutual term adds $2M = 36$ mH:
   $$\begin{aligned} L &= 10 + 40 + 36 \\ &= 86\ \text{mH} \end{aligned}$$
3. **Series opposing.** The mutual term subtracts:
   $$\begin{aligned} L &= 10 + 40 - 36 \\ &= 14\ \text{mH} \end{aligned}$$

**Answer:** M = 18 mH, and the total is 86 mH aiding and 14 mH opposing.
:::
:::

::: example
## A mains transformer's primary has 5 H of magnetizing inductance. What current does it draw from 230 V, 50 Hz with no load?

::: solution
1. **Current through the magnetizing inductance.**
   $$\begin{aligned} I &= \frac{230}{2\pi \times 50 \times 5} \\ &= 0.146\ \text{A} \end{aligned}$$
2. **What kind of current.** It lags the voltage by 90°: reactive current that does no work but heats the wiring.

**Answer:** 0.146 A, lagging the voltage by 90°.
:::
:::

::: example
## An 8 Ω speaker is driven through a 10:1 output transformer. What impedance does the amplifier see, and what happens to voltage and current?

::: solution
1. **Reflected impedance.** An ideal transformer reflects impedance by the square of the turns ratio:
   $$\begin{aligned} Z_{in} &= n^2Z_L \\ &= 100 \times 8 \\ &= 800\ \Omega \end{aligned}$$
2. **Voltage and current.** The voltage at the speaker is a tenth of the primary's, and the current ten times larger, so power passes through unchanged.
3. **Where it's used.** Tube amplifiers, whose output devices want loads of thousands of ohms, used exactly such transformers to drive low-impedance speakers.
4. **Matching a line.** The same reflection lets a transformer match a 50 Ω line to a 200 Ω antenna with a 1:2 turns ratio.

**Answer:** the amplifier sees 800 Ω, and the speaker gets a tenth of the voltage and ten times the current.
:::
:::

::: check
given: L1 = 10 | 47; L2 = 22 | 100; M = 5 | 15
answer: M/sqrt(L1*L2)
tolerance: 0.5%

## Two coils of {L1} mH and {L2} mH have {M} mH of mutual inductance. What is their coupling coefficient?

::: right
Right. $\frac{M}{\sqrt{L_1L_2}}$ = {answer}.
:::

::: misses
- [M/(L1 + L2)] Use the geometric mean of the self-inductances.
- [any] Not yet. $k = M/\sqrt{L_1L_2}$.
:::
:::

::: check
given: L1 = 10 | 22; L2 = 15 | 47; k = 0.3 | 0.8
answer: L1 + L2 + 2*k*sqrt(L1*L2)
unit: mH
tolerance: 0.5%

## Coils of {L1} mH and {L2} mH with k = {k} are connected in series, aiding. What is the total inductance?

::: right
Right. $L_1 + L_2 + 2M$ = {answer}.
:::

::: misses
- [L1 + L2 + k*sqrt(L1*L2)] Aiding adds $2M$.
- [L1 + L2] Include the mutual inductance.
- [any] Not yet. $L = L_1 + L_2 + 2k\sqrt{L_1L_2}$.
:::
:::

::: check
given: RL = 4 | 8 | 50; r = 3 | 10 | 20
answer: RL*r^2
unit: Ω
tolerance: 0.5%

## An ideal transformer has {r} primary turns per secondary turn and a {RL} Ω load. What resistance does the source see?

::: right
Right. $R_L(N_1/N_2)^2$ = {answer}.
:::

::: misses
- [RL*r] Impedance transforms with the square of the turns ratio.
- [RL/r^2] Stepping the voltage down steps the impedance up, seen from the primary.
- [any] Not yet. $Z_\text{in} = Z_L(N_1/N_2)^2$.
:::
:::

::: check
given: RS = 600 | 5000; RL = 8 | 50
answer: sqrt(RS/RL)
tolerance: 0.5%

## What primary-to-secondary turns ratio matches a {RL} Ω load to a {RS} Ω source?

::: right
Right. $\sqrt{R_S/R_L}$ = {answer}.
:::

::: misses
- [RS/RL] Turns ratio goes as the square root of the impedance ratio.
- [any] Not yet. Make $R_L(N_1/N_2)^2 = R_S$.
:::
:::

::: check
given: V = 120 | 230; f = 50 | 60; Lm = 2 | 10
answer: V/(2*pi*f*Lm)*1000
unit: mA
tolerance: 0.5%

## A transformer has {Lm} H of magnetizing inductance and runs from {V} V at {f} Hz with no load. What current does it draw?

::: right
Right. $\frac{V}{\omega L_m}$ = {answer}.
:::

::: misses
- [any] Not yet. The unloaded primary is just its magnetizing inductance.
:::
:::

::: check
given: L1 = 10 | 100; L2 = 1 | 4; k = 0.95 | 0.99; RL = 8 | 50; f = 1 | 10
answer: abs(j*2*pi*f*1000*L1*1e-3 + (2*pi*f*1000*k*sqrt(L1*L2)*1e-3)^2/(j*2*pi*f*1000*L2*1e-3 + RL))
unit: Ω
tolerance: 0.5%

## A transformer has $L_1$ = {L1} mH, $L_2$ = {L2} mH and k = {k}, with {RL} Ω on the secondary, at {f} kHz. What is the input impedance's magnitude?

::: right
Right. $\left|j\omega L_1 + \frac{(\omega M)^2}{j\omega L_2 + R_L}\right|$ = {answer}.
:::

::: misses
- [any] Not yet. Use the coupled-coil formula with $M = k\sqrt{L_1L_2}$.
:::
:::

::: check
kind: parts
given: n = 2 | 10 | 30; Z = 4 | 8 | 50; V = 10 | 100

## A load of {Z} Ω is driven through an ideal {n}:1 transformer from {V} V RMS.

::: part
answer: n^2*Z
unit: Ω
tolerance: 0.5%

### What impedance does the source see?

::: misses
- [n*Z] Impedance reflects by the square of the turns ratio.
- [any] $n^2Z_L$.
:::
:::

::: part
answer: V/n/Z
unit: A
tolerance: 0.5%

### What current flows in the load?

::: misses
- [any] $\frac{V/n}{Z_L}$.
:::
:::
:::

::: check
kind: derivation
vars: n = 0.1..100, Z = 0.1..10000, V = 1..1000

## An ideal transformer with turns ratio n:1 drives Z from V.

::: step
answer: V/n

### What's the secondary voltage?
:::

::: step
answer: V/(n*Z)

### What's the secondary current?
:::

::: step
answer: n^2*Z

### What impedance does the primary see?
:::

::: right
Right. Voltage divides by n, current multiplies by n, and power is unchanged.
:::
:::

::: explain
## Why does an unloaded transformer still draw current from the mains, and why doesn't that current waste much power?

::: model
With nothing on the secondary, the primary is just a large inductor, its magnetizing inductance, and an inductor across an AC supply draws a current that lags the voltage by 90°. That current builds and collapses the core's magnetic field each cycle, storing energy and handing it back, so on average it delivers almost no power. Only the small losses, in the winding's resistance and in the core's magnetization cycle, take real power. The current still loads the supply and wiring, which is why large transformers are designed with a high magnetizing inductance.
:::
:::

::: practice

::: check
given: k = 0.5 | 0.9; L1 = 4 | 16; L2 = 9 | 25
answer: k*sqrt(L1*L2)
unit: mH
tolerance: 0.5%

## What mutual inductance do {L1} mH and {L2} mH have with k = {k}?

::: misses
- [any] $M = k\sqrt{L_1L_2}$.
:::
:::

::: check
given: Np = 100 | 500; Ns = 20 | 50
answer: (Np/Ns)^2
tolerance: 0.5%

## By what factor does a transformer with {Np} primary and {Ns} secondary turns scale a load's impedance, seen from the primary?

::: misses
- [any] $(N_p/N_s)^2$.
:::
:::

::: check
given: L1 = 10 | 22; L2 = 15 | 47; k = 0.3 | 0.8
answer: L1 + L2 - 2*k*sqrt(L1*L2)
unit: mH
tolerance: 0.5%

## Coils of {L1} mH and {L2} mH with k = {k} are connected in series, opposing. What is the total?

::: misses
- [any] $L_1 + L_2 - 2M$.
:::
:::
:::