title: Problem set 4
heading: "Problem set 4: AC power, three-phase and harmonics"
eyebrow: C3 · Problem set 4
type: problems
---

::: hook
These problems use lessons 16 to 20: real, reactive and apparent power, power factor correction, three-phase and split-phase systems, and non-sinusoidal waveforms. Voltages and currents are RMS unless a problem says otherwise.
:::

::: pool
pick: 12

::: check
kind: parts
given: V = 120 | 230; R = 10 | 30; X = 10 | 40

## A load of {R} + j{X} Ω is connected to {V} V.

::: part
answer: V^2*R/(R^2 + X^2)
unit: W
tolerance: 0.5%

### What real power does it take?

::: misses
- [any] $I^2R$ with $I = V/|Z|$.
:::
:::

::: part
answer: R/sqrt(R^2 + X^2)
tolerance: 0.5%

### What is its power factor?

::: misses
- [any] $R/|Z|$.
:::
:::
:::

::: check
kind: parts
given: P = 2 | 8; Q = 1 | 6

## A load takes {P} kW and {Q} kVAR.

::: part
answer: sqrt(P^2 + Q^2)
unit: kVA
tolerance: 0.5%

### What is its apparent power?

::: misses
- [any] $\sqrt{P^2 + Q^2}$.
:::
:::

::: part
answer: atan(Q/P)*180/pi
unit: °
tolerance: 0.5%

### What is the phase angle between voltage and current?

::: misses
- [any] $\tan^{-1}(Q/P)$.
:::
:::
:::

::: check
kind: parts
given: P = 15 | 40; pf1 = 0.65 | 0.75; pf2 = 0.95 | 0.98; V = 230 | 400; f = 50 | 60

## A {P} kW single-phase load at pf {pf1} on {V} V, {f} Hz is corrected to pf {pf2}.

::: part
answer: P*(tan(acos(pf1)) - tan(acos(pf2)))
unit: kVAR
tolerance: 0.5%

### What reactive power must the capacitors supply?

::: misses
- [any] $P(\tan\varphi_1 - \tan\varphi_2)$.
:::
:::

::: part
answer: P*(tan(acos(pf1)) - tan(acos(pf2)))*1000/(2*pi*f*V^2)*1e6
unit: µF
tolerance: 0.5%

### What capacitance is that?

::: misses
- [any] $Q_C/(\omega V^2)$.
:::
:::
:::

::: check
kind: parts
given: P = 5 | 25; V = 230 | 400; pf1 = 0.6 | 0.7; pf2 = 0.9 | 0.97

## A {P} kW load on {V} V is corrected from pf {pf1} to {pf2}.

::: part
answer: P*1000/(V*pf1) - P*1000/(V*pf2)
unit: A
tolerance: 0.5%

### By how much does its supply current fall?

::: misses
- [any] $I = P/(V\cdot\text{pf})$ before and after.
:::
:::

::: part
answer: 100*(1 - (pf1/pf2)^2)
tolerance: 0.5%

### By what percentage do the cable losses fall?

::: misses
- [any] Losses ∝ $1/\text{pf}^2$.
:::
:::
:::

::: check
kind: parts
given: Vph = 120 | 230 | 277; I = 10 | 40; pf = 0.8 | 0.92

## A balanced wye load has {Vph} V per phase and draws {I} A at pf {pf}.

::: part
answer: Vph*sqrt(3)
unit: V
tolerance: 0.5%

### What is the line voltage?

::: misses
- [any] $\sqrt3V_\text{ph}$.
:::
:::

::: part
answer: 3*Vph*I*pf/1000
unit: kW
tolerance: 0.5%

### What total power does it take?

::: misses
- [any] $3V_\text{ph}I\,\text{pf}$.
:::
:::
:::

::: check
kind: parts
given: P = 7.5 | 55; VL = 400 | 480; pf = 0.8 | 0.88; eff = 0.9 | 0.95

## A three-phase motor delivers {P} kW of mechanical power at efficiency {eff}, pf {pf}, from {VL} V.

::: part
answer: P/eff
unit: kW
tolerance: 0.5%

### What electrical power does it take?

::: misses
- [any] Output over efficiency.
:::
:::

::: part
answer: P/eff*1000/(sqrt(3)*VL*pf)
unit: A
tolerance: 0.5%

### What line current does it draw?

::: misses
- [any] $P_\text{in}/(\sqrt3V_L\text{pf})$.
:::
:::
:::

::: check
kind: parts
given: Z = 10 | 25; VL = 208 | 400

## A balanced delta load of {Z} Ω resistors per phase is connected to {VL} V.

::: part
answer: VL/Z*sqrt(3)
unit: A
tolerance: 0.5%

### What line current does it draw?

::: misses
- [any] Phase current $V_L/Z$, line current $\sqrt3$ times that.
:::
:::

::: part
answer: 3*VL^2/Z/1000
unit: kW
tolerance: 0.5%

### What power does it take?

::: misses
- [any] Three phases of $V_L^2/Z$.
:::
:::
:::

::: check
kind: parts
given: Ia = 15 | 20; Ib = 10 | 15; Ic = 5 | 8

## A wye of resistive loads draws {Ia}, {Ib} and {Ic} A.

::: part
answer: abs(Ia + Ib*exp(-2*pi*j/3) + Ic*exp(2*pi*j/3))
unit: A
tolerance: 0.5%

### What current flows in the neutral?

::: misses
- [any] The phasor sum.
:::
:::

::: part
answer: Ia + Ib + Ic
unit: A
tolerance: 0.5%

### What would it carry if all three were in phase, as third harmonics are?

::: misses
- [any] In phase, they add directly.
:::
:::
:::

::: check
kind: parts
given: A = 2 | 10; R = 4 | 8

## A ±{A} V square wave drives a {R} Ω resistor.

::: part
answer: A^2/R
unit: W
tolerance: 0.5%

### What power does it deliver?

::: misses
- [any] The square wave's RMS is $A$.
:::
:::

::: part
answer: (4*A/pi)^2/2/R
unit: W
tolerance: 0.5%

### How much of that is in the fundamental?

::: misses
- [any] Fundamental peak $4A/\pi$.
:::
:::
:::

::: check
kind: parts
given: V1 = 100 | 230; h3 = 2 | 8; h5 = 1 | 5

## A voltage has a fundamental of {V1} V RMS, with third and fifth harmonics of {h3}% and {h5}% of the fundamental.

::: part
answer: sqrt(h3^2 + h5^2)
tolerance: 0.5%

### What is its THD, in percent?

::: misses
- [any] Combine in squares.
:::
:::

::: part
answer: V1*sqrt(1 + (h3/100)^2 + (h5/100)^2)
unit: V
tolerance: 0.1%

### What is its total RMS?

::: misses
- [any] $V_1\sqrt{1 + \text{THD}^2}$.
:::
:::
:::

::: check
kind: parts
given: Irms = 2 | 10; thd = 50 | 120; V = 120 | 230

## A rectifier load draws {Irms} A RMS with {thd}% current THD, its fundamental in phase with the {V} V supply.

::: part
answer: Irms/sqrt(1 + (thd/100)^2)
unit: A
tolerance: 0.5%

### What is the fundamental current?

::: misses
- [any] $I_\text{rms}/\sqrt{1 + \text{THD}^2}$.
:::
:::

::: part
answer: V*Irms/sqrt(1 + (thd/100)^2)
unit: W
tolerance: 0.5%

### What real power does it take?

::: misses
- [any] Only the fundamental current delivers power: $VI_1$.
:::
:::
:::

::: check
kind: parts
given: Vp = 5 | 12; Vrms = 2 | 4

## A waveform has {Vp} V peak and {Vrms} V RMS.

::: part
answer: Vp/Vrms
tolerance: 0.5%

### What is its crest factor?

::: misses
- [any] Peak over RMS.
:::
:::

::: part
answer: Vrms^2/50*1000
unit: mW
tolerance: 0.5%

### What power does it deliver to 50 Ω?

::: misses
- [any] $V_\text{rms}^2/R$.
:::
:::
:::

::: check
kind: parts
given: V = 120 | 230; I = 3 | 12; P = 0.6 | 0.9

## A load draws {I} A from {V} V at power factor {P}.

::: part
answer: V*I*P
unit: W
tolerance: 0.5%

### What's its real power?

::: misses
- [any] $VI\,\text{pf}$.
:::
:::

::: part
answer: V*I*sqrt(1 - P^2)
unit: var
tolerance: 0.5%

### What's its reactive power?

::: misses
- [any] $\sqrt{S^2 - P^2}$.
:::
:::
:::

::: check
kind: parts
given: P = 20 | 100; a = 0.7 | 0.8; b = 0.95 | 0.98

## A {P} kW load at pf {a} is corrected to {b}.

::: part
answer: P*(sqrt(1 - a^2)/a - sqrt(1 - b^2)/b)
unit: kvar
tolerance: 0.5%

### What reactive power must the capacitors supply?

::: misses
- [any] $P(\tan\phi_1 - \tan\phi_2)$.
:::
:::

::: part
answer: P/b
unit: kVA
tolerance: 0.5%

### What's the apparent power after correction?

::: misses
- [any] $\frac{P}{\text{pf}}$.
:::
:::
:::

::: check
kind: parts
given: A = 2 | 5; h = 0.3 | 0.6

## A triangle wave of peak {A} V, and a current with THD {h} whose fundamental is in phase.

::: part
answer: 8*A/pi^2
unit: V
tolerance: 0.5%

### What's the triangle's fundamental amplitude?

::: misses
- [any] $\frac{8A}{\pi^2}$.
:::
:::

::: part
answer: 1/sqrt(1 + h^2)
tolerance: 0.5%

### What's the current's power factor?

::: misses
- [any] $\frac{1}{\sqrt{1 + \text{THD}^2}}$.
:::
:::
:::

::: check
kind: parts
given: P1 = 900 | 1500 | 2400; P2 = 300 | 600; P3 = 3600 | 5400

## A split-phase panel feeds {P1} W of 120 V loads on L1, {P2} W on L2, and a {P3} W 240 V load.

::: part
answer: P2/120 + P3/240
unit: A
tolerance: 0.5%

### What current flows in L2?

::: misses
- [P2/120] Include the 240 V load's current.
- [any] Not yet. $P_2/120 + P_3/240$.
:::
:::

::: part
answer: 240*P1/(P1 + P2)
unit: V
tolerance: 0.5%

### If the neutral opens with the 240 V load off, what voltage reaches L2's loads?

::: misses
- [240*P2/(P1 + P2)] The lighter leg takes the larger share.
- [any] Not yet. $240P_1/(P_1 + P_2)$.
:::
:::

::: right
Right. Balanced legs keep the neutral quiet; an open neutral turns imbalance into overvoltage.
:::
:::
:::