title: Split-phase power and home wiring
heading: Two 120 V legs and a 240 V pair, what the neutral carries, and what happens when it breaks
eyebrow: C3 · Lesson 19 · Split-phase power and home wiring
xp: 40
---

::: hook
A North American house gets three wires from the pole: two "hot" legs and a neutral. Lamps and outlets use 120 V between a hot and the neutral; a dryer, range or heat pump uses 240 V between the two hots. Lesson 18 showed how three phases share their return; split-phase power does something similar with two legs that are exactly opposite, so the neutral carries only the difference between them. That's efficient until the neutral connection corrodes or breaks, when some rooms' lights glow brighter and others dim, and electronics on the bright side can be destroyed. The same arithmetic sizes the wires: how much voltage a long run loses, and why big loads run on 240 V.
:::

::: play
- The pole transformer's secondary is drawn as two 120 V rms sources (170 V peak) in series, with the center tap grounded. A 1200 W load (12 Ω) sits on leg 1, a 600 W load (24 Ω) on leg 2, and the neutral wire runs from the center tap to the point where the two loads meet.
- With a good neutral (a fraction of an ohm), each load sees its 170 V peak. Slide the neutral's resistance up toward an open connection and watch the voltages separate: the two loads end up in series across 240 V.
:::

```sim circuit
V1 a 0 sine 170 V 60 Hz     @ 0,0 down
V2 0 b sine 170 V 60 Hz     @ 0,2 down
Rn 0 n 0.1                  @ 0,2 right
R1 a n 12                   @ 0,0 right
R2 n b 24                   @ 2,2 right
slider: Rn 0.01..10k log
scope: v(a, n), v(n, b)
time: 0..50m s
meter: v(a, n), v(n, b)
```

::: predict
## A house's neutral connection fails open. Leg 1 has 1200 W of heaters turned on; leg 2 has only a 60 W lamp. Roughly what voltage does the lamp see?

- [ ] 120 V
- [ ] 60 V
- [x] Nearly 240 V
- [ ] 0 V

::: reveal
Nearly 240 V. With no neutral, the two loads are in series across the 240 V between the hots, and the voltage divides in proportion to their resistances. The 60 W lamp is 240 Ω and the heaters are 12 Ω, so the lamp gets $240 \times 240/252$ = 229 V, almost twice its rating, and burns out within moments, while the heaters get 11 V. An open neutral is one of the few wiring faults that destroys equipment all over a house at once.
:::
:::

::: nameit
## Split-phase service

The distribution transformer's secondary has a center tap. Each end, L1 and L2, is 120 V rms from the center, and they're 180° apart, so L1 to L2 is 240 V. The center tap is the **neutral**, bonded to earth at the transformer and at the house's service panel.

## What the neutral carries

Loads on L1 return current through the neutral in one direction, loads on L2 in the other. For resistive loads, the neutral current is

$$I_N = |I_1 - I_2|$$

so a perfectly balanced house puts no current on the neutral. Loads wired from L1 to L2 at 240 V draw from both hots and never touch the neutral. With reactive loads, the currents are phasors: since the two legs' voltages are opposite, $I_N = \left|I_1e^{-j\varphi_1} - I_2e^{-j\varphi_2}\right|$, with $\varphi$ each load's power-factor angle.

## The open neutral

If the neutral opens between the panel and the transformer, the 120 V loads on the two legs end up in series across 240 V. The voltage divides by impedance: with resistive loads of power ratings $P_1$ and $P_2$ (at 120 V), leg 2's loads get

$$V_2 = 240\frac{P_1}{P_1 + P_2}$$

so the lightly loaded leg sees the higher voltage.

## Voltage drop

A branch circuit's drop is its current times the round-trip resistance of its wire: hot out, neutral back. Copper 14, 12 and 10 AWG have about 8.28, 5.21 and 3.28 mΩ per meter at 20 °C. The U.S. electrical code (NEC) recommends no more than 3% drop on a branch circuit and 5% overall, and it pairs 15 A breakers with 14 AWG and 20 A with 12 AWG. For the same power, a 240 V load draws half the current of a 120 V one, so the same wire loses a quarter of the percentage.

## Neutral and ground

The neutral is a current-carrying conductor; the equipment ground isn't. They're bonded together only at the service panel, so normal return current flows on the neutral alone, and the ground carries current only during a fault, long enough to trip the breaker. A **GFCI** compares the hot and neutral currents and trips when they differ by about 5 mA (4 to 6 mA), which means current is leaking somewhere else, possibly through a person. Europe uses a different system: 230 V from each phase of a 400 V three-phase supply to neutral.
:::

::: example
## A house runs a 1200 W heater on L1, a 600 W heater on L2 and a 4800 W dryer element from L1 to L2. Find each hot's current and the neutral's.

::: solution
1. **Heater on L1.**
   $$\begin{aligned} I_1 &= \frac{1200}{120} \\ &= 10\ \text{A} \end{aligned}$$
2. **Heater on L2.**
   $$\begin{aligned} I_2 &= \frac{600}{120} \\ &= 5\ \text{A} \end{aligned}$$
3. **Dryer.** It draws its current through both hots:
   $$\begin{aligned} I_D &= \frac{4800}{240} \\ &= 20\ \text{A} \end{aligned}$$
4. **Hot currents.** So L1 carries 10 + 20 = 30 A, and L2 carries 5 + 20 = 25 A.
5. **Neutral.** The neutral carries only
   $$\begin{aligned} I_N &= 10 - 5 \\ &= 5\ \text{A} \end{aligned}$$
6. **Why the dryer adds nothing.** The dryer adds nothing to the neutral: its current goes out on one hot and back on the other.

**Answer:** L1 carries 30 A, L2 carries 25 A, and the neutral carries 5 A.
:::
:::

::: example
## In the same house, minus the dryer, the neutral opens. What voltage and power does each heater get?

::: solution
1. **Heater resistances.** At 120 V, $R = V^2/P$:
   $$\begin{aligned} R_1 &= \frac{120^2}{1200} \\ &= 12\ \Omega \\ R_2 &= \frac{120^2}{600} \\ &= 24\ \Omega \end{aligned}$$
2. **Series current.** In series across 240 V they carry
   $$\begin{aligned} I &= \frac{240}{36} \\ &= 6.67\ \text{A} \end{aligned}$$
3. **Voltage across each.**
   $$\begin{aligned} V_1 &= 6.67 \times 12 \\ &= 80\ \text{V} \\ V_2 &= 6.67 \times 24 \\ &= 160\ \text{V} \end{aligned}$$
4. **Power in the 600 W heater.**
   $$\begin{aligned} P_2 &= \frac{160^2}{24} \\ &= 1067\ \text{W} \end{aligned}$$
   78% over its rating.
5. **Power in the 1200 W heater.**
   $$\begin{aligned} P_1 &= \frac{80^2}{12} \\ &= 533\ \text{W} \end{aligned}$$
6. **What survives.** A heater may survive that for a while; a TV power supply rated 132 V maximum won't.

**Answer:** the 1200 W heater gets 80 V and 533 W, and the 600 W heater gets 160 V and 1067 W, 78% over its rating.
:::
:::

::: example
## A 15 A load runs on 30 m of 12 AWG cable from the panel at 120 V. What's the voltage drop? And a 4800 W, 240 V load on 30 m of 10 AWG?

::: solution
1. **Resistance of the 12 AWG run.** The round trip is 60 m, so
   $$\begin{aligned} R &= 60 \times 5.21\ \text{m}\Omega \\ &= 0.313\ \Omega \end{aligned}$$
2. **Drop on the 15 A load.**
   $$\begin{aligned} \Delta V &= 15 \times 0.313 \\ &= 4.69\ \text{V} \end{aligned}$$
   That's 3.9% of 120 V: over the 3% recommendation, so a run this long should use 10 AWG.
3. **Drop on the 240 V load.** It draws 20 A through two 30 m conductors of 3.28 mΩ/m:
   $$\begin{aligned} \Delta V &= 20 \times 60 \times 0.00328 \\ &= 3.94\ \text{V} \end{aligned}$$
   only 1.6% of 240 V.
4. **The same load at 120 V.** It would draw 40 A and lose 7.9 V, 6.6%.
5. **Why the higher voltage helps.** Doubling the voltage halves the current, halves the drop and doubles the base it's compared with.

**Answer:** the 15 A load loses 4.69 V (3.9%), and the 240 V load loses 3.94 V (1.6%).
:::
:::

::: check
given: P1 = 600 | 1200 | 1500 | 1800; P2 = 300 | 900 | 1000
answer: abs(P1 - P2)/120
unit: A
tolerance: 0.5%

## A house draws {P1} W of resistive load on L1 and {P2} W on L2, at 120 V each. What current does the neutral carry?

::: right
Right. The legs are opposite, so the neutral carries the difference: {answer}.
:::

::: misses
- [(P1 + P2)/120] The legs' return currents oppose each other in the neutral.
- [(P1 + P2)/240] That's the average leg current. The neutral carries the difference.
- [any] Not yet. $I_N = |I_1 - I_2|$.
:::
:::

::: check
kind: parts
given: P1 = 1000 | 1500 | 2000; P2 = 500 | 800; P3 = 3600 | 4800 | 7200

## L1 has {P1} W of 120 V loads, L2 has {P2} W, and a {P3} W load runs from L1 to L2 at 240 V.

::: part
answer: P1/120 + P3/240
unit: A
tolerance: 0.5%

### What current does L1 carry?

::: misses
- [P1/120 + P3/120] The 240 V load draws $P/240$, not $P/120$.
- [P1/120] Include the 240 V load, which draws through both hots.
- [any] Not yet. $P_1/120 + P_3/240$.
:::
:::

::: part
answer: abs(P1 - P2)/120
unit: A
tolerance: 0.5%

### And the neutral?

::: misses
- [abs(P1 - P2)/120 + P3/240] The 240 V load doesn't use the neutral.
- [any] Not yet. Only the 120 V loads' difference.
:::
:::

::: right
Right. 240 V loads add to both hots equally and leave the neutral alone.
:::
:::

::: check
kind: parts
given: P1 = 1500 | 1200 | 2000; P2 = 100 | 300 | 600

## The neutral opens while L1 has {P1} W of resistive load (rated at 120 V) and L2 has {P2} W.

::: part
answer: 240*P1/(P1 + P2)
unit: V
tolerance: 0.5%

### What voltage does L2's load see?

::: misses
- [240*P2/(P1 + P2)] That's the heavier load's share. The lighter load has the larger resistance and takes more voltage.
- [120] With the neutral open, the legs share 240 V by resistance.
- [any] Not yet. $V_2 = 240P_1/(P_1 + P_2)$.
:::
:::

::: part
answer: (240*P1/(P1 + P2))^2/(120^2/P2)
unit: W
tolerance: 0.5%

### What power does L2's load dissipate?

::: misses
- [P2] Its voltage has changed, so its power has.
- [any] Not yet. $V_2^2/R_2$ with $R_2 = 120^2/P_2$.
:::
:::

::: right
Right. The lightly loaded leg rises toward 240 V, and its loads dissipate several times their rating.
:::
:::

::: check
given: I = 10 | 15 | 20; L = 15 | 25 | 40; r = 8.28 | 5.21 | 3.28
answer: I*2*L*r*1e-3/120*100
tolerance: 0.5%

## A {I} A load runs at 120 V on {L} m of cable with {r} mΩ/m conductors. What percentage of 120 V is lost in the wiring?

::: right
Right. The round trip is $2L$, so the drop is $I \times 2Lr$ = {answer}% of 120 V.
:::

::: misses
- [I*L*r*1e-3/120*100] Current goes out on the hot and back on the neutral: count both.
- [I*2*L*r*1e-3] That's the drop in volts. Give it as a percentage of 120 V.
- [any] Not yet. $100 \times I \cdot 2Lr/120$.
:::
:::

::: check
kind: parts
given: I1 = 10 | 12 | 16; I2 = 6 | 8; p1 = 0.8 | 0.9; p2 = 1 | 0.6

## L1 carries {I1} A at power factor {p1} lagging, and L2 carries {I2} A at power factor {p2} lagging.

::: part
answer: sqrt(I1^2 + I2^2 - 2*I1*I2*cos(acos(p1) - acos(p2)))
unit: A
tolerance: 0.5%

### What's the neutral current's magnitude?

::: misses
- [abs(I1 - I2)] That's only right when the power factors match.
- [I1 + I2] The two legs' currents oppose each other in the neutral.
- [any] Not yet. $|I_1e^{-j\varphi_1} - I_2e^{-j\varphi_2}|$, which is $\sqrt{I_1^2 + I_2^2 - 2I_1I_2\cos(\varphi_1 - \varphi_2)}$.
:::
:::

::: right
Right. When the loads' phase angles differ, their currents no longer cancel along a line, and the neutral carries more than the simple difference.
:::
:::

::: check
kind: choice

## Why is the neutral bonded to the equipment ground only at the main service panel, and not at every outlet?

- [x] So that normal return current flows only on the neutral, leaving the ground wire carrying current only during a fault
- [ ] Because bonding at outlets would short the hot to ground
- [ ] To keep the neutral at 120 V
- [ ] Because the ground wire is too thin to bond more than once

::: right
Right. Bond them at every outlet and the return current would split between the neutral and the ground wires and the metal they connect to, putting current and voltage on enclosures, defeating GFCIs, and confusing fault detection.
:::

::: misses
- [2] Bonding neutral to ground doesn't touch the hot. The problem is return current on the ground path.
- [3] The neutral is near earth potential; bonding keeps it there.
- [4] The ground wire is sized to carry fault current; the problem is normal current flowing on it.
:::
:::

::: check
kind: derivation
vars: P1 = 100..3000, P2 = 100..3000

## Find the voltage across leg 2's loads with the neutral open, from the loads' 120 V power ratings.

::: step
answer: 14400/P2

### What is leg 2's resistance?
:::

::: step
answer: 240/(14400/P1 + 14400/P2)

### What current flows through both legs in series across 240 V?
:::

::: step
answer: 240*P1/(P1 + P2)

### What is $V_2$, simplified?
:::

::: right
Right. $V_2 = 240P_1/(P_1 + P_2)$: whichever leg has less load gets more of the 240 V.
:::
:::

::: check
kind: python
given: Rs = 0.02 | 0.05 | 0.1

## Model a split-phase panel. The service conductors (each hot and the neutral) have `Rs` = {Rs} Ω from the transformer. Write `panel(loads)`, where `loads` is a list of `(leg, watts)` with leg 1, 2 or 12 (a 240 V load) and watts rated at 120 V or 240 V, all resistive. Solve the circuit with the transformer as two ideal 120 V sources and return `(v1, v2)`, the voltages across leg 1's and leg 2's 120 V loads. Use `numpy.linalg.solve` on the node equations. Also set `open_v` to `panel_open([(1, 1200), (2, 600)])`'s result for an open neutral (the neutral conductor's resistance infinite).

```python starter
def panel(loads):
    return 120.0, 120.0
def panel_open(loads):
    return 120.0, 120.0
open_v = panel_open([(1, 1200), (2, 600)])
print(panel([(1, 1200), (2, 600)]), open_v)
```

```python solution
import numpy as np
def solve(loads, rn):
    g1 = sum(w / 120**2 for leg, w in loads if leg == 1)
    g2 = sum(w / 120**2 for leg, w in loads if leg == 2)
    g12 = sum(w / 240**2 for leg, w in loads if leg == 12)
    gs = 1 / Rs
    gn = 0.0 if rn is None else 1 / rn
    # unknowns: panel nodes A (L1), B (L2), N (neutral); sources +120 V and -120 V behind Rs; transformer center at 0
    G = np.array([[gs + g1 + g12, -g12, -g1],
                  [-g12, gs + g2 + g12, -g2],
                  [-g1, -g2, gn + g1 + g2]])
    b = np.array([120 * gs, -120 * gs, 0.0])
    a, bb, n = np.linalg.solve(G, b)
    return a - n, n - bb
def panel(loads):
    return solve(loads, Rs)
def panel_open(loads):
    return solve(loads, None)
open_v = panel_open([(1, 1200), (2, 600)])
print(panel([(1, 1200), (2, 600)]), open_v)
```

```python tests
v1, v2 = panel([(1, 1200), (2, 1200)])
i = 120 / (12 + Rs)
assert abs(v1 - 12 * i) < 1e-9 and abs(v2 - 12 * i) < 1e-9, "Balanced loads: no neutral current, so each load sees 120 V less only its own hot's drop."
v1, v2 = panel([(1, 1200), (2, 600)])
assert v1 < v2, "With the neutral's drop, the heavier leg's load sees less voltage."
w1, w2 = panel([(1, 1200), (2, 600), (12, 4800)])
assert w1 < v1 and w2 < v2, "A 240 V load adds drop on both hots."
o1, o2 = open_v
r1, r2 = 12.0, 24.0
i = 240 / (r1 + r2 + 2 * Rs)
assert abs(o1 - i * r1) < 1e-9 and abs(o2 - i * r2) < 1e-9, "With the neutral open, the two loads are in series across 240 V plus two hots' resistance."
```

::: right
Right. Nodal analysis handles the whole panel at once, and the open neutral is just a zero conductance.
:::
:::

::: explain
## An electrician finds that when a 1500 W space heater turns on in one room, the lights in another room get noticeably brighter. Explain what's probably wrong, and why it's dangerous.

::: model
Lights getting brighter, rather than dimmer, when a big load turns on points to a high-resistance or open neutral, usually a loose or corroded connection at the panel or the service drop. With a good neutral, each leg's loads see 120 V regardless of the other leg. With a poor neutral, the neutral point floats: the heater on one leg pulls the neutral toward that leg's hot, which lowers the heater leg's voltage and raises the other leg's. The other leg's lamps get more than 120 V and brighten. The worse the connection and the more unbalanced the loads, the closer the light leg comes to 240 V, enough to burn out lamps and destroy electronics, and the bad connection itself heats up and can start a fire. It needs a utility or electrician repair, not a new lamp.
:::
:::

::: practice

::: check
given: P = 1800 | 3600 | 5000; V = 120 | 240
answer: P/V
unit: A
tolerance: 0.5%

## A {P} W resistive load runs at {V} V. What current does it draw?

::: misses
- [P*V] Divide power by voltage.
- [any] $I = P/V$.
:::
:::

::: check
given: P1 = 800 | 1500; P2 = 60 | 200 | 400
answer: 240*P1/(P1 + P2)
unit: V
tolerance: 0.5%

## With an open neutral, leg 1 has {P1} W and leg 2 has {P2} W of 120 V loads. What voltage does leg 2 see?

::: misses
- [240*P2/(P1 + P2)] The lighter leg gets the larger share.
- [any] $240P_1/(P_1 + P_2)$.
:::
:::
:::