C3 · Lesson 18 · Three-phase power

Wye and delta, line and phase quantities, and steady power

Almost all electricity is generated and transmitted as three-phase AC: three sinusoids a third of a cycle apart, on three wires. That choice isn't arbitrary. Three phases deliver constant total power instead of the pulsing power of a single phase, which is why large motors run smoothly; they need less copper for the same power; and they make a rotating magnetic field almost for free, the basis of the induction motor. Analyzing a three-phase system is ordinary phasor analysis with one geometric fact: the three phasors are spaced 120° apart.

  • The three phase voltages of a balanced supply, a third of a cycle apart. The dashed line along zero is their sum: always zero.
  • The dashed line near the top is the total power into three equal resistors, scaled to fit: it doesn't ripple at all.
  • Compare with a single phase, whose power pulses between zero and twice its average a hundred times a second (at 50 Hz).

Predict

A three-phase supply has 230 V RMS from each line to neutral. What voltage is between two lines?

Name it

Balanced three-phase

The three phase voltages are V∠0°, V∠−120° and V∠120°, which add to zero. A balanced load has the same impedance in each phase, so the three currents are equal in size and also 120° apart.

Wye and delta

Wye (Y)Delta (Δ)
each phase connectsline to neutralline to line
line voltageVL=3VphVL=Vph
line currentIL=IphIL=3Iph

A balanced delta load of ZΔ draws the same line currents as a wye of ZY=ZΔ/3 (C1.11).

Power

Total power is three times one phase's, which works out the same for both connections:

P=3VphIphcos⁡φ=3VLILcos⁡φ

and the total instantaneous power is constant, equal to P at every moment, since cos2⁡θ+cos2⁡(θ−120°)+cos2⁡(θ+120°)=32.

Unbalanced loads

If the phases draw different currents, they no longer cancel at the star point, and the neutral wire carries the phasor sum Ia+Ib+Ic. In a balanced system it carries nothing, which is why high-voltage transmission lines have no neutral conductor.

Worked example

A balanced 10 kW motor at pf 0.85 runs from a 230/400 V supply. What line current does it draw?

Show the solution
  1. Line current. IL=P3VLcos⁡φ=10,0003×400×0.85=17.0A
  2. Check. Add up the three phases: P=3×230×17.0×0.85=9.97kW

Answer the motor draws 17.0 A in each line.

Worked example

A wye of resistive loads draws 10, 8 and 6 A in phases a, b and c. What current does the neutral carry?

Show the solution
  1. Add the phase currents as phasors. IN=|10∠0°+8∠−120°+6∠120°|=3.46A
  2. Why it's small. That's much less than any phase current, because the phasors still partly cancel.

Answer the neutral carries 3.46 A.

Worked example

Three 50 Ω heating elements run from a 400 V three-phase supply. How much power do they give in wye, and in delta?

Show the solution
  1. Phase voltage in wye. In wye each element sees the phase voltage: Vp=4003=231V
  2. Power in wye. Each element dissipates P=231250=1067W so 3.2 kW in all.
  3. Power in delta. Each element sees the full 400 V line voltage: P=400250=3200W so 9.6 kW in all.
  4. Compare. Switching from wye to delta triples the power.
  5. Star–delta starters. Starters for induction motors use this in reverse: start in wye at a third of the power and current, then switch to delta once the motor is up to speed.

Answer 3.2 kW in wye and 9.6 kW in delta.

Check

A wye supply has 230 V from each line to neutral. What is the line-to-line voltage?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

Check

A balanced load draws 10 A per line from a 400 V (line-to-line) supply at pf 0.95. What power does it take?

Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.

Check

A balanced 50 kW load at pf 0.9 runs from 400 V line-to-line. What line current does it draw?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A balanced delta load draws 17.3 A in each line. What current flows in each phase of the delta?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A wye of resistive loads draws 10, 8 and 6 A in phases a, b and c. What does the neutral carry?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A balanced wye load has 30 Ω per phase. What delta load draws the same line currents?

Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.

Check

Three 50 Ω elements run from a 208 V (line) three-phase supply.

(a)

What power do they give in wye?

Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.

(b)

And in delta?

Check

Three resistors R on a three-phase supply of line voltage V.

Step 1

What's the phase voltage in wye?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does a three-phase motor run more smoothly than a single-phase one?

Practice

Keep practicing

10 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.