C3 · Lesson 18 · Three-phase power
Wye and delta, line and phase quantities, and steady power
Almost all electricity is generated and transmitted as three-phase AC: three sinusoids a third of a cycle apart, on three wires. That choice isn't arbitrary. Three phases deliver constant total power instead of the pulsing power of a single phase, which is why large motors run smoothly; they need less copper for the same power; and they make a rotating magnetic field almost for free, the basis of the induction motor. Analyzing a three-phase system is ordinary phasor analysis with one geometric fact: the three phasors are spaced 120° apart.
- The three phase voltages of a balanced supply, a third of a cycle apart. The dashed line along zero is their sum: always zero.
- The dashed line near the top is the total power into three equal resistors, scaled to fit: it doesn't ripple at all.
- Compare with a single phase, whose power pulses between zero and twice its average a hundred times a second (at 50 Hz).
Predict
A three-phase supply has 230 V RMS from each line to neutral. What voltage is between two lines?
About 400 V: V. Two phasors of 230 V spaced 120° apart differ by a phasor of length . That's why European three-phase supplies are labeled 230/400 V and North American ones 120/208 V.
Name it
Balanced three-phase
The three phase voltages are , and , which add to zero. A balanced load has the same impedance in each phase, so the three currents are equal in size and also 120° apart.
Wye and delta
| Wye (Y) | Delta (Δ) | |
|---|---|---|
| each phase connects | line to neutral | line to line |
| line voltage | ||
| line current |
A balanced delta load of draws the same line currents as a wye of (C1.11).
Power
Total power is three times one phase's, which works out the same for both connections:
and the total instantaneous power is constant, equal to at every moment, since .
Unbalanced loads
If the phases draw different currents, they no longer cancel at the star point, and the neutral wire carries the phasor sum . In a balanced system it carries nothing, which is why high-voltage transmission lines have no neutral conductor.
Worked example
A balanced 10 kW motor at pf 0.85 runs from a 230/400 V supply. What line current does it draw?
Show the solution
- Line current.
- Check. Add up the three phases:
Answer the motor draws 17.0 A in each line.
Worked example
A wye of resistive loads draws 10, 8 and 6 A in phases a, b and c. What current does the neutral carry?
Show the solution
- Add the phase currents as phasors.
- Why it's small. That's much less than any phase current, because the phasors still partly cancel.
Answer the neutral carries 3.46 A.
Worked example
Three 50 Ω heating elements run from a 400 V three-phase supply. How much power do they give in wye, and in delta?
Show the solution
- Phase voltage in wye. In wye each element sees the phase voltage:
- Power in wye. Each element dissipates so 3.2 kW in all.
- Power in delta. Each element sees the full 400 V line voltage: so 9.6 kW in all.
- Compare. Switching from wye to delta triples the power.
- Star–delta starters. Starters for induction motors use this in reverse: start in wye at a third of the power and current, then switch to delta once the motor is up to speed.
Answer 3.2 kW in wye and 9.6 kW in delta.
Check
A wye supply has 230 V from each line to neutral. What is the line-to-line voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A balanced load draws 10 A per line from a 400 V (line-to-line) supply at pf 0.95. What power does it take?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
A balanced 50 kW load at pf 0.9 runs from 400 V line-to-line. What line current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A balanced delta load draws 17.3 A in each line. What current flows in each phase of the delta?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A wye of resistive loads draws 10, 8 and 6 A in phases a, b and c. What does the neutral carry?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A balanced wye load has 30 Ω per phase. What delta load draws the same line currents?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Three 50 Ω elements run from a 208 V (line) three-phase supply.
(a)
What power do they give in wye?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
(b)
And in delta?
Check
Three resistors R on a three-phase supply of line voltage V.
Step 1
What's the phase voltage in wye?
Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.
Step 2
What total power do they give in wye?
Step 3
In delta?
Explain why
Why does a three-phase motor run more smoothly than a single-phase one?
In a single phase, power flows as , pulsing from zero to twice its average every half cycle, so a single-phase motor's torque pulses too. In a balanced three-phase system the three phases' powers are curves shifted by a third of a cycle each, and their sum is exactly constant: whenever one phase is delivering little, the others are delivering more. A three-phase motor therefore receives steady power and produces steady torque, with less vibration and noise.