title: Three-phase power
heading: Wye and delta, line and phase quantities, and steady power
eyebrow: C3 · Lesson 18 · Three-phase power
xp: 40
---

::: hook
Almost all electricity is generated and transmitted as three-phase AC: three sinusoids a third of a cycle apart, on three wires. That choice isn't arbitrary. Three phases deliver constant total power instead of the pulsing power of a single phase, which is why large motors run smoothly; they need less copper for the same power; and they make a rotating magnetic field almost for free, the basis of the induction motor. Analyzing a three-phase system is ordinary phasor analysis with one geometric fact: the three phasors are spaced 120° apart.
:::

::: play
- The three phase voltages of a balanced supply, a third of a cycle apart. The dashed line along zero is their sum: always zero.
- The dashed line near the top is the total power into three equal resistors, scaled to fit: it doesn't ripple at all.
- Compare with a single phase, whose power pulses between zero and twice its average a hundred times a second (at 50 Hz).
:::
:::

```sim plot
view: graph
x: t = 0..40 ms
y: v = -400..400 V
slider: Vp = 100..400 step 5 = 325 V
plot: Vp*cos(2*pi*50*t/1000) | label: phase a | samples: 600
plot: Vp*cos(2*pi*50*t/1000 - 2*pi/3) | label: phase b | color: ch2 | samples: 600
plot: Vp*cos(2*pi*50*t/1000 + 2*pi/3) | label: phase c | color: ch3 | samples: 600
plot: Vp*cos(2*pi*50*t/1000) + Vp*cos(2*pi*50*t/1000 - 2*pi/3) + Vp*cos(2*pi*50*t/1000 + 2*pi/3) | label: sum | dashed | color: ch4 | samples: 600
plot: (cos(2*pi*50*t/1000)^2 + cos(2*pi*50*t/1000 - 2*pi/3)^2 + cos(2*pi*50*t/1000 + 2*pi/3)^2)*Vp/1.5*0.8 | label: total power (scaled) | dashed | color: ch5 | samples: 600
readout: phase voltage, V RMS = Vp/sqrt(2) | digits: 4
readout: line voltage, V RMS = Vp/sqrt(2)*sqrt(3) | digits: 4
```

::: predict
## A three-phase supply has 230 V RMS from each line to neutral. What voltage is between two lines?

- [ ] 230 V
- [ ] 460 V
- [x] About 400 V
- [ ] 115 V

::: reveal
About 400 V: $\sqrt3 \times 230 = 398$ V. Two phasors of 230 V spaced 120° apart differ by a phasor of length $2 \times 230\sin 60° = \sqrt3 \times 230$. That's why European three-phase supplies are labeled 230/400 V and North American ones 120/208 V.
:::
:::

::: nameit
## Balanced three-phase

The three phase voltages are $V\angle 0°$, $V\angle{-120°}$ and $V\angle 120°$, which add to zero. A **balanced** load has the same impedance in each phase, so the three currents are equal in size and also 120° apart.

## Wye and delta

| | Wye (Y) | Delta (Δ) |
|---|---|---|
| each phase connects | line to neutral | line to line |
| line voltage | $V_L = \sqrt3V_\text{ph}$ | $V_L = V_\text{ph}$ |
| line current | $I_L = I_\text{ph}$ | $I_L = \sqrt3I_\text{ph}$ |

A balanced delta load of $Z_\Delta$ draws the same line currents as a wye of $Z_Y = Z_\Delta/3$ (C1.11).

## Power

Total power is three times one phase's, which works out the same for both connections:

$$P = 3V_\text{ph}I_\text{ph}\cos\varphi = \sqrt3V_LI_L\cos\varphi$$

and the total instantaneous power is constant, equal to $P$ at every moment, since $\cos^2\theta + \cos^2(\theta - 120°) + \cos^2(\theta + 120°) = \frac32$.

## Unbalanced loads

If the phases draw different currents, they no longer cancel at the star point, and the **neutral** wire carries the phasor sum $I_a + I_b + I_c$. In a balanced system it carries nothing, which is why high-voltage transmission lines have no neutral conductor.
:::

::: example
## A balanced 10 kW motor at pf 0.85 runs from a 230/400 V supply. What line current does it draw?

::: solution
1. **Line current.**
   $$\begin{aligned} I_L &= \frac{P}{\sqrt3V_L\cos\varphi} \\ &= \frac{10{,}000}{\sqrt3 \times 400 \times 0.85} \\ &= 17.0\ \text{A} \end{aligned}$$
2. **Check.** Add up the three phases:
   $$\begin{aligned} P &= 3 \times 230 \times 17.0 \times 0.85 \\ &= 9.97\ \text{kW} \end{aligned}$$

**Answer:** the motor draws 17.0 A in each line.
:::
:::

::: example
## A wye of resistive loads draws 10, 8 and 6 A in phases a, b and c. What current does the neutral carry?

::: solution
1. **Add the phase currents as phasors.**
   $$\begin{aligned} I_N &= |10\angle 0° + 8\angle{-120°} \\ &\quad + 6\angle 120°| \\ &= 3.46\ \text{A} \end{aligned}$$
2. **Why it's small.** That's much less than any phase current, because the phasors still partly cancel.

**Answer:** the neutral carries 3.46 A.
:::
:::

::: example
## Three 50 Ω heating elements run from a 400 V three-phase supply. How much power do they give in wye, and in delta?

::: solution
1. **Phase voltage in wye.** In wye each element sees the phase voltage:
   $$\begin{aligned} V_p &= \frac{400}{\sqrt3} \\ &= 231\ \text{V} \end{aligned}$$
2. **Power in wye.** Each element dissipates
   $$\begin{aligned} P &= \frac{231^2}{50} \\ &= 1067\ \text{W} \end{aligned}$$
   so 3.2 kW in all.
3. **Power in delta.** Each element sees the full 400 V line voltage:
   $$\begin{aligned} P &= \frac{400^2}{50} \\ &= 3200\ \text{W} \end{aligned}$$
   so 9.6 kW in all.
4. **Compare.** Switching from wye to delta triples the power.
5. **Star–delta starters.** Starters for induction motors use this in reverse: start in wye at a third of the power and current, then switch to delta once the motor is up to speed.

**Answer:** 3.2 kW in wye and 9.6 kW in delta.
:::
:::

::: check
given: V = 120 | 230 | 7200
answer: V*sqrt(3)
unit: V
tolerance: 0.5%

## A wye supply has {V} V from each line to neutral. What is the line-to-line voltage?

::: right
Right. $\sqrt3V_\text{ph}$ = {answer}.
:::

::: misses
- [2*V] The phasors are 120° apart, not opposite.
- [any] Not yet. $V_L = \sqrt3V_\text{ph}$.
:::
:::

::: check
given: VL = 208 | 400 | 480; I = 10 | 50; pf = 0.8 | 0.95
answer: sqrt(3)*VL*I*pf/1000
unit: kW
tolerance: 0.5%

## A balanced load draws {I} A per line from a {VL} V (line-to-line) supply at pf {pf}. What power does it take?

::: right
Right. $\sqrt3V_LI_L\cos\varphi$ = {answer}.
:::

::: misses
- [3*VL*I*pf/1000] With line voltage, use $\sqrt3$, not 3.
- [any] Not yet. $P = \sqrt3V_LI_L\text{pf}$.
:::
:::

::: check
given: P = 5 | 50 | 250; VL = 400 | 480; pf = 0.75 | 0.9
answer: P*1000/(sqrt(3)*VL*pf)
unit: A
tolerance: 0.5%

## A balanced {P} kW load at pf {pf} runs from {VL} V line-to-line. What line current does it draw?

::: right
Right. $\frac{P}{\sqrt3V_L\text{pf}}$ = {answer}.
:::

::: misses
- [P*1000/(VL*pf)] Three-phase power includes a factor $\sqrt3$.
- [any] Not yet. Solve $P = \sqrt3V_LI_L\text{pf}$.
:::
:::

::: check
given: IL = 10 | 17.3 | 50
answer: IL/sqrt(3)
unit: A
tolerance: 0.5%

## A balanced delta load draws {IL} A in each line. What current flows in each phase of the delta?

::: right
Right. $I_L/\sqrt3$ = {answer}.
:::

::: misses
- [IL/3] It's $\sqrt3$, from the 120° spacing.
- [any] Not yet. $I_\text{ph} = I_L/\sqrt3$.
:::
:::

::: check
given: Ia = 10 | 12; Ib = 8 | 12; Ic = 4 | 6
answer: abs(Ia + Ib*exp(-2*pi*j/3) + Ic*exp(2*pi*j/3))
unit: A
tolerance: 0.5%

## A wye of resistive loads draws {Ia}, {Ib} and {Ic} A in phases a, b and c. What does the neutral carry?

::: right
Right. The phasor sum: {answer}.
:::

::: misses
- [Ia + Ib + Ic] Add the currents as phasors, 120° apart.
- [any] Not yet. $|I_a + I_b\angle{-120°} + I_c\angle 120°|$.
:::
:::

::: check
given: Z = 15 | 30 | 90
answer: Z*3
unit: Ω
tolerance: 0.5%

## A balanced wye load has {Z} Ω per phase. What delta load draws the same line currents?

::: right
Right. $Z_\Delta = 3Z_Y$ = {answer}.
:::

::: misses
- [Z/3] Going from wye to delta multiplies by 3.
- [any] Not yet. $Z_\Delta = 3Z_Y$.
:::
:::

::: check
kind: parts
given: R = 20 | 50 | 100; V = 208 | 400

## Three {R} Ω elements run from a {V} V (line) three-phase supply.

::: part
answer: 3*(V/sqrt(3))^2/R/1000
unit: kW
tolerance: 0.5%

### What power do they give in wye?

::: misses
- [any] Each sees $V/\sqrt3$.
:::
:::

::: part
answer: 3*V^2/R/1000
unit: kW
tolerance: 0.5%

### And in delta?

::: misses
- [any] Each sees the full line voltage.
:::
:::
:::

::: check
kind: derivation
vars: V = 100..1000, R = 1..1000

## Three resistors R on a three-phase supply of line voltage V.

::: step
answer: V/sqrt(3)

### What's the phase voltage in wye?
:::

::: step
answer: V^2/R

### What total power do they give in wye?
:::

::: step
answer: 3*V^2/R

### In delta?
:::

::: right
Right. Delta gives three times the power of wye with the same resistors.
:::
:::

::: explain
## Why does a three-phase motor run more smoothly than a single-phase one?

::: model
In a single phase, power flows as $\cos^2$, pulsing from zero to twice its average every half cycle, so a single-phase motor's torque pulses too. In a balanced three-phase system the three phases' powers are $\cos^2$ curves shifted by a third of a cycle each, and their sum is exactly constant: whenever one phase is delivering little, the others are delivering more. A three-phase motor therefore receives steady power and produces steady torque, with less vibration and noise.
:::
:::

::: practice

::: check
given: VL = 208 | 380 | 400 | 415 | 480 | 600 | 690
answer: VL/sqrt(3)
unit: V
tolerance: 0.5%

## A system has {VL} V line to line. What is the line-to-neutral voltage?

::: misses
- [any] $V_L/\sqrt3$.
:::
:::

::: check
given: V = 120 | 230; I = 5 | 20; pf = 0.7 | 1
answer: 3*V*I*pf/1000
unit: kW
tolerance: 0.5%

## Each phase of a balanced wye has {V} V across it and {I} A through it at pf {pf}. What is the total power?

::: misses
- [any] $3V_\text{ph}I_\text{ph}\text{pf}$.
:::
:::

::: check
given: I = 5 | 10 | 15 | 20 | 30 | 40
answer: 0
unit: A
tolerance: 0.01 A

## A balanced wye load draws {I} A in every phase. What current flows in the neutral?

::: misses
- [any] Balanced currents cancel.
:::
:::
:::