C31 of 29
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

C3 · Lesson 1 · Why AC

Why the power grid alternates

The electricity in a wall socket reverses direction 100 or 120 times a second. That's not an accident of history: it's what spinning generators naturally make, and it's what transformers need to step voltage up for long-distance transmission and back down for your home. Stepping up matters because a power line's losses grow with the square of the current it carries. Send the same power at a hundred times the voltage and the line wastes ten thousand times less.

Play

  • A power line with resistance R delivers power P. The curve shows the share of the power lost in the line at each transmission voltage.
  • Read the loss at 11 kV, then at 110 kV. How do they compare?
  • Double the line resistance, or the power. What happens to the curve?

Predict

A line delivers the same power at 10 times the voltage. What happens to the power it wastes as heat?

Name it

The case for AC

Generators make sinusoids. A coil turning steadily in a magnetic field has a flux through it of Φ0cos⁡ωt, and Faraday's law gives an EMF ωNΦ0sin⁡ωt (B6.4). Big generators turn at a fixed speed locked to the grid: 3000 or 3600 rpm for a two-pole machine on a 50 Hz or 60 Hz grid.

Transformers need change. A transformer couples two coils through a shared core; its secondary voltage is Vs=VpNs/Np (B6.10). It works by induction, so it needs a changing current. With AC it changes voltage at over 99% efficiency, with no moving parts.

High voltage for transmission. Delivering power P at voltage V over a line of resistance R:

I=PVPloss=I2R=P2RV2

so the share lost is PR/V2. Typical voltages:

  • generation: 10 to 25 kV;
  • long-distance transmission: 110 to 765 kV;
  • local distribution: 4 to 35 kV;
  • homes: 120/240 V (North America) or 230 V (most of the world).

Frequency. 60 Hz in the Americas and parts of Asia, 50 Hz in most of the rest of the world: a period of 16.7 ms or 20 ms.

DC's return. Power electronics can now convert DC voltages efficiently too, so very long or undersea links increasingly use high-voltage DC (HVDC), which avoids the cable capacitance and the reactive power that AC lines carry (lesson 16). Phones, computers and LED lights all run on DC internally, converted from AC at the plug.

Worked example

A town draws 100 kW through lines with 1 Ω of total resistance. What is lost at 400 V, and at 11 kV?

Show the solution
  1. Current at 400 V. I=100kW400V=250A
  2. Loss at 400 V. P=I2R=2502×1=62.5kW That's most of the delivered power.
  3. The same at 11 kV. The current is 9.1 A, so the loss is P=9.12×1=83W
  4. Why it matters. That's why power travels at high voltage and transformers step it down near the user.

Answer the lines lose 62.5 kW at 400 V and only 83 W at 11 kV.

Worked example

A distribution transformer steps 11 kV down to 230 V. What turns ratio does it need?

Show the solution
  1. Turns ratio. The turns ratio equals the voltage ratio: N1N2=11,000230=47.8
  2. Current. It steps the current up by the same ratio.

Answer 47.8 primary turns per secondary turn.

Worked example

How long is one wavelength of 50 Hz power, and what fraction of it does a 300 km transmission line span?

Show the solution
  1. Wavelength. Along a line, signals travel at nearly the speed of light, so λ=cf=3×10850=6000km
  2. The line's share. A 300 km line spans 3006000 of that, or 5%.
  3. Why lumped analysis works. That's why lumped circuit analysis works for nearly all power wiring: the voltage along a building's wires is the same everywhere at a given instant.
  4. When it doesn't. Only long transmission lines, hundreds of kilometers, need the wave treatment of C10, and in a gigahertz circuit the same 5% is a few millimeters of trace.

Answer one wavelength is 6000 km, and a 300 km line spans 5% of it.

Check

A line delivers 100 MW at 110 kV. What current does it carry?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A line with 2 Ω of resistance carries 200 A. How much power does it lose as heat?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

The transmission voltage is raised 5 times for the same delivered power. By what factor do the line losses fall?

Check

A step-up transformer has 100 primary turns and 5000 secondary turns. Its primary is fed 22 kV. What is the secondary voltage?

Write units the way you normally would: 1.5 kV, 1500 V and 0.0015 MV are the same answer.

Check

Why did AC win over DC for the early power grid?

Check

Power at 60 Hz travels along a 100 km line at nearly the speed of light.

(a)

How long is one wavelength?

Write units the way you normally would: 1.5 km and 1500 m are the same answer.

(b)

What percentage of a wavelength does the line span?

Check

A load of power P is fed at voltage V through a line of resistance R (unity power factor).

Step 1

What current flows?

Type it the way you would write it, like 3sin(2πft) or 3*sin(2*pi*f*t). Angles can be in radians or carry a degree sign, like 45°.

Explain why

Why does raising the transmission voltage reduce the power lost in a line?

Practice

Keep practicing

8 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.