title: "Why AC: the grid, generators and transformers"
heading: Why the power grid alternates
eyebrow: C3 · Lesson 1 · Why AC
xp: 40
---

::: hook
The electricity in a wall socket reverses direction 100 or 120 times a second. That's not an accident of history: it's what spinning generators naturally make, and it's what transformers need to step voltage up for long-distance transmission and back down for your home. Stepping up matters because a power line's losses grow with the square of the current it carries. Send the same power at a hundred times the voltage and the line wastes ten thousand times less.

::: play
- A power line with resistance R delivers power P. The curve shows the share of the power lost in the line at each transmission voltage.
- Read the loss at 11 kV, then at 110 kV. How do they compare?
- Double the line resistance, or the power. What happens to the curve?
:::
:::

```sim plot
view: graph
x: V = 5..1000 kV log
y: loss = 0.001..100 % log
slider: P = 1..500 = 100 MW log
slider: R = 1..20 step 1 = 5 Ω
slider: Vt = 5..1000 = 110 kV log
plot: 100*P*1e6*R/(V*1e3)^2 | label: share of power lost in the line
point: Vt, 100*P*1e6*R/(Vt*1e3)^2
readout: line current in A = P*1e6/(Vt*1e3)
readout: power lost in MW = (P*1e6/(Vt*1e3))^2*R/1e6
readout: share lost in % = 100*P*1e6*R/(Vt*1e3)^2
```

::: predict
## A line delivers the same power at 10 times the voltage. What happens to the power it wastes as heat?

- [ ] It's 10 times smaller
- [x] It's 100 times smaller
- [ ] It stays the same
- [ ] It's 10 times larger

::: reveal
100 times smaller. For the same power, ten times the voltage means a tenth of the current ($P = VI$), and the line's loss is $I^2R$, so it falls by $10^2$. That's why long-distance lines run at hundreds of kilovolts, and why the grid needed a cheap, efficient way to change voltages: the transformer, which only works with alternating current.
:::
:::

::: nameit
## The case for AC

**Generators make sinusoids.** A coil turning steadily in a magnetic field has a flux through it of $\Phi_0\cos\omega t$, and Faraday's law gives an EMF $\omega N\Phi_0\sin\omega t$ (B6.4). Big generators turn at a fixed speed locked to the grid: 3000 or 3600 rpm for a two-pole machine on a 50 Hz or 60 Hz grid.

**Transformers need change.** A transformer couples two coils through a shared core; its secondary voltage is $V_s = V_p N_s/N_p$ (B6.10). It works by induction, so it needs a changing current. With AC it changes voltage at over 99% efficiency, with no moving parts.

**High voltage for transmission.** Delivering power $P$ at voltage $V$ over a line of resistance $R$:

$$I = \frac PV \qquad P_\text{loss} = I^2R = \frac{P^2R}{V^2}$$

so the share lost is $PR/V^2$. Typical voltages:

- generation: 10 to 25 kV;
- long-distance transmission: 110 to 765 kV;
- local distribution: 4 to 35 kV;
- homes: 120/240 V (North America) or 230 V (most of the world).

**Frequency.** 60 Hz in the Americas and parts of Asia, 50 Hz in most of the rest of the world: a period of 16.7 ms or 20 ms.

**DC's return.** Power electronics can now convert DC voltages efficiently too, so very long or undersea links increasingly use high-voltage DC (HVDC), which avoids the cable capacitance and the reactive power that AC lines carry (lesson 16). Phones, computers and LED lights all run on DC internally, converted from AC at the plug.
:::

::: example
## A town draws 100 kW through lines with 1 Ω of total resistance. What is lost at 400 V, and at 11 kV?

::: solution
1. **Current at 400 V.**
   $$\begin{aligned} I &= \frac{100\ \text{kW}}{400\ \text{V}} \\ &= 250\ \text{A} \end{aligned}$$
2. **Loss at 400 V.**
   $$\begin{aligned} P &= I^2 R \\ &= 250^2 \times 1 \\ &= 62.5\ \text{kW} \end{aligned}$$
   That's most of the delivered power.
3. **The same at 11 kV.** The current is 9.1 A, so the loss is
   $$\begin{aligned} P &= 9.1^2 \times 1 \\ &= 83\ \text{W} \end{aligned}$$
4. **Why it matters.** That's why power travels at high voltage and transformers step it down near the user.

**Answer:** the lines lose 62.5 kW at 400 V and only 83 W at 11 kV.
:::
:::

::: example
## A distribution transformer steps 11 kV down to 230 V. What turns ratio does it need?

::: solution
1. **Turns ratio.** The turns ratio equals the voltage ratio:
   $$\begin{aligned} \frac{N_1}{N_2} &= \frac{11{,}000}{230} \\ &= 47.8 \end{aligned}$$
2. **Current.** It steps the current up by the same ratio.

**Answer:** 47.8 primary turns per secondary turn.
:::
:::

::: example
## How long is one wavelength of 50 Hz power, and what fraction of it does a 300 km transmission line span?

::: solution
1. **Wavelength.** Along a line, signals travel at nearly the speed of light, so
   $$\begin{aligned} \lambda &= \frac{c}{f} \\ &= \frac{3 \times 10^8}{50} \\ &= 6000\ \text{km} \end{aligned}$$
2. **The line's share.** A 300 km line spans $\frac{300}{6000}$ of that, or 5%.
3. **Why lumped analysis works.** That's why lumped circuit analysis works for nearly all power wiring: the voltage along a building's wires is the same everywhere at a given instant.
4. **When it doesn't.** Only long transmission lines, hundreds of kilometers, need the wave treatment of C10, and in a gigahertz circuit the same 5% is a few millimeters of trace.

**Answer:** one wavelength is 6000 km, and a 300 km line spans 5% of it.
:::
:::

::: check
given: P = 10 | 100 | 500; V = 110 | 230 | 500
answer: 1000*P/V
unit: A
tolerance: 0.5%

## A line delivers {P} MW at {V} kV. What current does it carry?

::: right
Right. $I = P/V$ = {answer}.
:::

::: misses
- [P/V] MW over kV gives kA. Give it in amps.
- [P*V] Divide power by voltage.
- [any] Not yet. $I = P/V$.
:::
:::

::: check
given: I = 100 | 200 | 500; R = 2 | 5 | 10
answer: I^2*R/1e6
unit: MW
tolerance: 0.5%

## A line with {R} Ω of resistance carries {I} A. How much power does it lose as heat?

::: right
Right. $I^2R$ = {answer}.
:::

::: misses
- [I*R/1e6] That's $IR$, the voltage drop. Power is $I^2R$.
- [I^2*R] Give it in MW.
- [any] Not yet. $P_\text{loss} = I^2R$.
:::
:::

::: check
given: k = 2 | 5 | 10 | 20
answer: k^2
tolerance: 0.5%

## The transmission voltage is raised {k} times for the same delivered power. By what factor do the line losses fall?

::: right
Right. The current falls {k} times, and losses go as $I^2$: {answer}.
:::

::: misses
- [k] Losses go as the square of the current.
- [any] Not yet. $P_\text{loss} \propto 1/V^2$.
:::
:::

::: check
given: Vp = 11 | 22 | 33; Np = 100 | 200; Ns = 2000 | 5000
answer: Vp*Ns/Np
unit: kV
tolerance: 0.5%

## A step-up transformer has {Np} primary turns and {Ns} secondary turns. Its primary is fed {Vp} kV. What is the secondary voltage?

::: right
Right. $V_s = V_pN_s/N_p$ = {answer}.
:::

::: misses
- [Vp*Np/Ns] That steps down. Multiply by $N_s/N_p$.
- [any] Not yet. Voltage scales with the turns ratio.
:::
:::

::: check
kind: choice

## Why did AC win over DC for the early power grid?

- [ ] AC is safer to touch
- [x] Transformers could change AC voltages efficiently, allowing high-voltage transmission with low losses
- [ ] DC can't power motors
- [ ] AC travels faster down wires

::: right
Right. High voltage cuts losses, and only AC could be transformed cheaply at the time.
:::

::: misses
- [1] AC at the same voltage is, if anything, more dangerous.
- [3] DC motors work well; Edison's grid ran them.
- [4] Both travel at about the same speed.
:::
:::

::: check
kind: parts
given: f = 50 | 60 | 400; L = 100 | 1000

## Power at {f} Hz travels along a {L} km line at nearly the speed of light.

::: part
answer: 3e8/f/1000
unit: km
tolerance: 0.5%

### How long is one wavelength?

::: misses
- [any] $\lambda = \frac cf$.
:::
:::

::: part
answer: L/(3e8/f/1000)*100
unit: %
tolerance: 0.5%

### What percentage of a wavelength does the line span?

::: misses
- [any] Line length over wavelength.
:::
:::
:::

::: check
kind: derivation
vars: P = 1000..10000000, V = 100..500000, R = 0.01..10

## A load of power P is fed at voltage V through a line of resistance R (unity power factor).

::: step
answer: P/V

### What current flows?
:::

::: step
answer: (P/V)^2*R

### What power does the line lose?
:::

::: step
answer: P*R/V^2

### What fraction of the delivered power is that?
:::

::: right
Right. The fraction falls as $1/V^2$, the reason for high-voltage transmission.
:::
:::

::: explain
## Why does raising the transmission voltage reduce the power lost in a line?

::: model
For a given amount of power delivered, the current needed is the power divided by the voltage, so a higher voltage means a smaller current. The line's resistance turns power into heat at a rate of current squared times resistance. Halving the current therefore quarters the loss, and raising the voltage tenfold cuts the loss a hundredfold, for the same wires.
:::
:::

::: practice

::: check
given: f = 16.7 | 25 | 50 | 60 | 400
answer: 1000/f
unit: ms
tolerance: 0.5%

## What is the period of a {f} Hz AC supply?

::: misses
- [f/1000] Period is one over frequency.
- [any] $T = 1/f$.
:::
:::

::: check
given: P = 1 | 5 | 20; V = 10 | 20
answer: 1000*P/V
unit: A
tolerance: 0.5%

## {P} MW at {V} kV. Current?

::: misses
- [P/V] Give it in amps: MW/kV is kA.
- [any] $P/V$.
:::
:::

::: check
given: Vp = 230 | 240; n = 10 | 20
answer: Vp/n
unit: V
tolerance: 0.5%

## A {n}:1 step-down transformer is fed {Vp} V. Its output?

::: misses
- [Vp*n] Step-down divides.
- [any] $V_p/n$.
:::
:::
:::