D1 · Lesson 6 · Faults and protection

What happens when a conductor shorts, how a transformer's impedance sets the fault current, short-circuit capacity, fuses, breakers and relays, inverse-time overcurrent curves, and how protection is coordinated so only the faulted section trips

A tree branch falls across a distribution line, or a squirrel bridges a transformer bushing, and in a millisecond the current through that spot jumps to tens of times its normal value. Left alone, it would melt conductors and destroy transformers. Protection systems detect the fault, decide which breaker should open, and clear it in a fraction of a second, ideally disconnecting only the faulted section so everyone else keeps their power. How large the fault current gets is set mostly by the impedances of the transformers and lines between the source and the fault.

  • The trip time of an inverse-time overcurrent relay against the fault current as a multiple M of its pickup setting, using the IEEE moderately inverse curve t=TD(0.0515M0.02−1+0.114), for a chosen time dial TD.
  • Larger faults trip faster. A relay closer to the source gets a larger time dial so that the relay nearest the fault trips first.
  • That margin between curves is coordination.

Predict

A 50 kVA, 240 V transformer has an impedance of 2%. If its secondary is shorted right at its terminals, about how much current flows?

Name it

Fault current

A short circuit leaves only the impedances of the source, transformers and lines to limit the current. Expressing a transformer's impedance as a per-unit (or percent) value Zpu of its rating makes the estimate quick:

Ifault=IratedZpu,Ssc=SratedZpu

where Ssc is the short-circuit capacity. Farther from the source, line impedance adds: a three-phase fault on a line of impedance Zline behind a source impedance Zs draws VL/[3(Zs+Zline)].

Protective devices

  • Fuses melt when overcurrent persists, fastest for the largest faults.
  • Circuit breakers interrupt the arc in air, oil, vacuum or SF₆, commanded by relays.
  • Overcurrent relays trip after a time that falls with current (inverse-time curves).
  • Distance relays on transmission lines measure the impedance to the fault; differential relays on transformers and buses trip when current in doesn't equal current out.

Coordination

Devices are set so that the one closest to the fault operates first, with the upstream one waiting a coordination margin (around 0.3 s) as backup. Most faults on overhead lines are temporary, so reclosers reopen and reclose a few times before locking out.

Worked example

A relay with time dial 1 sees faults of 2, 10 and 20 times its pickup. When does it trip? What's the fault current at the end of a 12.47 kV feeder with 0.5 Ω of source and 2 Ω of line impedance per phase?

Show the solution
  1. Trip times. Put M = 2, 10 and 20 into the moderately inverse curve with time dial 1: t(2)=3.80st(10)=1.21st(20)=0.95s
  2. Feeder fault current. The source and line add to 2.5 Ω per phase: If=124703×2.5=2.88kA
  3. What that means for relays. It's far below the tens of kiloamperes at the substation, which is why relays far out on a feeder need lower pickup settings.

Answer the relay trips in 3.80 s, 1.21 s and 0.95 s, and the fault at the end of the feeder draws 2.88 kA.

Worked example

A 50 MVA, 138/13.8 kV transformer has 10% impedance. What fault current can it deliver on its 13.8 kV side, ignoring the source behind it?

Show the solution
  1. Rated current. I=50MVA3×13.8kV=2092A
  2. Fault current. A bolted fault draws If=2092/0.10=20.9kA
  3. Short-circuit power. 50/0.10=500MVA Breakers on that bus must interrupt at least that much.

Answer it can deliver 20.9 kA, a short-circuit power of 500 MVA.

Worked example

A downstream relay with time dial 1 trips in 1.21 s for a fault at 10 times its pickup. An upstream relay sees the same multiple and must wait 0.3 s longer. What time dial does it need?

Show the solution
  1. Required trip time. 1.21+0.3=1.51s
  2. Time dial. The trip time is proportional to the time dial: 1.51/1.21=1.25
  3. A different multiple. If the upstream relay sees a smaller multiple (its pickup is higher), the curve shape must be used at its own M.

Answer the upstream relay needs a time dial of 1.25.

Check

A single-phase transformer rated 50 kVA at 240 V on its secondary has 0.08 per-unit impedance. What's the fault current for a short at its secondary terminals?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

Check

A 50 MVA transformer has 0.06 per-unit impedance. What's its short-circuit capacity, behind an infinite source?

Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.

Check

A three-phase fault occurs at the end of a 12.47 kV feeder with 0.3 Ω of source impedance and 8 Ω of line impedance per phase. What current flows?

Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.

Check

An IEEE moderately inverse relay with time dial 0.5 sees 5 times its pickup current. When does it trip?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

Check

A 50 MVA transformer with 12% impedance feeds a 4.16 kV bus.

(a)

What is its rated current on that side?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

What fault current can it deliver?

Check

An IEEE moderately inverse relay, t=TD(0.0515/(M0.02−1)+0.114), has time dial 1 and sees a fault at 3 times pickup.

(a)

When does it trip?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

(b)

What time dial gives an upstream relay, seeing the same M, a 0.3 s margin?

Explain why

Why are protective relays coordinated so that the device nearest a fault trips first?