title: Faults and protection
heading: What happens when a conductor shorts, how a transformer's impedance sets the fault current, short-circuit capacity, fuses, breakers and relays, inverse-time overcurrent curves, and how protection is coordinated so only the faulted section trips
eyebrow: D1 · Lesson 6 · Faults and protection
xp: 40
---

::: hook
A tree branch falls across a distribution line, or a squirrel bridges a transformer bushing, and in a millisecond the current through that spot jumps to tens of times its normal value. Left alone, it would melt conductors and destroy transformers. Protection systems detect the fault, decide which breaker should open, and clear it in a fraction of a second, ideally disconnecting only the faulted section so everyone else keeps their power. How large the fault current gets is set mostly by the impedances of the transformers and lines between the source and the fault.
:::

::: play
- The trip time of an inverse-time overcurrent relay against the fault current as a multiple M of its pickup setting, using the IEEE moderately inverse curve $t = TD\left(\frac{0.0515}{M^{0.02} - 1} + 0.114\right)$, for a chosen time dial TD.
- Larger faults trip faster. A relay closer to the source gets a larger time dial so that the relay nearest the fault trips first.
- That margin between curves is **coordination**.
:::

```sim plot
view: graph
x: M = 1.2..30 log
y: t = 0.01..100 log
slider: T = 0.5..10 step 0.5 = 1
plot: T*(0.0515/(M^0.02 - 1) + 0.114) | samples: 300 | label: trip time, s
plot: 3*T*(0.0515/(M^0.02 - 1) + 0.114) | samples: 300 | dashed | color: ch3 | label: upstream relay, time dial ×3
readout: trip time at 10× pickup, s = T*(0.0515/(10^0.02 - 1) + 0.114) | digits: 3
```

::: predict
## A 50 kVA, 240 V transformer has an impedance of 2%. If its secondary is shorted right at its terminals, about how much current flows?

- [ ] 208 A
- [ ] About 2 kA
- [x] About 10 kA
- [ ] About 100 kA

::: reveal
Rated current is 50 kVA/240 V = 208 A. A 2% impedance means rated voltage drives rated current through 2% of the "base" impedance, so a dead short draws 1/0.02 = 50 times rated: 10.4 kA. The breaker on that secondary must be able to interrupt at least that.
:::
:::

::: nameit
## Fault current

A short circuit leaves only the impedances of the source, transformers and lines to limit the current. Expressing a transformer's impedance as a per-unit (or percent) value $Z_\text{pu}$ of its rating makes the estimate quick:

$$I_\text{fault} = \frac{I_\text{rated}}{Z_\text{pu}}, \qquad S_\text{sc} = \frac{S_\text{rated}}{Z_\text{pu}}$$

where $S_\text{sc}$ is the **short-circuit capacity**. Farther from the source, line impedance adds: a three-phase fault on a line of impedance $Z_\text{line}$ behind a source impedance $Z_s$ draws $V_L/[\sqrt{3}(Z_s + Z_\text{line})]$.

## Protective devices

- **Fuses** melt when overcurrent persists, fastest for the largest faults.
- **Circuit breakers** interrupt the arc in air, oil, vacuum or SF₆, commanded by **relays**.
- **Overcurrent relays** trip after a time that falls with current (inverse-time curves).
- **Distance relays** on transmission lines measure the impedance to the fault; **differential relays** on transformers and buses trip when current in doesn't equal current out.

## Coordination

Devices are set so that the one closest to the fault operates first, with the upstream one waiting a coordination margin (around 0.3 s) as backup. Most faults on overhead lines are temporary, so **reclosers** reopen and reclose a few times before locking out.
:::

::: example
## A relay with time dial 1 sees faults of 2, 10 and 20 times its pickup. When does it trip? What's the fault current at the end of a 12.47 kV feeder with 0.5 Ω of source and 2 Ω of line impedance per phase?

::: solution
1. **Trip times.** Put M = 2, 10 and 20 into the moderately inverse curve with time dial 1:
   $$\begin{aligned} t(2) &= 3.80\ \text{s} \\ t(10) &= 1.21\ \text{s} \\ t(20) &= 0.95\ \text{s} \end{aligned}$$
2. **Feeder fault current.** The source and line add to 2.5 Ω per phase:
   $$\begin{aligned} I_f &= \frac{12\,470}{\sqrt3 \times 2.5} \\ &= 2.88\ \text{kA} \end{aligned}$$
3. **What that means for relays.** It's far below the tens of kiloamperes at the substation, which is why relays far out on a feeder need lower pickup settings.

**Answer:** the relay trips in 3.80 s, 1.21 s and 0.95 s, and the fault at the end of the feeder draws 2.88 kA.
:::
:::

::: example
## A 50 MVA, 138/13.8 kV transformer has 10% impedance. What fault current can it deliver on its 13.8 kV side, ignoring the source behind it?

::: solution
1. **Rated current.**
   $$\begin{aligned} I &= \frac{50\ \text{MVA}}{\sqrt3 \times 13.8\ \text{kV}} \\ &= 2092\ \text{A} \end{aligned}$$
2. **Fault current.** A bolted fault draws
   $$\begin{aligned} I_f &= 2092/0.10 \\ &= 20.9\ \text{kA} \end{aligned}$$
3. **Short-circuit power.**
   $$50/0.10 = 500\ \text{MVA}$$
   Breakers on that bus must interrupt at least that much.

**Answer:** it can deliver 20.9 kA, a short-circuit power of 500 MVA.
:::
:::

::: example
## A downstream relay with time dial 1 trips in 1.21 s for a fault at 10 times its pickup. An upstream relay sees the same multiple and must wait 0.3 s longer. What time dial does it need?

::: solution
1. **Required trip time.**
   $$1.21 + 0.3 = 1.51\ \text{s}$$
2. **Time dial.** The trip time is proportional to the time dial:
   $$1.51/1.21 = 1.25$$
3. **A different multiple.** If the upstream relay sees a smaller multiple (its pickup is higher), the curve shape must be used at its own M.

**Answer:** the upstream relay needs a time dial of 1.25.
:::
:::

::: check
given: S = 25 | 50 | 500; V = 240 | 480; Z = 0.02 | 0.05 | 0.08
answer: S*1000/V/Z/1000
unit: kA
tolerance: 0.5%

## A single-phase transformer rated {S} kVA at {V} V on its secondary has {Z} per-unit impedance. What's the fault current for a short at its secondary terminals?

::: right
Right. $I_\text{rated}/Z_\text{pu}$ = {answer} kA.
:::

::: misses
- [S*1000/V*Z/1000] Divide by the per-unit impedance.
- [any] Not yet. Rated current over per-unit impedance.
:::
:::

::: check
given: S = 10 | 50 | 200; Z = 0.06 | 0.1 | 0.15
answer: S/Z
unit: MVA
tolerance: 0.5%

## A {S} MVA transformer has {Z} per-unit impedance. What's its short-circuit capacity, behind an infinite source?

::: right
Right. $S/Z_\text{pu}$ = {answer} MVA.
:::

::: misses
- [any] Not yet. Rating over per-unit impedance.
:::
:::

::: check
given: V = 4.16 | 12.47 | 34.5; s = 0.3 | 1; l = 1 | 3 | 8
answer: V*1000/(sqrt(3)*(s + l))/1000
unit: kA
tolerance: 0.5%

## A three-phase fault occurs at the end of a {V} kV feeder with {s} Ω of source impedance and {l} Ω of line impedance per phase. What current flows?

::: right
Right. $V_L/[\sqrt{3}(Z_s + Z_\text{line})]$ = {answer} kA.
:::

::: misses
- [V*1000/(s + l)/1000] Use the phase voltage, $V_L/\sqrt{3}$.
- [any] Not yet. Phase voltage over the total impedance.
:::
:::

::: check
given: M = 2 | 5 | 15; T = 0.5 | 1 | 4
answer: T*(0.0515/(M^0.02 - 1) + 0.114)
unit: s
tolerance: 0.5%

## An IEEE moderately inverse relay with time dial {T} sees {M} times its pickup current. When does it trip?

::: right
Right. $TD(0.0515/(M^{0.02} - 1) + 0.114)$ = {answer} s.
:::

::: misses
- [any] Not yet. Evaluate the curve.
:::
:::

::: check
kind: parts
given: S = 10 | 50 | 100; V = 4.16 | 13.8 | 34.5; z = 6 | 10 | 12

## A {S} MVA transformer with {z}% impedance feeds a {V} kV bus.

::: part
answer: S*1000/(sqrt(3)*V)
unit: A
tolerance: 0.5%

### What is its rated current on that side?

::: misses
- [any] $S/(\sqrt3V)$.
:::
:::

::: part
answer: S*1000/(sqrt(3)*V)/(z/100)/1000
unit: kA
tolerance: 0.5%

### What fault current can it deliver?

::: misses
- [any] Rated current ÷ per-unit impedance.
:::
:::
:::

::: check
kind: parts
given: T = 0.5 | 1 | 2; M = 3 | 8 | 20

## An IEEE moderately inverse relay, $t = TD\,(0.0515/(M^{0.02} - 1) + 0.114)$, has time dial {T} and sees a fault at {M} times pickup.

::: part
answer: T*(0.0515/(M^0.02 - 1) + 0.114)
unit: s
tolerance: 0.5%

### When does it trip?

::: misses
- [any] Put M and TD into the curve.
:::
:::

::: part
answer: (T*(0.0515/(M^0.02 - 1) + 0.114) + 0.3)/(0.0515/(M^0.02 - 1) + 0.114)
tolerance: 0.5%

### What time dial gives an upstream relay, seeing the same M, a 0.3 s margin?

::: misses
- [any] (trip time + 0.3 s) ÷ the curve's value at M.
:::
:::
:::

::: explain
## Why are protective relays coordinated so that the device nearest a fault trips first?

::: model
A fault current flows through every device between the source and the fault, so several relays and fuses see it at once. If the one closest to the source tripped first, it would disconnect every customer downstream, including those on healthy branches. Coordinating the devices, giving each upstream device a slightly longer delay at every current level than the one below it, means the nearest device clears the fault and only the customers beyond it lose power. The upstream devices stay ready as backups: if the nearest device fails to clear, the next one trips after its margin.
:::
:::

::: practice

::: check
given: S = 5 | 2000; V = 120 | 600; Z = 0.015 | 0.1
answer: S*1000/V/Z/1000
unit: kA
tolerance: 0.5%

## Fault current: {S} kVA, {V} V, Z = {Z} pu?

::: misses
- [any] $I_\text{rated}/Z_\text{pu}$.
:::
:::

::: check
given: V = 2.4 | 69; s = 0.1 | 3; l = 0.2 | 20
answer: V*1000/(sqrt(3)*(s + l))/1000
unit: kA
tolerance: 0.5%

## Feeder fault: {V} kV, $Z_s$ = {s} Ω, $Z_\text{line}$ = {l} Ω?

::: misses
- [any] $V_L/[\sqrt{3}(Z_s + Z_\text{line})]$.
:::
:::

::: check
given: M = 1.5 | 40; T = 0.5 | 10
answer: T*(0.0515/(M^0.02 - 1) + 0.114)
unit: s
tolerance: 0.5%

## Trip time: M = {M}, TD = {T}?

::: misses
- [any] The moderately inverse curve.
:::
:::
:::