title: Grid frequency and load balance
heading: Why the grid's frequency tracks the balance of generation and load, the spinning inertia that slows a frequency change, droop control that shares a load step among generators, and how big a disturbance the grid can ride through
eyebrow: D1 · Lesson 4 · Grid frequency and load balance
xp: 40
---

::: hook
The grid stores almost no electrical energy, so every watt consumed must be generated at the same instant. The only buffer is the kinetic energy of thousands of generator rotors spinning in synchrony at exactly 60 Hz (50 Hz in much of the world). When a load switches on, the energy comes out of that rotation, and the whole grid's frequency starts to fall. Operators watch the frequency as a direct measure of whether supply matches demand, and governors on the generators respond to it automatically within seconds.
:::

::: play
- The grid's frequency after a sudden load increase ΔP, in a simplified model: inertia constant H (seconds of rated power stored as rotation) and governor droop R (the fractional speed change that brings a generator from no load to full output).
- Right after the step the frequency falls at a rate set by inertia; it settles where the governors' extra output matches the load, a deviation set by droop.
- Real grids dip lower before recovering, because governors and turbines take seconds to respond.
:::

```sim plot
view: graph
x: t = 0..5
y: f = 59.5..60.05
slider: P = 10..500 = 100 log
slider: H = 1..10 step 0.5 = 5
slider: R = 0.02..0.1 step 0.005 = 0.05
plot: 60 - P/10000*R*60*(1 - exp(-t/(2*H*R))) | samples: 300 | label: frequency, Hz (P in MW on a 10 GW system)
readout: initial rate of change, Hz/s = P/10000*60/(2*H) | digits: 3
readout: settled deviation, Hz = P/10000*R*60 | digits: 3
```

::: predict
## A 10 GW system with an inertia constant of 5 s suddenly loses 100 MW of generation. How fast does its frequency start falling?

- [ ] 6 Hz/s
- [x] 0.06 Hz/s
- [ ] 0.6 Hz/s
- [ ] 0.0006 Hz/s

::: reveal
The rotors store H × S = 5 × 10 GW = 50 GJ of kinetic energy. The rate of change of frequency is $\Delta Pf_0/(2HS)$ = 100 MW × 60/(2 × 5 × 10,000 MW) = 0.06 Hz/s. Less inertia, from replacing spinning generators with inverters (lesson 7), makes the same loss hit faster.
:::
:::

::: nameit
## Synchronous speed

A generator with p poles turns at $n = 120f/p$ rpm: 3600 rpm for a two-pole steam turbine at 60 Hz, 150 rpm for a 48-pole hydro unit. All synchronous generators on a grid share one electrical frequency.

## Inertia

The **inertia constant** H is the rotating kinetic energy divided by the machine's rating, typically 2 to 9 s. A power imbalance ΔP changes the frequency at first at the **rate of change of frequency**

$$\text{ROCOF} = \frac{\Delta P\,f_0}{2HS}$$

## Droop

Each governor raises its output in proportion to the frequency drop: a droop R of 5% means full output change for a 5% speed change. With all generators participating, a load step settles at

$$\Delta f = \frac{\Delta P}{S}Rf_0$$

shared in proportion to ratings. Slower **secondary control** (automatic generation control) then restores 60 Hz by adjusting setpoints over minutes.
:::

::: example
## For the 10 GW system with 5% droop, where does the frequency settle after the 100 MW loss, and how big a loss would drop it by 0.5 Hz?

::: solution
1. **Frequency drop.**
   $$\begin{aligned} \Delta f &= \frac{100}{10\,000} \times 0.05 \times 60 \\ &= 0.03\ \text{Hz} \end{aligned}$$
   so the frequency settles at 59.97 Hz.
2. **Loss for a 0.5 Hz drop.**
   $$\begin{aligned} \Delta P &= \frac{0.5 \times 10\,000}{0.05 \times 60} \\ &= 1667\ \text{MW} \end{aligned}$$
3. **How fast it settles.** In this simple model the frequency settles with a time constant of
   $$2HR = 0.5\ \text{s}$$

**Answer:** it settles at 59.97 Hz, and a 1667 MW loss would drop it by 0.5 Hz.
:::
:::

::: example
## The grid runs at 59.98 Hz for an hour. How much time does a clock that counts cycles lose?

::: solution
1. **Cycles counted.** In the hour the clock counts $3600 \times 59.98$ cycles.
2. **Time shown.** It takes each 60 cycles as a second:
   $$\begin{aligned} t &= \frac{3600 \times 59.98}{60} \\ &= 3598.8\ \text{s} \end{aligned}$$
   which is 1.2 s slow.
3. **Correcting it.** Grid operators correct such **time error** by running slightly fast later.

**Answer:** the clock loses 1.2 s.
:::
:::

::: example
## A 1000 MW, two-pole turbine-generator has H = 6 s. How much kinetic energy does it store, and what is its moment of inertia?

::: solution
1. **Stored energy.**
   $$\begin{aligned} E &= HS \\ &= 6 \times 1000\ \text{MW·s} \\ &= 6\ \text{GJ} \end{aligned}$$
2. **Speed.** Two poles at 60 Hz turn at 3600 rpm, $\omega = 377$ rad/s.
3. **Moment of inertia.**
   $$\begin{aligned} J &= 2E/\omega^2 \\ &= \frac{2 \times 6 \times 10^9}{377^2} \\ &= 84\,400\ \text{kg·m}^2 \end{aligned}$$

**Answer:** it stores 6 GJ, and its moment of inertia is 84,400 kg·m².
:::
:::

::: check
given: P = 50 | 300 | 1000; S = 5000 | 20000 | 100000; H = 2 | 4 | 6
answer: P*60/(2*H*S)
unit: Hz/s
tolerance: 0.5%

## A {S} MW system with H = {H} s loses {P} MW. What's the initial rate of change of frequency (60 Hz grid)?

::: right
Right. $\Delta Pf_0/(2HS)$ = {answer} Hz/s.
:::

::: misses
- [P*60/(H*S)] Include the factor of 2 from the kinetic energy.
- [any] Not yet. ROCOF from inertia.
:::
:::

::: check
given: P = 50 | 300 | 1000; S = 5000 | 20000 | 100000; R = 0.04 | 0.05
answer: P/S*R*60
unit: Hz
tolerance: 0.5%

## With {R} droop on all generators of a {S} MW system, how far does a {P} MW load step drop the frequency in steady state?

::: right
Right. $(\Delta P/S)Rf_0$ = {answer} Hz.
:::

::: misses
- [P/S*60] Multiply by the droop.
- [any] Not yet. Governors share the step in proportion to droop.
:::
:::

::: check
given: f = 50 | 60; p = 2 | 4 | 40
answer: 120*f/p
unit: rpm
tolerance: 0.5%

## How fast does a {p}-pole generator turn on a {f} Hz grid?

::: right
Right. $120f/p$ = {answer} rpm.
:::

::: misses
- [60*f/p] Each pair of poles produces one cycle per revolution: 120f/p.
- [any] Not yet. Synchronous speed.
:::
:::

::: check
given: H = 3 | 5 | 8; S = 500 | 1000
answer: H*S
unit: MJ
tolerance: 0.5%

## A {S} MW generator has H = {H} s. How much kinetic energy do its rotor and turbine store?

::: right
Right. HS = {answer} MJ.
:::

::: misses
- [any] Not yet. H is stored energy over rating, in seconds.
:::
:::

::: check
kind: parts
given: f = 59.95 | 59.98 | 60.02; h = 1 | 4

## The grid runs at {f} Hz for {h} hours.

::: part
answer: abs(h*3600*(f/60 - 1))
unit: s
tolerance: 0.5%

### How far off is a clock that counts cycles?

::: misses
- [any] Time × the fractional frequency error.
:::
:::

::: part
answer: h*3600*f
tolerance: 0.5%

### How many cycles occur?

::: misses
- [any] Seconds × frequency.
:::
:::
:::

::: check
kind: parts
given: S = 200 | 600 | 1200; H = 3 | 6; p = 2 | 4

## A {S} MW, {p}-pole generator on a 60 Hz grid has H = {H} s.

::: part
answer: H*S/1000
unit: GJ
tolerance: 0.5%

### What kinetic energy does it store?

::: misses
- [any] $E = HS$.
:::
:::

::: part
answer: 120*60/p
unit: rpm
tolerance: 0.5%

### At what speed does it turn?

::: misses
- [any] $120f/p$.
:::
:::

::: part
answer: 2*H*S*1e6/(2*pi*120*60/p/60)^2
unit: kg·m²
tolerance: 0.5%

### What is its moment of inertia?

::: misses
- [any] $J = 2E/\omega^2$.
:::
:::
:::

::: explain
## Why does the grid's frequency tell operators whether generation matches load?

::: model
The generators on a grid are locked together electrically and turn at a speed fixed by the frequency. The only energy store that can respond instantly to a mismatch is their rotation: if load exceeds generation, the shortfall is drawn from the rotors' kinetic energy, they slow down, and the frequency falls; if generation exceeds load, they speed up. So the frequency, measured anywhere on the grid, is a running indicator of the balance. Governors respond to it automatically by adjusting turbine power, and control centers use it to schedule generation.
:::
:::

::: practice

::: check
given: P = 10 | 3000; S = 1000 | 200000; H = 1 | 9
answer: P*60/(2*H*S)
unit: Hz/s
tolerance: 0.5%

## ROCOF: {P} MW lost, {S} MW system, H = {H} s?

::: misses
- [any] $\Delta Pf_0/(2HS)$.
:::
:::

::: check
given: P = 10 | 3000; S = 1000 | 200000; R = 0.03 | 0.08
answer: P/S*R*60
unit: Hz
tolerance: 0.5%

## Droop deviation: {P} MW, {S} MW, R = {R}?

::: misses
- [any] $(\Delta P/S)Rf_0$.
:::
:::

::: check
given: f = 50 | 60; p = 2 | 80
answer: 120*f/p
unit: rpm
tolerance: 0.5%

## Speed: {p} poles, {f} Hz?

::: misses
- [any] 120f/p.
:::
:::
:::