title: From power plant to outlet
heading: The journey of electric power from a generator through step-up transformers, high-voltage transmission, substations and distribution feeders to the 120/240 V outlet, and why each stage uses the voltage it does
eyebrow: D1 · Lesson 1 · From power plant to outlet
xp: 40
---

::: hook
The electricity in a wall outlet was, a fraction of a second earlier, spinning a generator tens or hundreds of kilometers away. Between the two it was transformed up to hundreds of thousands of volts, carried across the country on steel towers, and stepped down several times through substations and pole transformers. Every one of those voltage changes exists for the same reason: the power lost in a wire grows with the square of the current, and higher voltage carries the same power with less current.
:::

::: play
- The voltage at each stage of a typical North American system: generator (20 kV), transmission (345 kV), subtransmission (69 kV), distribution (12.47 kV), and the service to a home (240 V).
- The second set of stems shows the line current each stage needs to carry the power P, for a three-phase system: $I = P/(\sqrt{3}V)$.
- High voltage carries the bulk power with modest currents; only near the customer does the current become large, over short distances.
:::

```sim plot
view: graph
x: n = 1..5
y: v = 0.1..10000000 log
slider: P = 1..500 = 100 log
plot: (20*step(1.5 - n) + 345*step(n - 1.5)*step(2.5 - n) + 69*step(n - 2.5)*step(3.5 - n) + 12.47*step(n - 3.5)*step(4.5 - n) + 0.24*step(n - 4.5)) | stems | label: voltage, kV (generator, transmission, subtransmission, distribution, service)
plot: P*1e3/(sqrt(3)*(20*step(1.5 - n) + 345*step(n - 1.5)*step(2.5 - n) + 69*step(n - 2.5)*step(3.5 - n) + 12.47*step(n - 3.5)*step(4.5 - n) + 0.24*step(n - 4.5))) | stems | color: ch3 | label: current for P, A (P in MW)
readout: transmission current at 345 kV, A = P*1e3/(sqrt(3)*345) | digits: 4
readout: the same power at 20 kV, A = P*1e3/(sqrt(3)*20) | digits: 4
```

::: predict
## A 100 MW power plant sends its output over a line with 10 Ω per phase. How much less power is lost if the line runs at 345 kV instead of the generator's 20 kV?

- [ ] About 17 times less
- [x] About 300 times less
- [ ] The same
- [ ] About 4 times less

::: reveal
The current falls by the voltage ratio, 345/20 = 17.25, from 2887 A to 167 A, and the loss $3I^2R$ falls by its square, about 298 times: from 250 MW, more than the plant makes, to 0.84 MW. That's why generators feed step-up transformers before anything else.
:::
:::

::: nameit
## The stages

- **Generation**: synchronous generators make three-phase power at 10 to 25 kV.
- **Transmission**: step-up transformers raise it to 115 to 765 kV for long distances.
- **Subtransmission**: substations step down to 35 to 138 kV for regional delivery.
- **Distribution**: substations feed 4 to 35 kV lines (12.47 kV is common) along streets.
- **Service**: a pole or pad transformer steps down to 120/240 V split phase for homes, or 208 or 480 V three-phase for businesses.

## Why high voltage

A balanced three-phase line carrying power P at line voltage V and power factor 1 needs current

$$I = \frac{P}{\sqrt{3}\,V}$$

per phase, and loses $3I^2R$ in its conductors. For the same power and wire, loss scales as $1/V^2$. Above a few hundred kilovolts, insulation, tower size and corona discharge set the practical limit.
:::

::: example
## A 100 MW plant transmits at 345 kV. What current flows, and what fraction is lost in a line of 10 Ω per phase?

::: solution
1. **Line current.**
   $$\begin{aligned} I &= \frac{100\ \text{MW}}{\sqrt3 \times 345\ \text{kV}} \\ &= 167\ \text{A} \end{aligned}$$
2. **Line loss.**
   $$\begin{aligned} P_\text{loss} &= 3 \times 167^2 \times 10 \\ &= 0.84\ \text{MW} \end{aligned}$$
   which is 0.84% of the power.
3. **Compare with 20 kV.** At 20 kV the same line would need 2887 A and lose 250 MW.

**Answer:** 167 A flows, and the line loses 0.84 MW, 0.84% of the power.
:::
:::

::: example
## Send the same 100 MW over the same 10 Ω-per-phase line at 138 kV instead of 345 kV. What current flows, and what fraction is lost?

::: solution
1. **Line current.**
   $$\begin{aligned} I &= \frac{100\ \text{MW}}{\sqrt3 \times 138\ \text{kV}} \\ &= 418\ \text{A} \end{aligned}$$
2. **Line loss.**
   $$\begin{aligned} P_\text{loss} &= 3I^2R \\ &= 3 \times 418^2 \times 10 \\ &= 5.25\ \text{MW} \end{aligned}$$
   which is 5.25% of the power.
3. **Compare with 345 kV.** At 345 kV the current is 167 A and the loss 0.84 MW. The ratio is
   $$(345/138)^2 = 6.25$$
   so loss falls with the square of the voltage.

**Answer:** 418 A flows, and the line loses 5.25 MW, 5.25% of the power.
:::
:::

::: example
## A pole transformer takes 7.2 kV (one phase of a 12.47 kV feeder, line to neutral) down to 240 V. What is its turns ratio, and what current does it deliver at its 25 kVA rating?

::: solution
1. **Turns ratio.**
   $$7200/240 = 30$$
2. **Secondary current at 25 kVA.**
   $$\begin{aligned} I_2 &= 25\,000/240 \\ &= 104\ \text{A} \end{aligned}$$
3. **Primary current.**
   $$\begin{aligned} I_1 &= 104/30 \\ &= 3.5\ \text{A} \end{aligned}$$
4. **What it serves.** A handful of houses share one such transformer.

**Answer:** the turns ratio is 30, and at 25 kVA the transformer delivers 104 A at 240 V while drawing only 3.5 A from the 7.2 kV line.
:::
:::

::: check
given: P = 10 | 100 | 500; V = 69 | 138 | 345
answer: P*1e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

## A three-phase line at {V} kV carries {P} MW at unity power factor. What current flows in each phase?

::: right
Right. $P/(\sqrt{3}V)$ = {answer} A.
:::

::: misses
- [P*1e6/(V*1e3)] For three phases, divide by $\sqrt{3}V$.
- [any] Not yet. Three-phase power.
:::
:::

::: check
given: a = 20 | 69 | 138; b = 230 | 345 | 500
answer: (b/a)^2
tolerance: 0.5%

## A line's voltage is raised from {a} kV to {b} kV while carrying the same power. By what factor do its losses fall?

::: right
Right. $(V_2/V_1)^2$ = {answer}.
:::

::: misses
- [b/a] Current falls by the voltage ratio; losses by its square.
- [any] Not yet. Loss goes as $I^2$.
:::
:::

::: check
given: P = 50 | 200; V = 138 | 345; R = 2 | 10
answer: 3*(P*1e6/(sqrt(3)*V*1e3))^2*R/1e6
unit: MW
tolerance: 0.5%

## A {V} kV line with {R} Ω per phase carries {P} MW. How much power is lost?

::: right
Right. $3I^2R$ = {answer} MW.
:::

::: misses
- [(P*1e6/(sqrt(3)*V*1e3))^2*R/1e6] All three phases lose power.
- [any] Not yet. Find I, then $3I^2R$.
:::
:::

::: check
given: P = 50 | 200; V = 138 | 345; R = 2 | 10
answer: 100*3*(P*1e6/(sqrt(3)*V*1e3))^2*R/(P*1e6)
tolerance: 0.5%

## What percentage of the {P} MW is lost on that {V} kV line with {R} Ω per phase?

::: right
Right. {answer}%.
:::

::: misses
- [any] Not yet. Loss over power sent.
:::
:::

::: check
kind: parts
given: P = 50 | 200 | 500; V = 69 | 138 | 345; R = 5 | 20

## {P} MW is sent over a three-phase line at {V} kV with {R} Ω per phase.

::: part
answer: P*1000/(sqrt(3)*V)
unit: A
tolerance: 0.5%

### What current flows?

::: misses
- [P*1000/V] Three phases share the power: divide by $\sqrt3V$.
- [any] $P/(\sqrt3 V_{LL})$.
:::
:::

::: part
answer: 3*(P*1000/(sqrt(3)*V))^2*R/(P*1e6)*100
unit: %
tolerance: 0.5%

### What fraction of the power is lost?

::: misses
- [any] $3I^2R/P$.
:::
:::
:::

::: check
kind: parts
given: V = 7200 | 13800; v = 240 | 480; S = 25 | 75

## A transformer takes {V} V down to {v} V and is rated {S} kVA.

::: part
answer: V/v
tolerance: 0.5%

### What is its turns ratio?

::: misses
- [any] $V_1/V_2$.
:::
:::

::: part
answer: S*1000/v
unit: A
tolerance: 0.5%

### What secondary current does it deliver at full rating?

::: misses
- [any] Rating ÷ secondary voltage.
:::
:::
:::

::: explain
## Why does the power grid use such high transmission voltages?

::: model
The power a line carries is voltage times current, but the power it wastes heating its wires is current squared times resistance. Raising the voltage lets the same power flow with proportionally less current, and the losses fall with the square of that reduction. Long-distance lines therefore run at hundreds of kilovolts, where a few hundred amperes carry hundreds of megawatts with losses of a percent or two. Transformers make this possible because they change voltage efficiently for alternating current, and the voltage is stepped back down in stages only as the power is divided among smaller loads close to customers.
:::
:::

::: practice

::: check
given: P = 1 | 1000; V = 12.47 | 765
answer: P*1e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

## Line current: {P} MW at {V} kV?

::: misses
- [any] $P/(\sqrt{3}V)$.
:::
:::

::: check
given: a = 12 | 230; b = 115 | 765
answer: (b/a)^2
tolerance: 0.5%

## Loss reduction from {a} kV to {b} kV?

::: misses
- [any] $(V_2/V_1)^2$.
:::
:::

::: check
given: P = 5 | 500; V = 69 | 500; R = 0.5 | 20
answer: 3*(P*1e6/(sqrt(3)*V*1e3))^2*R/1e6
unit: MW
tolerance: 0.5%

## Loss: {P} MW, {V} kV, {R} Ω per phase?

::: misses
- [any] $3I^2R$.
:::
:::
:::