D1 Power systems and the grid · Practice
Every topic, mixed
Problems dealt one at a time, with new numbers every time. The kinds you miss come back more often, and you can keep going as long as you like.
Topics: all 9
Check
A three-phase line at 69 kV carries 100 MW at unity power factor. What current flows in each phase?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A line's voltage is raised from 69 kV to 230 kV while carrying the same power. By what factor do its losses fall?
Check
A 138 kV line with 10 Ω per phase carries 50 MW. How much power is lost?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
What percentage of the 50 MW is lost on that 138 kV line with 10 Ω per phase?
Check
200 MW is sent over a three-phase line at 69 kV with 20 Ω per phase.
(a)
What current flows?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What fraction of the power is lost?
Check
A transformer takes 7200 V down to 240 V and is rated 75 kVA.
(a)
What is its turns ratio?
(b)
What secondary current does it deliver at full rating?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Line current: 1 MW at 12.47 kV?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Loss reduction from 12 kV to 115 kV?
Check
Loss: 5 MW, 69 kV, 20 Ω per phase?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A three-phase system has 277 V from each line to neutral. What's the line-to-line voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
In-phase loads draw 10, 8 and 12 A from the three phases. What's the neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A balanced three-phase load at 480 V line-to-line draws 20 A per phase at power factor 0.95. What's its power?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
A single-phase load takes 5 kW on average at unity power factor. What's the peak of its instantaneous power?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
Three 10 Ω resistors run from a 208 V (line-to-line) supply.
(a)
What power do they take in wye?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
(b)
And in delta?
Check
A three-phase load takes 50 kW from 208 V line-to-line at power factor 0.9.
(a)
What line current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What is its apparent power?
Check
Line-to-line from 230 V phase?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
Neutral current: 0, 1, 30 A?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
Power: 208 V, 5 A, pf 1?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
A transformer steps 12470 V down to 120 V. What's its turns ratio, primary to secondary?
Check
A single-phase transformer rated 50 kVA has a 120 V secondary. What's its full-load secondary current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A 5 Ω load sits on the secondary of a transformer with turns ratio 10:1. What impedance does the primary see?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
A 25 kVA transformer has 0.1 kW of core loss and 1.2 kW of full-load copper loss. What's its efficiency, in percent, at 0.75 of rated load and unity power factor?
Check
A 25 kVA transformer has 0.2% core loss and 4% copper loss at full load (as fractions of its rating); it runs at full load for 12 hours a day and is idle otherwise, at unity power factor.
(a)
How much energy does it deliver a day?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
What is its all-day efficiency?
Check
A transformer with turns ratio 30 has 0.05 Ω on its low-voltage side.
(a)
What impedance does that look like from the high-voltage side?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
(b)
By what factor would a load on the low side appear larger?
Check
Turns ratio: 2400 V to 120 V?
Check
Reflected impedance: 0.5 Ω, ratio 2?
Write units the way you normally would: 1.5 Ω, 1500 mΩ and 0.0015 kΩ are the same answer.
Check
Load fraction for peak efficiency: core 0.05 kW, full-load copper 0.2 kW?
Check
A 5000 MW system with H = 6 s loses 300 MW. What's the initial rate of change of frequency (60 Hz grid)?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
With 0.05 droop on all generators of a 5000 MW system, how far does a 300 MW load step drop the frequency in steady state?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
How fast does a 2-pole generator turn on a 50 Hz grid?
Check
A 500 MW generator has H = 5 s. How much kinetic energy do its rotor and turbine store?
Write units the way you normally would: 1.5 MJ, 1500 kJ and 0.0015 GJ are the same answer.
Check
The grid runs at 59.98 Hz for 1 hours.
(a)
How far off is a clock that counts cycles?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
How many cycles occur?
Check
A 600 MW, 4-pole generator on a 60 Hz grid has H = 3 s.
(a)
What kinetic energy does it store?
Write units the way you normally would: 1.5 GJ, 1500 MJ and 0.0015 TJ are the same answer.
(b)
At what speed does it turn?
(c)
What is its moment of inertia?
Check
ROCOF: 10 MW lost, 1000 MW system, H = 9 s?
Write units the way you normally would: 1.5 Hz/s, 1500 mHz/s and 0.0015 kHz/s are the same answer.
Check
Droop deviation: 10 MW, 1000 MW, R = 0.08?
Write units the way you normally would: 1.5 Hz, 1500 mHz and 0.0015 kHz are the same answer.
Check
Speed: 2 poles, 50 Hz?
Check
Buses at 230 kV and 115 kV are joined by a 100 Ω line, with an angle of 60° between them. What real power flows?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Two 230 kV buses are joined by a 20 Ω line. What angle carries 300 MW?
Check
What's the steady-state transfer limit of a 150 Ω line between 230 kV and 115 kV buses?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 500 kW load runs at power factor 0.7. What capacitor raises it to 1?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
Check
Two 138 kV buses are joined by a line of 20 Ω reactance, at an angle of 30°.
(a)
What power flows?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
What is the most the line could carry?
Check
A 2 MW load runs at power factor 0.7, to be corrected to 1 with capacitors.
(a)
What reactive power does it draw now?
Write units the way you normally would: 1.5 Mvar, 1500 kvar and 0.0015 Gvar are the same answer.
(b)
What capacitor rating does the correction need?
Check
P: 69 and 69 kV, 300 Ω, 60°?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Transfer limit: 69 and 69 kV, 300 Ω?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
Correction: 10 kW from pf 0.6 to 0.99?
Write units the way you normally would: 1.5 kvar, 1500 var and 0.0015 Mvar are the same answer.
Check
A single-phase transformer rated 50 kVA at 240 V on its secondary has 0.08 per-unit impedance. What's the fault current for a short at its secondary terminals?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
A 50 MVA transformer has 0.06 per-unit impedance. What's its short-circuit capacity, behind an infinite source?
Write units the way you normally would: 1.5 MVA, 1500 kVA and 0.0015 GVA are the same answer.
Check
A three-phase fault occurs at the end of a 12.47 kV feeder with 0.3 Ω of source impedance and 8 Ω of line impedance per phase. What current flows?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
An IEEE moderately inverse relay with time dial 0.5 sees 5 times its pickup current. When does it trip?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A 50 MVA transformer with 12% impedance feeds a 4.16 kV bus.
(a)
What is its rated current on that side?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What fault current can it deliver?
Check
An IEEE moderately inverse relay, , has time dial 1 and sees a fault at 3 times pickup.
(a)
When does it trip?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
(b)
What time dial gives an upstream relay, seeing the same M, a 0.3 s margin?
Check
Fault current: 5 kVA, 120 V, Z = 0.1 pu?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
Feeder fault: 2.4 kV, = 0.1 Ω, = 20 Ω?
Write units the way you normally would: 1.5 kA, 1500 A and 0.0015 MA are the same answer.
Check
Trip time: M = 1.5, TD = 0.5?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A rotor 120 m across in a 6 m/s wind has a power coefficient of 0.48. What power does it produce (ρ = 1.225 kg/m³)?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
A 5 MW plant has a capacity factor of 0.2. How much energy does it produce in a year?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
Check
A grid has 3000 MW of synchronous generation with H = 4 s and 5000 MW of inverter-based generation. What's its system inertia constant?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
A 1.6 m² panel with 0.22 efficiency is in 800 W/m² of sunlight. What power does it produce?
Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.
Check
A wind turbine with a 120 m rotor and power coefficient 0.48 faces 6 m/s wind (air 1.225 kg/m³).
(a)
What power does it extract?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
(b)
And at half that wind speed?
Check
A 3.6 MW wind turbine has a capacity factor of 25%.
(a)
What does it produce in a year?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
(b)
How many homes using 10.5 MWh a year does that supply, on average?
Check
Wind: D = 20 m, v = 4 m/s, = 0.5?
Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.
Check
System H: 500 MW at H = 2 s plus 50000 MW of inverters?
Write units the way you normally would: 1.5 s and 1500 ms are the same answer.
Check
Annual energy: 0.5 MW, CF 0.1?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
Check
A battery is rated 50 MW and 400 MWh. How long can it discharge at full power?
Check
A storage plant with 0.75 round-trip efficiency is charged with 100 MWh. How much does it return?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
Check
Net load rises from 12 GW to 20 GW over 5 hours. What's the average ramp rate?
Write units the way you normally would: 1.5 GW/h, 1500 MW/h and 0.0015 TW/h are the same answer.
Check
A battery must deliver 50 MW for 2 hours each evening, with round-trip efficiency 0.9. How much energy must it absorb from midday solar?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
Check
A battery is rated 100 MW for 2 hours, with 90% round-trip efficiency.
(a)
What energy does it deliver?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
(b)
What must it take in to deliver that?
Check
A pumped-hydro reservoir holds 5 million m³ at 100 m above the lower one, with 80% round-trip efficiency.
(a)
How much energy is stored?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
(b)
How much comes back?
Check
Duration: 10 MWh, 5 MW?
Check
Charge needed: 10 MW for 1 h, η = 0.95?
Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.
Check
Ramp: 2 → 21 GW in 6 h?
Write units the way you normally would: 1.5 GW/h, 1500 MW/h and 0.0015 TW/h are the same answer.
Check
Solar output follows a half-sine from 6:00 to 18:00 peaking at 60 kW. How much energy does it make in a day?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
Check
A 15 kW load must run from the battery for 12 hours with discharge efficiency 0.95. What usable capacity does the battery need?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
Check
Ignoring timing, what solar peak (half-sine, 6:00 to 18:00) makes enough energy for a 20 kW constant load if all of the load's energy passes through a battery of round-trip efficiency 0.85?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
A microgrid's solar follows a half-sine peaking at 60 kW over 12 hours; the load is a steady 10 kW.
(a)
What is the daily solar energy?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
What surplus or shortfall (negative) is there over the day, before battery losses?
Check
The microgrid's 15 kW load must be carried by the battery for 12 hours each night, with 95% discharge efficiency.
(a)
What usable capacity does that need?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
(b)
What nameplate capacity, if only 80% may be used?
Check
Daily solar energy, peak 50 kW?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
Check
Battery for 1 kW over 8 h, η = 0.98?
Write units the way you normally would: 1.5 kWh, 1500 Wh and 0.0015 MWh are the same answer.
A kind of problem counts as solid once you've got it right on the first try twice in a row. Back to D1