D17 of 9
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

D1 · Lesson 7 · Renewables, inverters and inertia

Power from wind as the cube of wind speed with the Betz limit, solar panel output, capacity factors and annual energy, why inverter-based generation adds no spinning inertia, and how a grid with less inertia responds faster to a lost generator

Wind turbines and solar panels now supply a large and growing share of many grids, and they connect differently from the generators they replace. Instead of a massive spinning rotor locked to the grid frequency, they feed power through inverters, power electronics (D2) that synthesize a sine wave. That brings fast, flexible control but no stored rotational energy, so a grid with fewer spinning machines changes frequency faster when something trips. Grid operators now buy "fast frequency response" from batteries and inverters to make up for it.

  • A wind turbine's output against wind speed: P=12ρAv3Cp, capped at its rating and zero below cut-in (3 m/s) and above cut-out (25 m/s).
  • Doubling the wind speed multiplies the available power by eight, so turbines spend most of their time well below rating.
  • Larger rotors reach rated power at lower wind speeds.

Predict

A 100 m rotor turns 45% of the wind's power into electricity. How much does it produce in an 8 m/s wind?

Name it

Wind

Wind of speed v through a rotor of swept area A carries power 12ρAv3. No turbine can extract more than 16/27 = 59.3% of it (the Betz limit); modern turbines reach Cp of about 0.45 to 0.5 below their rated speed.

Solar

A panel of area A and efficiency η in irradiance G (1000 W/m² at standard test conditions) produces GAη. Output follows the sun and clouds; inverters track the maximum power point (D2).

Capacity factor

Variable sources rarely run at their rating. Annual energy is Prated×CF×8760 h, with capacity factors around 20 to 25% for solar and 30 to 45% for wind, against 90% for nuclear.

Inertia

Inverter-connected sources aren't magnetically locked to the grid, so their stored energy doesn't automatically support frequency. A grid's inertia is the rating-weighted average

Hsys=∑HiSi∑Si

with Hi ≈ 0 for inverter-based units. Lower Hsys means a faster rate of change of frequency for the same lost generation (lesson 4). Inverters can be programmed to inject power in proportion to the frequency's rate of change, synthetic inertia, and batteries can respond within milliseconds.

Worked example

A 10 GW grid runs 6 GW of synchronous generation with H = 5 s and 4 GW of inverter-based generation. What's its inertia, and its ROCOF for a 100 MW loss?

Show the solution
  1. System inertia. Hsys=6000×5+4000×010000=3s
  2. ROCOF. ROCOF=100×602×3×10000=0.10Hz/s
  3. Compare. With all-synchronous generation it's 0.06 Hz/s.

Answer the system inertia is 3 s, and the ROCOF is 0.10 Hz/s.

Worked example

A 2 MW turbine has a capacity factor of 35%. What does it produce in a year? What does a 1.7 m², 21% efficient panel make at 1000 W/m²?

Show the solution
  1. Turbine energy in a year. 2×0.35×8760=6132MWh
  2. Panel power. 1000×1.7×0.21=357W

Answer the turbine makes 6132 MWh a year, and the panel makes 357 W.

Worked example

A turbine has a 100 m rotor diameter and a power coefficient of 0.45. What does it produce at 10 m/s in air of density 1.225 kg/m³, and at 5 m/s?

Show the solution
  1. Swept area. π×502=7854m2
  2. Power at 10 m/s. P=12ρAv3Cp=0.5×1.225×7854×1000×0.45=2.16MW
  3. Power at 5 m/s. At half the wind speed, an eighth: 0.27 MW. That cube is why wind output swings so widely.

Answer 2.16 MW at 10 m/s and 0.27 MW at 5 m/s.

Check

A rotor 120 m across in a 6 m/s wind has a power coefficient of 0.48. What power does it produce (ρ = 1.225 kg/m³)?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

Check

A 5 MW plant has a capacity factor of 0.2. How much energy does it produce in a year?

Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.

Check

A grid has 3000 MW of synchronous generation with H = 4 s and 5000 MW of inverter-based generation. What's its system inertia constant?

Write units the way you normally would: 1.5 s and 1500 ms are the same answer.

Check

A 1.6 m² panel with 0.22 efficiency is in 800 W/m² of sunlight. What power does it produce?

Write units the way you normally would: 1.5 W, 1500 mW and 0.0015 kW are the same answer.

Check

A wind turbine with a 120 m rotor and power coefficient 0.48 faces 6 m/s wind (air 1.225 kg/m³).

(a)

What power does it extract?

Write units the way you normally would: 1.5 MW, 1500 kW and 0.0015 GW are the same answer.

(b)

And at half that wind speed?

Check

A 3.6 MW wind turbine has a capacity factor of 25%.

(a)

What does it produce in a year?

Write units the way you normally would: 1.5 MWh, 1500 kWh and 0.0015 GWh are the same answer.

(b)

How many homes using 10.5 MWh a year does that supply, on average?

Explain why

Why does replacing spinning generators with inverter-based sources make grid frequency harder to control?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.