title: Renewables, inverters and inertia
heading: Power from wind as the cube of wind speed with the Betz limit, solar panel output, capacity factors and annual energy, why inverter-based generation adds no spinning inertia, and how a grid with less inertia responds faster to a lost generator
eyebrow: D1 · Lesson 7 · Renewables, inverters and inertia
xp: 40
---

::: hook
Wind turbines and solar panels now supply a large and growing share of many grids, and they connect differently from the generators they replace. Instead of a massive spinning rotor locked to the grid frequency, they feed power through inverters, power electronics (D2) that synthesize a sine wave. That brings fast, flexible control but no stored rotational energy, so a grid with fewer spinning machines changes frequency faster when something trips. Grid operators now buy "fast frequency response" from batteries and inverters to make up for it.
:::

::: play
- A wind turbine's output against wind speed: $P = \frac{1}{2}\rho Av^3C_p$, capped at its rating and zero below cut-in (3 m/s) and above cut-out (25 m/s).
- Doubling the wind speed multiplies the available power by eight, so turbines spend most of their time well below rating.
- Larger rotors reach rated power at lower wind speeds.
:::

```sim plot
view: graph
x: v = 0..30
y: P = 0..6
slider: D = 50..170 step 5 = 100
slider: R = 1..6 step 0.1 = 3
plot: step(v - 3)*step(25 - v)*((0.5*1.225*pi*(D/2)^2*v^3*0.45/1e6 + R - abs(0.5*1.225*pi*(D/2)^2*v^3*0.45/1e6 - R))/2) | samples: 600 | label: output, MW (Cp = 0.45)
readout: wind speed for rated power, m/s = (R*1e6/(0.5*1.225*pi*(D/2)^2*0.45))^(1/3) | digits: 3
```

::: predict
## A 100 m rotor turns 45% of the wind's power into electricity. How much does it produce in an 8 m/s wind?

- [ ] About 0.1 MW
- [x] About 1.1 MW
- [ ] About 8 MW
- [ ] About 45 MW

::: reveal
The swept area is π(50 m)² = 7854 m², and $P = \frac{1}{2} \times 1.225 \times 7854 \times 8^3 \times 0.45$ = 1.11 MW. At 12 m/s the same turbine would make 3.74 MW, more than three times as much, because power goes as the cube of wind speed.
:::
:::

::: nameit
## Wind

Wind of speed v through a rotor of swept area A carries power $\frac{1}{2}\rho Av^3$. No turbine can extract more than 16/27 = 59.3% of it (the **Betz limit**); modern turbines reach $C_p$ of about 0.45 to 0.5 below their rated speed.

## Solar

A panel of area A and efficiency η in irradiance G (1000 W/m² at standard test conditions) produces $GA\eta$. Output follows the sun and clouds; inverters track the maximum power point (D2).

## Capacity factor

Variable sources rarely run at their rating. Annual energy is $P_\text{rated} \times CF \times 8760$ h, with capacity factors around 20 to 25% for solar and 30 to 45% for wind, against 90% for nuclear.

## Inertia

Inverter-connected sources aren't magnetically locked to the grid, so their stored energy doesn't automatically support frequency. A grid's inertia is the rating-weighted average

$$H_\text{sys} = \frac{\sum H_iS_i}{\sum S_i}$$

with $H_i$ ≈ 0 for inverter-based units. Lower $H_\text{sys}$ means a faster rate of change of frequency for the same lost generation (lesson 4). Inverters can be programmed to inject power in proportion to the frequency's rate of change, **synthetic inertia**, and batteries can respond within milliseconds.
:::

::: example
## A 10 GW grid runs 6 GW of synchronous generation with H = 5 s and 4 GW of inverter-based generation. What's its inertia, and its ROCOF for a 100 MW loss?

::: solution
1. **System inertia.**
   $$\begin{aligned} H_\text{sys} &= \frac{6000 \times 5 + 4000 \times 0}{10\,000} \\ &= 3\ \text{s} \end{aligned}$$
2. **ROCOF.**
   $$\begin{aligned} \text{ROCOF} &= \frac{100 \times 60}{2 \times 3 \times 10\,000} \\ &= 0.10\ \text{Hz/s} \end{aligned}$$
3. **Compare.** With all-synchronous generation it's 0.06 Hz/s.

**Answer:** the system inertia is 3 s, and the ROCOF is 0.10 Hz/s.
:::
:::

::: example
## A 2 MW turbine has a capacity factor of 35%. What does it produce in a year? What does a 1.7 m², 21% efficient panel make at 1000 W/m²?

::: solution
1. **Turbine energy in a year.**
   $$2 \times 0.35 \times 8760 = 6132\ \text{MWh}$$
2. **Panel power.**
   $$1000 \times 1.7 \times 0.21 = 357\ \text{W}$$

**Answer:** the turbine makes 6132 MWh a year, and the panel makes 357 W.
:::
:::

::: example
## A turbine has a 100 m rotor diameter and a power coefficient of 0.45. What does it produce at 10 m/s in air of density 1.225 kg/m³, and at 5 m/s?

::: solution
1. **Swept area.**
   $$\pi \times 50^2 = 7854\ \text{m}^2$$
2. **Power at 10 m/s.**
   $$\begin{aligned} P &= \tfrac12\rho Av^3C_p \\ &= 0.5 \times 1.225 \times 7854 \\ &\quad \times 1000 \times 0.45 \\ &= 2.16\ \text{MW} \end{aligned}$$
3. **Power at 5 m/s.** At half the wind speed, an eighth: 0.27 MW. That cube is why wind output swings so widely.

**Answer:** 2.16 MW at 10 m/s and 0.27 MW at 5 m/s.
:::
:::

::: check
given: D = 80 | 120 | 160; v = 6 | 9 | 11; c = 0.4 | 0.48
answer: 0.5*1.225*pi*(D/2)^2*v^3*c/1e6
unit: MW
tolerance: 0.5%

## A rotor {D} m across in a {v} m/s wind has a power coefficient of {c}. What power does it produce (ρ = 1.225 kg/m³)?

::: right
Right. $\frac{1}{2}\rho Av^3C_p$ = {answer} MW.
:::

::: misses
- [0.5*1.225*pi*(D/2)^2*v^2*c/1e6] Wind power goes as the cube of speed.
- [any] Not yet. Swept area, then the cube law.
:::
:::

::: check
given: P = 2 | 5 | 100; c = 0.2 | 0.35 | 0.9
answer: P*c*8760
unit: MWh
tolerance: 0.5%

## A {P} MW plant has a capacity factor of {c}. How much energy does it produce in a year?

::: right
Right. $P \times CF \times 8760$ h = {answer} MWh.
:::

::: misses
- [any] Not yet. Average power times hours in a year.
:::
:::

::: check
given: a = 3000 | 6000; h = 4 | 6; b = 2000 | 5000
answer: a*h/(a + b)
unit: s
tolerance: 0.5%

## A grid has {a} MW of synchronous generation with H = {h} s and {b} MW of inverter-based generation. What's its system inertia constant?

::: right
Right. $\sum H_iS_i/\sum S_i$ = {answer} s.
:::

::: misses
- [h] The inverter-based share contributes no inertia but counts in the total.
- [any] Not yet. Rating-weighted average with H = 0 for inverters.
:::
:::

::: check
given: G = 400 | 800 | 1000; A = 1.6 | 2; e = 0.18 | 0.22
answer: G*A*e
unit: W
tolerance: 0.5%

## A {A} m² panel with {e} efficiency is in {G} W/m² of sunlight. What power does it produce?

::: right
Right. $GA\eta$ = {answer} W.
:::

::: misses
- [any] Not yet. Irradiance × area × efficiency.
:::
:::

::: check
kind: parts
given: D = 80 | 120 | 160; v = 6 | 9 | 12; c = 0.4 | 0.48

## A wind turbine with a {D} m rotor and power coefficient {c} faces {v} m/s wind (air 1.225 kg/m³).

::: part
answer: 0.5*1.225*pi*(D/2)^2*v^3*c/1e6
unit: MW
tolerance: 0.5%

### What power does it extract?

::: misses
- [0.5*1.225*pi*D^2*v^3*c/1e6] The area uses the radius, half the diameter.
- [any] $\tfrac12\rho Av^3C_p$.
:::
:::

::: part
answer: 0.5*1.225*pi*(D/2)^2*(v/2)^3*c/1e6
unit: MW
tolerance: 0.5%

### And at half that wind speed?

::: misses
- [any] An eighth.
:::
:::
:::

::: check
kind: parts
given: P = 2 | 3.6 | 8; f = 25 | 35 | 45

## A {P} MW wind turbine has a capacity factor of {f}%.

::: part
answer: P*f/100*8766
unit: MWh
tolerance: 0.5%

### What does it produce in a year?

::: misses
- [any] Rating × capacity factor × 8766 h.
:::
:::

::: part
answer: P*f/100*8766/10.5
unit: homes
tolerance: 0.5%

### How many homes using 10.5 MWh a year does that supply, on average?

::: misses
- [any] Energy ÷ use per home.
:::
:::
:::

::: explain
## Why does replacing spinning generators with inverter-based sources make grid frequency harder to control?

::: model
A synchronous generator's rotor is magnetically locked to the grid, so when generation falls short the rotor automatically gives up some of its kinetic energy, slowing the frequency's fall and buying time for governors to respond. Wind turbines and solar panels connect through inverters that synthesize their output under software control, so unless they're programmed to, they don't release stored energy when the frequency changes. As they replace synchronous plants, the grid's total inertia falls and the same lost generator makes the frequency drop faster and deeper. The remedy is to make inverters and batteries respond deliberately, with fast frequency response and synthetic inertia.
:::
:::

::: practice

::: check
given: D = 20 | 220; v = 4 | 14; c = 0.3 | 0.5
answer: 0.5*1.225*pi*(D/2)^2*v^3*c/1e6
unit: MW
tolerance: 0.5%

## Wind: D = {D} m, v = {v} m/s, $C_p$ = {c}?

::: misses
- [any] $\frac{1}{2}\rho Av^3C_p$.
:::
:::

::: check
given: a = 500 | 50000; h = 2 | 9; b = 0 | 50000
answer: a*h/(a + b)
unit: s
tolerance: 0.5%

## System H: {a} MW at H = {h} s plus {b} MW of inverters?

::: misses
- [any] Weighted average.
:::
:::

::: check
given: P = 0.5 | 1000; c = 0.1 | 0.95
answer: P*c*8760
unit: MWh
tolerance: 0.5%

## Annual energy: {P} MW, CF {c}?

::: misses
- [any] $P \times CF \times 8760$.
:::
:::
:::