D1 · Lesson 2 · Why three phases
Three voltages 120° apart that sum to zero, balanced loads with no neutral current, line and phase voltages, the constant power that keeps motors smooth, and the copper three-phase saves
Nearly every power system in the world generates and transmits three alternating voltages, each a third of a cycle behind the last. Two would seem simpler and one simpler still, but three phases have a remarkable property: when the three loads are equal, the currents add to exactly zero at every instant, so the return wire carries nothing and the power delivered never pulses. Generators run smoothly, motors start themselves, and the wires carry more power per kilogram of copper.
- Three phase currents drawn as phasors, 120° apart, with magnitudes , and , and their sum, which is the current in the neutral wire.
- With equal magnitudes the sum is exactly zero: a balanced load needs no return current.
- Unbalance one phase and a neutral current appears.
Predict
A three-phase load draws 10 A, 10 A and 6 A in its three phases, all at unity power factor. What current flows in the neutral?
The two 10 A phases and 10 A of the third would cancel exactly; what's left is the 4 A shortfall in the third phase, so the neutral carries 4 A. In general the neutral current is for in-phase loads.
Name it
Balanced three-phase
The three phase voltages are , and . Their sum, and the sum of balanced currents, is zero at every instant, so a balanced load needs no neutral conductor.
Line and phase voltages
The voltage between two lines is times the voltage from a line to neutral: 120 V phase gives 208 V line-to-line, 277 V gives 480 V, and a 7.2 kV distribution phase gives 12.47 kV.
Power
A balanced three-phase load takes
and the instantaneous power is constant, unlike a single-phase load, whose power pulses at twice the line frequency between zero and twice the average. Constant power means constant torque in generators and motors.
Why not more phases
Three is the smallest number that gives constant power and a rotating magnetic field (D2). More phases add conductors without much further benefit.
Worked example
A 480 V (line-to-line) motor draws 50 A per phase at a power factor of 0.9. What's its phase voltage and power?
Show the solution
- Phase voltage.
- Power.
- Same result from line values. Equivalently,
Answer the phase voltage is 277 V, and the motor draws 37.4 kW.
Worked example
Three 10 Ω heater elements run from a 208 V (line-to-line) supply, first in wye, then in delta. What power does each connection give?
Show the solution
- Wye. Each element sees V and draws 12 A, so
- Delta. Each element sees the full 208 V and draws 20.8 A, so three times as much.
- Line current in delta.
Answer 4.32 kW in wye and 12.98 kW in delta, three times as much.
Worked example
A 10 kW resistive heater can run from 240 V single-phase or from 208 V three-phase. What current does each draw from the wires?
Show the solution
- Single-phase. in each of two wires.
- Three-phase. in each of three wires.
- Compare. Three wires carrying 27.8 A deliver the same power as two carrying 41.7 A, using less copper in all.
Answer 41.7 A in each of two wires at 240 V single-phase, and 27.8 A in each of three wires at 208 V three-phase.
Check
A three-phase system has 277 V from each line to neutral. What's the line-to-line voltage?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
In-phase loads draw 10, 8 and 12 A from the three phases. What's the neutral current?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
Check
A balanced three-phase load at 480 V line-to-line draws 20 A per phase at power factor 0.95. What's its power?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
A single-phase load takes 5 kW on average at unity power factor. What's the peak of its instantaneous power?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
Check
Three 10 Ω resistors run from a 208 V (line-to-line) supply.
(a)
What power do they take in wye?
Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.
(b)
And in delta?
Check
A three-phase load takes 50 kW from 208 V line-to-line at power factor 0.9.
(a)
What line current does it draw?
Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.
(b)
What is its apparent power?
Explain why
Why does a balanced three-phase load need no neutral current?
The three phase currents are equal sinusoids shifted by a third of a cycle each. Drawn as phasors, they're three equal arrows 120° apart, which form a closed triangle when placed tip to tail, so their sum is zero. Equivalently, at any instant one phase's current is exactly balanced by the sum of the other two, so the current flowing out on some lines returns on the others and nothing is left for a neutral. Only when the loads are unequal does a neutral current flow, equal to the imbalance.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.