D12 of 9
0 XP
  1. Hook
  2. Play
  3. Predict
  4. Name it
  5. Check
  6. Explain

D1 · Lesson 2 · Why three phases

Three voltages 120° apart that sum to zero, balanced loads with no neutral current, line and phase voltages, the constant power that keeps motors smooth, and the copper three-phase saves

Nearly every power system in the world generates and transmits three alternating voltages, each a third of a cycle behind the last. Two would seem simpler and one simpler still, but three phases have a remarkable property: when the three loads are equal, the currents add to exactly zero at every instant, so the return wire carries nothing and the power delivered never pulses. Generators run smoothly, motors start themselves, and the wires carry more power per kilogram of copper.

  • Three phase currents drawn as phasors, 120° apart, with magnitudes Ia, Ib and Ic, and their sum, which is the current in the neutral wire.
  • With equal magnitudes the sum is exactly zero: a balanced load needs no return current.
  • Unbalance one phase and a neutral current appears.

Predict

A three-phase load draws 10 A, 10 A and 6 A in its three phases, all at unity power factor. What current flows in the neutral?

Name it

Balanced three-phase

The three phase voltages are V∠0°, V∠−120° and V∠120°. Their sum, and the sum of balanced currents, is zero at every instant, so a balanced load needs no neutral conductor.

Line and phase voltages

The voltage between two lines is 3 times the voltage from a line to neutral: 120 V phase gives 208 V line-to-line, 277 V gives 480 V, and a 7.2 kV distribution phase gives 12.47 kV.

Power

A balanced three-phase load takes

P=3VphIcos⁡φ=3VLIcos⁡φ

and the instantaneous power is constant, unlike a single-phase load, whose power pulses at twice the line frequency between zero and twice the average. Constant power means constant torque in generators and motors.

Why not more phases

Three is the smallest number that gives constant power and a rotating magnetic field (D2). More phases add conductors without much further benefit.

Worked example

A 480 V (line-to-line) motor draws 50 A per phase at a power factor of 0.9. What's its phase voltage and power?

Show the solution
  1. Phase voltage. Vph=480/3=277V
  2. Power. P=3×277×50×0.9=37.4kW
  3. Same result from line values. Equivalently, P=3×480×50×0.9

Answer the phase voltage is 277 V, and the motor draws 37.4 kW.

Worked example

Three 10 Ω heater elements run from a 208 V (line-to-line) supply, first in wye, then in delta. What power does each connection give?

Show the solution
  1. Wye. Each element sees 208/3=120 V and draws 12 A, so P=3×120×12=4.32kW
  2. Delta. Each element sees the full 208 V and draws 20.8 A, so P=3×208×20.8=12.98kW three times as much.
  3. Line current in delta. 3×20.8=36.0A

Answer 4.32 kW in wye and 12.98 kW in delta, three times as much.

Worked example

A 10 kW resistive heater can run from 240 V single-phase or from 208 V three-phase. What current does each draw from the wires?

Show the solution
  1. Single-phase. 10000/240=41.7A in each of two wires.
  2. Three-phase. 100003×208=27.8A in each of three wires.
  3. Compare. Three wires carrying 27.8 A deliver the same power as two carrying 41.7 A, using less copper in all.

Answer 41.7 A in each of two wires at 240 V single-phase, and 27.8 A in each of three wires at 208 V three-phase.

Check

A three-phase system has 277 V from each line to neutral. What's the line-to-line voltage?

Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.

Check

In-phase loads draw 10, 8 and 12 A from the three phases. What's the neutral current?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

Check

A balanced three-phase load at 480 V line-to-line draws 20 A per phase at power factor 0.95. What's its power?

Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.

Check

A single-phase load takes 5 kW on average at unity power factor. What's the peak of its instantaneous power?

Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.

Check

Three 10 Ω resistors run from a 208 V (line-to-line) supply.

(a)

What power do they take in wye?

Write units the way you normally would: 1.5 kW, 1500 W and 0.0015 MW are the same answer.

(b)

And in delta?

Check

A three-phase load takes 50 kW from 208 V line-to-line at power factor 0.9.

(a)

What line current does it draw?

Write units the way you normally would: 1.5 A, 1500 mA and 0.0015 kA are the same answer.

(b)

What is its apparent power?

Explain why

Why does a balanced three-phase load need no neutral current?

Practice

Keep practicing

9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.