title: Why three phases
heading: Three voltages 120° apart that sum to zero, balanced loads with no neutral current, line and phase voltages, the constant power that keeps motors smooth, and the copper three-phase saves
eyebrow: D1 · Lesson 2 · Why three phases
xp: 40
---

::: hook
Nearly every power system in the world generates and transmits three alternating voltages, each a third of a cycle behind the last. Two would seem simpler and one simpler still, but three phases have a remarkable property: when the three loads are equal, the currents add to exactly zero at every instant, so the return wire carries nothing and the power delivered never pulses. Generators run smoothly, motors start themselves, and the wires carry more power per kilogram of copper.
:::

::: play
- Three phase currents drawn as phasors, 120° apart, with magnitudes $I_a$, $I_b$ and $I_c$, and their sum, which is the current in the neutral wire.
- With equal magnitudes the sum is exactly zero: a balanced load needs no return current.
- Unbalance one phase and a neutral current appears.
:::

```sim plot
view: complex
range: 20
slider: a = 0..20 step 1 = 10
slider: b = 0..20 step 1 = 10
slider: c = 0..20 step 1 = 10
arrow: a | color: ch3 | label: a
arrow: b*exp(-j*2*pi/3) | color: ch4 | label: b
arrow: c*exp(j*2*pi/3) | color: ch5 | label: c
dot: a + b*exp(-j*2*pi/3) + c*exp(j*2*pi/3) | label: neutral current
readout: neutral current, A = abs(a + b*exp(-j*2*pi/3) + c*exp(j*2*pi/3)) | digits: 3
```

::: predict
## A three-phase load draws 10 A, 10 A and 6 A in its three phases, all at unity power factor. What current flows in the neutral?

- [ ] 26 A
- [ ] 0 A
- [x] 4 A
- [ ] 6 A

::: reveal
The two 10 A phases and 10 A of the third would cancel exactly; what's left is the 4 A shortfall in the third phase, so the neutral carries 4 A. In general the neutral current is $\sqrt{I_a^2 + I_b^2 + I_c^2 - I_aI_b - I_bI_c - I_cI_a}$ for in-phase loads.
:::
:::

::: nameit
## Balanced three-phase

The three phase voltages are $V\angle0°$, $V\angle-120°$ and $V\angle120°$. Their sum, and the sum of balanced currents, is zero at every instant, so a balanced load needs no neutral conductor.

## Line and phase voltages

The voltage between two lines is $\sqrt{3}$ times the voltage from a line to neutral: 120 V phase gives 208 V line-to-line, 277 V gives 480 V, and a 7.2 kV distribution phase gives 12.47 kV.

## Power

A balanced three-phase load takes

$$P = 3V_\text{ph}I\cos\varphi = \sqrt{3}V_LI\cos\varphi$$

and the instantaneous power is constant, unlike a single-phase load, whose power pulses at twice the line frequency between zero and twice the average. Constant power means constant torque in generators and motors.

## Why not more phases

Three is the smallest number that gives constant power and a rotating magnetic field (D2). More phases add conductors without much further benefit.
:::

::: example
## A 480 V (line-to-line) motor draws 50 A per phase at a power factor of 0.9. What's its phase voltage and power?

::: solution
1. **Phase voltage.**
   $$\begin{aligned} V_\text{ph} &= 480/\sqrt3 \\ &= 277\ \text{V} \end{aligned}$$
2. **Power.**
   $$\begin{aligned} P &= 3 \times 277 \times 50 \times 0.9 \\ &= 37.4\ \text{kW} \end{aligned}$$
3. **Same result from line values.** Equivalently,
   $$P = \sqrt3 \times 480 \times 50 \times 0.9$$

**Answer:** the phase voltage is 277 V, and the motor draws 37.4 kW.
:::
:::

::: example
## Three 10 Ω heater elements run from a 208 V (line-to-line) supply, first in wye, then in delta. What power does each connection give?

::: solution
1. **Wye.** Each element sees $208/\sqrt3 = 120$ V and draws 12 A, so
   $$\begin{aligned} P &= 3 \times 120 \times 12 \\ &= 4.32\ \text{kW} \end{aligned}$$
2. **Delta.** Each element sees the full 208 V and draws 20.8 A, so
   $$\begin{aligned} P &= 3 \times 208 \times 20.8 \\ &= 12.98\ \text{kW} \end{aligned}$$
   three times as much.
3. **Line current in delta.**
   $$\sqrt3 \times 20.8 = 36.0\ \text{A}$$

**Answer:** 4.32 kW in wye and 12.98 kW in delta, three times as much.
:::
:::

::: example
## A 10 kW resistive heater can run from 240 V single-phase or from 208 V three-phase. What current does each draw from the wires?

::: solution
1. **Single-phase.**
   $$10\,000/240 = 41.7\ \text{A}$$
   in each of two wires.
2. **Three-phase.**
   $$\frac{10\,000}{\sqrt3 \times 208} = 27.8\ \text{A}$$
   in each of three wires.
3. **Compare.** Three wires carrying 27.8 A deliver the same power as two carrying 41.7 A, using less copper in all.

**Answer:** 41.7 A in each of two wires at 240 V single-phase, and 27.8 A in each of three wires at 208 V three-phase.
:::
:::

::: check
given: V = 120 | 277 | 7200
answer: sqrt(3)*V
unit: V
tolerance: 0.5%

## A three-phase system has {V} V from each line to neutral. What's the line-to-line voltage?

::: right
Right. $\sqrt{3}V_\text{ph}$ = {answer} V.
:::

::: misses
- [2*V] The phases are 120° apart, so the difference is √3 times one of them.
- [any] Not yet. Subtract two phasors 120° apart.
:::
:::

::: check
given: a = 10 | 20; b = 8 | 15; c = 5 | 12
answer: sqrt(a^2 + b^2 + c^2 - a*b - b*c - c*a)
unit: A
tolerance: 0.5%

## In-phase loads draw {a}, {b} and {c} A from the three phases. What's the neutral current?

::: right
Right. {answer} A.
:::

::: misses
- [a + b + c] The phase currents are 120° apart; they mostly cancel.
- [any] Not yet. Add the three phasors.
:::
:::

::: check
given: V = 208 | 480 | 600; I = 20 | 100; p = 0.8 | 0.95
answer: sqrt(3)*V*I*p/1000
unit: kW
tolerance: 0.5%

## A balanced three-phase load at {V} V line-to-line draws {I} A per phase at power factor {p}. What's its power?

::: right
Right. $\sqrt{3}V_LI\cos\varphi$ = {answer} kW.
:::

::: misses
- [3*V*I*p/1000] With line-to-line voltage, use √3, or use 3 with the phase voltage.
- [any] Not yet. Three-phase power.
:::
:::

::: check
given: P = 1 | 5 | 20
answer: 2*P
unit: kW
tolerance: 0.5%

## A single-phase load takes {P} kW on average at unity power factor. What's the peak of its instantaneous power?

::: right
Right. Single-phase power pulses between 0 and twice the average: {answer} kW.
:::

::: misses
- [P] That's a balanced three-phase load, whose power is constant.
- [any] Not yet. $p(t) = VI(1 - \cos 2\omega t)$ for a resistor.
:::
:::

::: check
kind: parts
given: R = 5 | 10 | 20; V = 208 | 480

## Three {R} Ω resistors run from a {V} V (line-to-line) supply.

::: part
answer: 3*(V/sqrt(3))^2/R/1000
unit: kW
tolerance: 0.5%

### What power do they take in wye?

::: misses
- [any] Each sees $V/\sqrt3$.
:::
:::

::: part
answer: 3*V^2/R/1000
unit: kW
tolerance: 0.5%

### And in delta?

::: misses
- [any] Each sees the full line voltage: three times the wye power.
:::
:::
:::

::: check
kind: parts
given: P = 10 | 50 | 200; V = 208 | 480 | 4160; f = 0.8 | 0.85 | 0.9

## A three-phase load takes {P} kW from {V} V line-to-line at power factor {f}.

::: part
answer: P*1000/(sqrt(3)*V*f)
unit: A
tolerance: 0.5%

### What line current does it draw?

::: misses
- [P*1000/(sqrt(3)*V)] Divide by the power factor too.
- [any] $P/(\sqrt3 V_{LL}\,\text{pf})$.
:::
:::

::: part
answer: P/f
unit: kVA
tolerance: 0.5%

### What is its apparent power?

::: misses
- [any] $P/\text{pf}$.
:::
:::
:::

::: explain
## Why does a balanced three-phase load need no neutral current?

::: model
The three phase currents are equal sinusoids shifted by a third of a cycle each. Drawn as phasors, they're three equal arrows 120° apart, which form a closed triangle when placed tip to tail, so their sum is zero. Equivalently, at any instant one phase's current is exactly balanced by the sum of the other two, so the current flowing out on some lines returns on the others and nothing is left for a neutral. Only when the loads are unequal does a neutral current flow, equal to the imbalance.
:::
:::

::: practice

::: check
given: V = 100 | 120 | 230 | 240 | 277 | 7200 | 20000
answer: sqrt(3)*V
unit: V
tolerance: 0.5%

## Line-to-line from {V} V phase?

::: misses
- [any] √3 × phase.
:::
:::

::: check
given: a = 0 | 50; b = 1 | 40; c = 2 | 30
answer: sqrt(a^2 + b^2 + c^2 - a*b - b*c - c*a)
unit: A
tolerance: 0.5%

## Neutral current: {a}, {b}, {c} A?

::: misses
- [any] Add the phasors.
:::
:::

::: check
given: V = 208 | 13800; I = 5 | 2000; p = 0.7 | 1
answer: sqrt(3)*V*I*p/1000
unit: kW
tolerance: 0.5%

## Power: {V} V, {I} A, pf {p}?

::: misses
- [any] $\sqrt{3}V_LI\cos\varphi$.
:::
:::
:::