title: Transformers and voltage levels
heading: How a transformer trades voltage for current through its turns ratio, the pole transformer that feeds a house, kVA ratings, impedances seen through a transformer, and core and copper losses with the load where efficiency peaks
eyebrow: D1 · Lesson 3 · Transformers and voltage levels
xp: 40
---

::: hook
A transformer is two coils on an iron core, with no moving parts, and it's the reason the grid uses alternating current. It changes voltage in proportion to its turns, changes current in the inverse proportion, and does it at 98 to 99.5% efficiency. The gray can on a utility pole takes 7.2 kV from the distribution line and delivers 240 V to a few houses, and the same principle, scaled up, steps a power plant's output up to 345 kV.
:::

::: play
- Efficiency of a 50 kVA distribution transformer against its load, as a fraction of rated: $\eta = xS/(xS + P_\text{core} + x^2P_\text{cu})$, with constant core loss and copper loss rising as the square of the load.
- The efficiency peaks where the two losses are equal, at $x = \sqrt{P_\text{core}/P_\text{cu}}$.
- Utilities design distribution transformers to peak near their typical load, often well below full rating.
:::

```sim plot
view: graph
x: x = 0.02..1.5
y: e = 0.9..1
slider: c = 50..400 step 10 = 150
slider: u = 200..1500 step 50 = 600
plot: x*50000/(x*50000 + c + x^2*u) | samples: 300 | label: efficiency
readout: load for peak efficiency, × rated = sqrt(c/u) | digits: 3
readout: peak efficiency = sqrt(c/u)*50000/(sqrt(c/u)*50000 + 2*c) | digits: 4
```

::: predict
## A pole transformer steps 7.2 kV down to 240 V and is rated 50 kVA. At full load, what current flows on the 240 V side?

- [ ] 6.9 A
- [x] About 208 A
- [ ] About 50 A
- [ ] About 7 kA

::: reveal
50 kVA/240 V = 208 A on the secondary, while the primary carries only 50 kVA/7.2 kV = 6.9 A. The turns ratio is 30, and current goes down by exactly the factor that voltage goes up.
:::
:::

::: nameit
## The ideal transformer

With $N_1$ turns on the primary and $N_2$ on the secondary,

$$\frac{V_2}{V_1} = \frac{N_2}{N_1}, \qquad \frac{I_2}{I_1} = \frac{N_1}{N_2}$$

so power in equals power out. An impedance $Z_2$ on the secondary looks like $Z_2(N_1/N_2)^2$ from the primary.

## Ratings

Transformers are rated in volt-amperes (kVA or MVA), because their heating depends on current and voltage regardless of power factor. Rated current on a side is the rating divided by that side's voltage (by $\sqrt{3}V_L$ for three-phase).

## Losses

- **Core loss** (hysteresis and eddy currents in the iron) depends on voltage and is nearly constant whenever the transformer is energized.
- **Copper loss** in the windings goes as current squared, $x^2P_\text{cu}$ at a fraction x of rated load.

Efficiency peaks where they're equal. A real transformer also has leakage reactance, usually quoted as a percent impedance, which limits fault current (lesson 6).
:::

::: example
## The 50 kVA transformer has 150 W of core loss and 600 W of copper loss at full load. Find its efficiency at full and half load at unity power factor.

::: solution
1. **Full load.**
   $$\begin{aligned} \eta &= \frac{50\,000}{50\,000 + 150 + 600} \\ &= 98.5\% \end{aligned}$$
2. **Half load.** The copper loss is now 150 W:
   $$\begin{aligned} \eta &= \frac{25\,000}{25\,000 + 150 + 150} \\ &= 98.8\% \end{aligned}$$
3. **Why half load is the peak.** The two losses are equal at
   $$\begin{aligned} x &= \sqrt{150/600} \\ &= 0.5 \end{aligned}$$
4. **Referred load.** A 2.4 Ω load on the 240 V side looks like this from the 7.2 kV line:
   $$2.4 \times 30^2 = 2160\ \Omega$$

**Answer:** 98.5% at full load and 98.8% at half load, which is the peak.
:::
:::

::: example
## The 50 kVA transformer (150 W core loss, 600 W copper loss at full load) runs at full load for 8 hours a day and quarter load for 16. What is its efficiency over the day?

::: solution
1. **Energy out.**
   $$\begin{aligned} E &= 8 \times 50 + 16 \times 12.5 \\ &= 600\ \text{kWh} \end{aligned}$$
2. **Core loss.** It runs all day:
   $$0.15 \times 24 = 3.6\ \text{kWh}$$
3. **Copper loss.** It scales with the square of the load. At full load:
   $$0.6 \times 8 = 4.8\ \text{kWh}$$
   and at quarter load:
   $$0.6 \times 0.0625 \times 16 = 0.6\ \text{kWh}$$
4. **Efficiency.** The losses total 9.0 kWh:
   $$\begin{aligned} \eta &= \frac{600}{600 + 9.0} \\ &= 98.5\% \end{aligned}$$

**Answer:** the transformer is 98.5% efficient over the day.
:::
:::

::: example
## A 30:1 transformer has 0.1 Ω of winding resistance referred to its secondary. What does that look like from the primary?

::: solution
1. **Scale by the turns ratio squared.** Impedances transform by the square of the turns ratio:
   $$0.1 \times 30^2 = 90\ \Omega$$
2. **What that means.** A transformer makes the load look $n^2$ times bigger from the high-voltage side, which is why the same per-unit impedance describes it from either side.

**Answer:** from the primary, the winding resistance looks like 90 Ω.
:::
:::

::: check
given: a = 7200 | 12470 | 34500; b = 120 | 240 | 480
answer: a/b
tolerance: 0.5%

## A transformer steps {a} V down to {b} V. What's its turns ratio, primary to secondary?

::: right
Right. $N_1/N_2 = V_1/V_2$ = {answer}.
:::

::: misses
- [b/a] That's secondary over primary.
- [any] Not yet. Voltage ratio.
:::
:::

::: check
given: S = 25 | 50 | 167; V = 120 | 240 | 480
answer: S*1000/V
unit: A
tolerance: 0.5%

## A single-phase transformer rated {S} kVA has a {V} V secondary. What's its full-load secondary current?

::: right
Right. S/V = {answer} A.
:::

::: misses
- [any] Not yet. Rating over voltage.
:::
:::

::: check
given: Z = 1 | 5 | 20; n = 10 | 30 | 60
answer: Z*n^2
unit: Ω
tolerance: 0.5%

## A {Z} Ω load sits on the secondary of a transformer with turns ratio {n}:1. What impedance does the primary see?

::: right
Right. $Z(N_1/N_2)^2$ = {answer} Ω.
:::

::: misses
- [Z*n] Impedance transforms by the square of the turns ratio.
- [any] Not yet. Voltage up by n, current down by n.
:::
:::

::: check
given: S = 25 | 100; c = 0.1 | 0.3; u = 0.4 | 1.2; x = 0.3 | 0.5 | 0.75
answer: 100*x*S/(x*S + c + x^2*u)
tolerance: 0.05%

## A {S} kVA transformer has {c} kW of core loss and {u} kW of full-load copper loss. What's its efficiency, in percent, at {x} of rated load and unity power factor?

::: right
Right. $xS/(xS + P_\text{core} + x^2P_\text{cu})$ = {answer}%.
:::

::: misses
- [100*x*S/(x*S + c + u)] Copper loss scales with the square of the load fraction.
- [any] Not yet. Output over output plus losses.
:::
:::

::: check
kind: parts
given: S = 25 | 100; c = 0.2 | 0.5 | 1; u = 1 | 2 | 4; h = 6 | 12

## A {S} kVA transformer has {c}% core loss and {u}% copper loss at full load (as fractions of its rating); it runs at full load for {h} hours a day and is idle otherwise, at unity power factor.

::: part
answer: S*h
unit: kWh
tolerance: 0.5%

### How much energy does it deliver a day?

::: misses
- [any] Rating × hours.
:::
:::

::: part
answer: S*h/(S*h + S*c/100*24 + S*u/100*h)*100
unit: %
tolerance: 0.1%

### What is its all-day efficiency?

::: misses
- [S*h/(S*h + S*c/100*h + S*u/100*h)*100] The core loss runs all 24 hours.
- [any] Out ÷ (out + core × 24 h + copper × load hours).
:::
:::
:::

::: check
kind: parts
given: n = 10 | 30 | 60; z = 0.05 | 0.2

## A transformer with turns ratio {n} has {z} Ω on its low-voltage side.

::: part
answer: z*n^2
unit: Ω
tolerance: 0.5%

### What impedance does that look like from the high-voltage side?

::: misses
- [z*n] Impedance scales with the square of the ratio.
- [any] $Zn^2$.
:::
:::

::: part
answer: n^2
tolerance: 0.5%

### By what factor would a load on the low side appear larger?

::: misses
- [any] $n^2$.
:::
:::
:::

::: explain
## Why does a transformer's efficiency peak at partial load?

::: model
A transformer has two kinds of loss. The core loss, from magnetizing the iron, is nearly constant whenever the transformer is energized, so at light load it's a large fraction of the small power delivered. The copper loss grows with the square of the current, so at heavy load it dominates. Efficiency, output over output plus losses, is highest where the total loss per unit of output is smallest, which works out to the load at which the two losses are equal. Utilities size distribution transformers so that this point falls near the typical load, which is usually well below the peak rating.
:::
:::

::: practice

::: check
given: a = 2400 | 765000; b = 120 | 34500
answer: a/b
tolerance: 0.5%

## Turns ratio: {a} V to {b} V?

::: misses
- [any] $V_1/V_2$.
:::
:::

::: check
given: Z = 0.5 | 50; n = 2 | 100
answer: Z*n^2
unit: Ω
tolerance: 0.5%

## Reflected impedance: {Z} Ω, ratio {n}?

::: misses
- [any] $Zn^2$.
:::
:::

::: check
given: c = 0.05 | 2; u = 0.2 | 8
answer: sqrt(c/u)
tolerance: 0.5%

## Load fraction for peak efficiency: core {c} kW, full-load copper {u} kW?

::: misses
- [any] $\sqrt{P_\text{core}/P_\text{cu}}$.
:::
:::
:::