D2 · Lesson 4 · Rectifiers and inverters
Turning AC into DC with a diode bridge and a reservoir capacitor, the ripple that capacitor leaves, three-phase rectifiers for industrial drives, and turning DC back into AC with an H-bridge, from square waves to pulse-width-modulated sine waves
Almost everything plugged into a wall starts by turning the AC into DC: four diodes flip the negative half-cycles positive and a big capacitor holds the voltage up between peaks. Solar panels, batteries and motor drives need the reverse, an inverter that makes AC from DC. An inverter is four switches in an H shape that connect the load one way and then the other; switched cleverly, thousands of times per cycle, they make a waveform whose average follows a sine.
- A full-wave bridge rectifier on a 120 V RMS, 60 Hz line (170 V peak), with a reservoir capacitor C feeding a load current I.
- The capacitor charges to the peak, then discharges into the load until the next half-cycle's peak catches it: the sawtooth is the ripple.
- More load current or less capacitance means more ripple, approximately .
Predict
A bridge rectifier with a 1000 µF capacitor supplies 1 A from a 60 Hz line. About how large is the ripple?
Between peaks, 1/120 s apart for a full-wave rectifier, the capacitor supplies the 1 A load alone and falls by = 1/(120 × 0.001) = 8.3 V. Halving the ripple takes twice the capacitance, which is why power supplies carry such large capacitors.
Name it
Rectifiers
A bridge of four diodes makes from a sine of peak . Without a capacitor, its average is (108 V from a 120 V RMS line). With a reservoir capacitor, the output sits near , less a ripple of
for a full-wave rectifier (I/(fC) for half-wave). The diodes conduct only in short pulses near the peaks, which draws a distorted current from the line, the reason larger equipment uses power-factor correction (S11).
A three-phase six-pulse rectifier, six diodes on three lines, gives an average of
with small ripple at six times the line frequency: about 648 V from a 480 V line, the DC bus of most industrial motor drives.
Inverters
An H-bridge of four switches applies +V_dc or −V_dc (or zero) across the load. Switched once per half-cycle, it makes a square wave, whose fundamental has a peak of along with large odd harmonics. Sinusoidal PWM switches much faster, varying the duty cycle so that the local average follows a sine; the fundamental's peak is then , with m ≤ 1 the modulation index, and the harmonics move up near the switching frequency, where a small filter or the load's inductance removes them (lesson 5).
Worked example
A 2 A load runs from a 120 V, 60 Hz bridge rectifier. What capacitance keeps the ripple to 5 V?
Show the solution
- Capacitance. The next standard size up is 3900 µF.
- Average output. The peak less half the ripple:
Answer it needs 3333 µF, so a 3900 µF capacitor, and the output averages about 167 V.
Worked example
An H-bridge runs from 170 V. What's the fundamental's peak as a square wave, and the RMS output with sinusoidal PWM at m = 0.9 from 400 V?
Show the solution
- Square wave. peak.
- Sinusoidal PWM. peak, or 255 V RMS.
Answer the square wave's fundamental peaks at 216 V, and sinusoidal PWM gives 255 V RMS (360 V peak).
Worked example
The 120 V supply in the first example (3900 µF, 2 A, about 167 V) loses its input. How long until the capacitor falls to 120 V?
Show the solution
- Hold-up time. At constant current, the capacitor falls 47 V, from 167 V to 120 V, in
- Compare with the line. That's more than five cycles of the line. This hold-up time lets equipment ride through brief dips without resetting.
Answer about 92 ms.
Check
A bridge rectifier without a capacitor runs from 120 V RMS. What's the average of its output?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A full-wave rectifier on a 50 Hz line feeds 2 A from a 4700 µF capacitor. About how large is the ripple?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A six-pulse diode rectifier runs on a 400 V (line-to-line) three-phase supply. What's its average DC output?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
An H-bridge inverter with sinusoidal PWM runs from a 170 V bus at modulation index 0.6. What's the RMS of its fundamental output?
Write units the way you normally would: 1.5 V, 1500 mV and 0.0015 kV are the same answer.
Check
A bridge rectifier on 120 V rms at 60 Hz feeds 0.5 A; the ripple must be under 10 V.
(a)
What capacitance does it need?
Write units the way you normally would: 1.5 µF, 1500 nF and 0.0015 mF are the same answer.
(b)
What is the peak of the output, allowing 0.7 V for each of two diodes?
Check
A rectifier's 1000 µF capacitor at 160 V carries 2 A when its input fails; the load quits below 120 V.
(a)
How long is the hold-up?
Write units the way you normally would: 1.5 ms, 1500 µs and 0.0015 s are the same answer.
(b)
What energy does the capacitor give up?
Explain why
Why does a rectifier's reservoir capacitor make the line current flow in short pulses?
With a large capacitor, the rectifier's output stays close to the line's peak voltage, so the diodes are forward-biased only when the line's instantaneous voltage rises above the capacitor's, which happens for a short interval near each peak. In that brief interval the capacitor must take back all the charge the load drew during the rest of the half-cycle, so the current flows as a tall, narrow pulse instead of a sine. These pulses are rich in harmonics and give a poor power factor, which is why larger power supplies add a power-factor-correction stage that draws a sinusoidal current.
Practice
Keep practicing
9 kinds of problem on this topic, dealt one at a time with new numbers every time, for as long as you like.