title: Distribution systems and power quality
heading: Radial feeders, voltage drop and loss with distributed load, voltage limits and regulation, distributed generation raising voltages, harmonics and total harmonic distortion, triplen currents in neutrals, capacitor resonance, and reliability indices
eyebrow: S10 · Lesson 47 · Distribution systems and power quality
xp: 50
---

::: hook
Transmission gets the attention, but most outages customers see start on the distribution system, and most of a utility's capital goes into it. Distribution feeders are radial, resistive and unbalanced, they now carry rooftop solar pushing power backward, and they serve loads, from LED drivers to motor drives, whose currents aren't sinusoidal. This lesson covers the calculations distribution engineers make daily: feeder voltage drop, the voltage rise from distributed generation, harmonic distortion and resonance, and how reliability is measured.
:::

::: play
- A load current with a 60 Hz fundamental of 100 A plus adjustable 3rd, 5th and 7th harmonics, in time and as a spectrum.
- The readout is the total harmonic distortion: the RMS of all harmonics relative to the fundamental.
- Odd harmonics like these come from rectifier front ends in electronics. The third harmonics of three phases are in step, so they add in the neutral instead of cancelling.
:::

```sim plot
view: spectrum
x: t = 0..0.05 s
y: i = -250..250 A
slider: a = 0..60 = 20 A
slider: b = 0..60 = 15 A
slider: c = 0..60 = 10 A
plot: 100*sqrt(2)*cos(2*pi*60*t) + a*sqrt(2)*cos(2*pi*180*t) + b*sqrt(2)*cos(2*pi*300*t) + c*sqrt(2)*cos(2*pi*420*t) | label: current
samples: 1024
freq: f = 0..600 Hz
readout: THD, % = sqrt(a^2 + b^2 + c^2) | digits: 3
readout: neutral current from the 3rd harmonic, A = 3*a | digits: 3
```

::: predict
## A 5 MW load is spread evenly along a feeder instead of sitting at its far end. How does the voltage drop at the end compare?

- [ ] The same
- [x] Half as much
- [ ] A third as much
- [ ] Twice as much

::: reveal
With evenly distributed load the current falls linearly along the feeder, and integrating the drop gives exactly half the drop of the same load lumped at the end: equivalent to lumping it at the midpoint. The loss falls even more, to a third, because loss goes as current squared.
:::
:::

::: nameit
## Feeders

Distribution feeders are radial: one source, power flowing outward. The drop along a feeder segment is about $\sqrt{3}I(R\cos\phi + X\sin\phi)$ line to line, and R is comparable to X. For load spread uniformly along a feeder, the drop at the end is half and the loss a third of what the same total load lumped at the end would cause.

## Voltage limits and control

ANSI C84.1 Range A holds service voltage within ±5% (114 to 126 V on a 120 V base). Substation load tap changers, line voltage regulators and switched capacitors keep feeders inside it.

## Distributed generation

A generator exporting P and absorbing Q at the end of a feeder of impedance R + jX raises the voltage there by about $(RP - XQ)/V^2$ in per unit. Rooftop solar on lightly loaded feeders can push voltages over the upper limit; smart inverters respond by absorbing vars (volt-var control) or curtailing.

## Harmonics

Nonlinear loads draw harmonic currents. **Total harmonic distortion**

$$\text{THD} = \frac{\sqrt{\sum_{h\ge2}I_h^2}}{I_1}$$

IEEE 519 limits harmonic currents at the point of common coupling and voltage THD (5% at most voltages). **Triplen** harmonics (3, 9, 15, ...) are zero sequence (lesson 37): their phase currents add in the neutral, which can carry more current than the phases. A shunt capacitor and the system's inductance resonate at the harmonic order $h_r = \sqrt{S_{sc}/Q_C}$; if that lands near a harmonic the loads produce, distortion is amplified.

## Reliability

**SAIFI** is total customer interruptions divided by customers served (interruptions per customer per year); **SAIDI** is total customer-minutes of interruption divided by customers served (minutes per customer per year); **CAIDI** = SAIDI/SAIFI is the average outage length.
:::

::: example
## A 12.47 kV feeder 5 km long (z = 0.3 + j0.4 Ω/km) serves 5 MW at 0.9 power factor. Compare the drop and loss with the load at the end and spread evenly.

::: solution
1. **Current.**
   $$\begin{aligned} I &= \frac{5\ \text{MW}}{\sqrt{3} \times 12.47\ \text{kV} \times 0.9} \\ &= 257\ \text{A} \end{aligned}$$
2. **Drop with the load at the end.** With R = 1.5 Ω and X = 2.0 Ω:
   $$\begin{aligned} \Delta V &= \sqrt{3}I(R\cos\phi + X\sin\phi) \\ &= 990\ \text{V} \end{aligned}$$
   which is 7.9%.
3. **Loss with the load at the end.**
   $$\begin{aligned} P_\text{loss} &= 3I^2R \\ &= 298\ \text{kW} \end{aligned}$$
4. **Load spread evenly.** The drop is 4.0% and the loss 99 kW.
5. **What it means.** Uniform loading is why long rural feeders survive where a lumped analysis would fail.

**Answer:** lumped at the end, a 7.9% drop and 298 kW of loss; spread evenly, 4.0% and 99 kW.
:::
:::

::: example
## A 3 Mvar capacitor bank is added at a bus with a 75 MVA short-circuit level that feeds many rectifier loads. Is there a problem?

::: solution
1. **Resonant harmonic.**
   $$\begin{aligned} h_r &= \sqrt{75/3} \\ &= 5 \end{aligned}$$
   The bank and the system resonate exactly at the 5th harmonic, the strongest one six-pulse rectifiers produce.
2. **The problem.** Harmonic voltages will be amplified, overheating the capacitors.
3. **The fix.** The usual fix is to detune the bank with a series reactor so it resonates near the 4.7th harmonic, below the 5th.

**Answer:** yes: the bank resonates with the system at the 5th harmonic, which the rectifiers produce most strongly.
:::
:::

::: example
## A 2 MW rooftop-solar aggregate at the end of a 12.47 kV feeder (R = 1.5 Ω, X = 2 Ω) exports at unity power factor. How much does it raise the voltage, and what does absorbing 0.75 Mvar do?

::: solution
1. **Rise at unity power factor.**
   $$\begin{aligned} \Delta V &= RP/V^2 \\ &= \frac{1.5 \times 2 \times 10^6}{12\,470^2} \\ &= 1.93\% \end{aligned}$$
2. **Effect of absorbing vars.** Absorbing Q lowers it by
   $$\begin{aligned} XQ/V^2 &= \frac{2 \times 0.75 \times 10^6}{12\,470^2} \\ &= 0.96\% \end{aligned}$$
   leaving 0.96%.
3. **Power factor.** The inverters then run at power factor 0.94, which is how volt–var settings in modern interconnection rules let more solar onto a feeder.

**Answer:** a 1.93% rise at unity power factor, cut to 0.96% by absorbing 0.75 Mvar.
:::
:::

::: check
given: a = 10 | 25 | 40; b = 5 | 15; c = 3 | 10; I = 100 | 200
answer: 100*sqrt(a^2 + b^2 + c^2)/I
unit: %
tolerance: 0.5%

## A current has a fundamental of {I} A with harmonics of {a}, {b} and {c} A. What's its THD?

::: right
Right. $\sqrt{\sum I_h^2}/I_1$ = {answer}%.
:::

::: misses
- [100*(a + b + c)/I] Harmonics add as root-sum-square, not linearly.
- [any] Not yet. RMS of the harmonics over the fundamental.
:::
:::

::: check
given: a = 8 | 20 | 45
answer: 3*a
unit: A
tolerance: 0.5%

## Each phase of a balanced load carries {a} A of third harmonic. How much third-harmonic current flows in the neutral?

::: right
Right. The three are in phase, so they add: {answer} A.
:::

::: misses
- [0] Positive- and negative-sequence currents cancel in the neutral; third harmonics are zero sequence and add.
- [sqrt(3)*a] They're in step, not 120° apart, so they add directly.
- [any] Not yet. Triplens are zero sequence.
:::
:::

::: check
given: S = 40 | 150 | 500; Q = 1 | 4 | 10
answer: sqrt(S/Q)
tolerance: 0.5%

## A {Q} Mvar capacitor bank sits at a bus with a {S} MVA short-circuit level. At what harmonic order do they resonate?

::: right
Right. $\sqrt{S_{sc}/Q_C}$ = {answer}.
:::

::: misses
- [S/Q] Take the square root: the resonance frequency goes as $1/\sqrt{LC}$.
- [any] Not yet. $h_r = \sqrt{S_{sc}/Q_C}$.
:::
:::

::: check
given: R = 1 | 3; X = 2 | 4; P = 1 | 3; Q = 0.3 | 1; V = 12.47 | 24.9
answer: 100*(R*P - X*Q)/V^2
unit: %
tolerance: 0.5%

## A generator exports {P} MW and absorbs {Q} Mvar at the end of a feeder of {R} + j{X} Ω at {V} kV. Estimate the voltage rise.

::: right
Right. $(RP - XQ)/V^2$ = {answer}%.
:::

::: misses
- [100*(R*P + X*Q)/V^2] Absorbing vars lowers the voltage: subtract XQ.
- [any] Not yet. Reverse the voltage-drop formula.
:::
:::

::: check
given: d = 2 | 6 | 12
answer: d/2
unit: %
tolerance: 0.5%

## A load lumped at the end of a feeder would cause a {d}% drop. What's the drop if the same load is spread evenly along it?

::: right
Right. Half: {answer}%.
:::

::: misses
- [d/3] That's the ratio for the loss, not the drop.
- [any] Not yet. Even loading acts like the load at the midpoint.
:::
:::

::: check
given: N = 10000 | 50000; m = 4000 | 30000; k = 60 | 180
answer: m*k/N
unit: min
tolerance: 0.5%

## A utility serving {N} customers had {m} customer interruptions in a year, averaging {k} minutes each. What's its SAIDI?

::: right
Right. Customer-minutes over customers: {answer} minutes per customer per year.
:::

::: misses
- [m/N] That's SAIFI, interruptions per customer.
- [any] Not yet. Total customer-minutes divided by customers served.
:::
:::

::: check
kind: parts
given: R = 0.5 | 1.5 | 3; X = 1 | 2 | 4; P = 1 | 3; Q = 0.3 | 0.5 | 1; V = 12.47 | 24.9

## Solar inverters export {P} MW and absorb {Q} Mvar at the end of a {V} kV feeder of {R} + j{X} Ω.

::: part
answer: (R*P - X*Q)/V^2*100
unit: %
tolerance: 1%

### By how much do they raise the voltage there?

::: misses
- [(R*P + X*Q)/V^2*100] Absorbing vars lowers the voltage.
- [any] $(RP - XQ)/V^2$.
:::
:::

::: part
answer: P/sqrt(P^2 + Q^2)
tolerance: 0.5%

### At what power factor do they run?

::: misses
- [any] P/|S|.
:::
:::
:::

::: check
kind: derivation
vars: I = 10..1000, a = 0..300, b = 0..300, c = 0..300

## A current has fundamental I and harmonics a, b and c (all RMS).

::: step
answer: sqrt(a^2 + b^2 + c^2)/I

### What is its THD (as a fraction)?
:::

::: step
answer: sqrt(I^2 + a^2 + b^2 + c^2)

### What is its total RMS value?
:::

::: right
Right. Harmonics add in power, so a THD of 30% raises the RMS current only 4.4%, though it can still overheat transformers.
:::
:::

::: explain
## Why does third-harmonic current add up in the neutral of a balanced three-phase system instead of cancelling?

::: model
In a balanced system the fundamental currents of the three phases are 120° apart, so they sum to zero at every instant and the neutral carries nothing. The third harmonic of each phase is at three times the frequency, so phase shifts of 120° and 240° at the fundamental become 360° and 720° at the third harmonic: whole cycles. The three third-harmonic currents are therefore exactly in step, a zero-sequence set, and they add in the neutral to three times the per-phase value. With many single-phase electronic loads, the neutral can carry more current than any phase conductor, which is why neutrals in office buildings are often oversized.
:::
:::

::: practice

::: check
given: a = 6 | 30; b = 4 | 20; c = 2 | 12; I = 50 | 150
answer: 100*sqrt(a^2 + b^2 + c^2)/I
unit: %
tolerance: 0.5%

## THD: {I} A with {a}, {b}, {c} A of harmonics?

::: misses
- [any] Root-sum-square over the fundamental.
:::
:::

::: check
given: S = 60 | 300; Q = 2 | 12
answer: sqrt(S/Q)
tolerance: 0.5%

## Resonant order: {Q} Mvar at {S} MVA?

::: misses
- [any] $\sqrt{S_{sc}/Q}$.
:::
:::

::: check
given: R = 0.5 | 2; X = 1 | 3; P = 0.5 | 2; Q = 0.2 | 0.8; V = 12.47 | 34.5
answer: 100*(R*P - X*Q)/V^2
unit: %
tolerance: 0.5%

## DG voltage change: {R} + j{X} Ω, {P} MW out, {Q} Mvar in, {V} kV?

::: misses
- [any] $(RP - XQ)/V^2$.
:::
:::
:::