title: Final exam
heading: "Final exam: power system analysis"
eyebrow: S10 · Final exam
type: problems
---

::: hook
Twelve problems from the whole course: complex power and per unit, transformers and lines, power transfer and compensation, network matrices and power flow, generators and their capability, generation adequacy, dispatch and prices, frequency control, HVDC, state estimation, faults and open conductors, protection, stability, inverter-based resources and distribution. Give yourself three hours and work without the lessons open. "Another set" deals a different exam.
:::

::: pool
pick: 12

::: check
kind: parts
given: P = 40 | 150; f = 0.75 | 0.85; b = 0.95 | 0.98; V = 69 | 138

## A {P} MW load at {f} lagging on a {V} kV line.

::: part
answer: P*1e6/(sqrt(3)*V*1e3*f)
unit: A
tolerance: 0.5%

### Line current?

::: misses
- [any] $P/(\sqrt{3}V\cos\phi)$.
:::
:::

::: part
answer: P*(tan(acos(f)) - tan(acos(b)))
unit: Mvar
tolerance: 0.5%

### Capacitor for {b}?

::: misses
- [any] $P(\tan\phi_1 - \tan\phi_2)$.
:::
:::

::: part
answer: 100*(1 - (f/b)^2)
unit: %
tolerance: 0.5%

### Cut in line loss?

::: misses
- [any] $1 - (\text{pf}_1/\text{pf}_2)^2$.
:::
:::
:::

::: check
kind: parts
given: X = 0.08 | 0.2; a = 30 | 250; b = 12.5 | 22; c = 13.8 | 24; r = 0.007 | 0.012; x = 0.05 | 0.09; g = 0.8 | 0.9

## A machine ({a} MVA, {b} kV, X = {X}) on a 100 MVA, {c} kV base; a transformer with R = {r}, X = {x} pu at full load, {g} lagging.

::: part
answer: X*(b/c)^2*(100/a)
tolerance: 0.5%

### Machine's X on the base?

::: misses
- [any] Change of base.
:::
:::

::: part
answer: 100*(sqrt((1 + r*g + x*sqrt(1 - g^2))^2 + (x*g - r*sqrt(1 - g^2))^2) - 1)
unit: %
tolerance: 0.5%

### Transformer regulation?

::: misses
- [any] $|1 + IZ| - 1$.
:::
:::
:::

::: check
kind: parts
given: D = 7 | 11; s = 10 | 14; d = 0.4 | 0.5; r = 13 | 17; V = 230 | 500

## A {V} kV line, $D_m$ = {D} m, two-conductor bundles {d} m apart, GMR {s} mm, radius {r} mm.

::: part
answer: 0.2*ln(D/sqrt(s/1000*d))
unit: mH
tolerance: 0.5%

### L per km?

::: misses
- [any] $0.2\ln(D_m/\sqrt{D_sd})$.
:::
:::

::: part
answer: 55.63/ln(D/sqrt(r/1000*d))
unit: nF
tolerance: 0.5%

### C per km?

::: misses
- [any] $55.63/\ln(D_m/\sqrt{rd})$.
:::
:::

::: part
answer: V^2/sqrt(0.2e-3*ln(D/sqrt(s/1000*d))/(55.63e-12*1000/ln(D/sqrt(r/1000*d))))
unit: MW
tolerance: 0.5%

### SIL?

::: misses
- [any] $V^2/\sqrt{L/C}$.
:::
:::
:::

::: check
kind: parts
given: l = 150 | 400; V = 345 | 500; B = 4 | 5

## An open {l} km, {V} kV line with B = {B} µS/km (wavelength 4940 km).

::: part
answer: 1/cos(2*pi*l/4940)
tolerance: 0.5%

### Ferranti rise?

::: misses
- [any] $1/\cos\beta l$.
:::
:::

::: part
answer: V^2*B*1e-6*l
unit: Mvar
tolerance: 0.5%

### Charging vars?

::: misses
- [any] $V^2Bl$.
:::
:::
:::

::: check
kind: parts
given: V = 0.97 | 1.04; W = 0.95 | 1; X = 0.2 | 0.4; d = 12 | 25; k = 0.3 | 0.5

## Buses at {V} and {W} pu, {d}° apart across X = {X}; the line gets {k} series compensation.

::: part
answer: V*W*sin(d*pi/180)/X
tolerance: 0.5%

### Real power now?

::: misses
- [any] $V_1V_2\sin\delta/X$.
:::
:::

::: part
answer: V*W/(X*(1 - k))
tolerance: 0.5%

### Transfer limit with compensation?

::: misses
- [any] $V_1V_2/(X(1 - k))$.
:::
:::
:::

::: check
kind: parts
given: X = 0.15 | 0.25; P = 0.5 | 1; Q = 0.2 | 0.5; n = 57 | 300; f = 0.1 | 0.2; let m = round(n*f)

## A two-bus case (X = {X}, load {P} + j{Q}); a {n}-bus case with {m} PV buses.

::: part
answer: sqrt(((1 - 2*Q*X) + sqrt((1 - 2*Q*X)^2 - 4*X^2*(P^2 + Q^2)))/2)
tolerance: 0.5%

### Two-bus load voltage?

::: misses
- [any] Upper root.
:::
:::

::: part
answer: 2*(n - 1) - m
tolerance: 0

### Unknowns in the second?

::: misses
- [any] $2(n - 1) - n_{PV}$.
:::
:::
:::

::: check
kind: parts
given: a = 0.1 | 0.2; b = 0.15 | 0.3; c = 0.12 | 0.4; g = 0.15 | 0.25

## A triangle ($x_{12}$ = {a}, $x_{23}$ = {b}, $x_{13}$ = {c}) with a generator j{g} at bus 1.

::: part
answer: (a + b)/(a + b + c)
tolerance: 0.5%

### PTDF of line 1–3 for a transfer 1 → 3?

::: misses
- [any] Inverse-reactance share.
:::
:::

::: part
answer: g + c*(a + b)/(a + b + c)
tolerance: 0.5%

### $Z_{33}$?

::: misses
- [any] $x_g + x_{13}\parallel(x_{12} + x_{23})$.
:::
:::
:::

::: check
kind: parts
given: X = 1 | 1.6; P = 0.6 | 0.9; Q = 0 | 0.4; E = 1.8 | 2.3

## A generator with $X_s$ = {X} delivers {P} + j{Q} at 1 pu; its field limit is E = {E}.

::: part
answer: atan(X*P/(1 + X*Q))*180/pi
unit: °
tolerance: 0.5%

### Power angle?

::: misses
- [any] $\tan^{-1}(X_sP/(1 + X_sQ))$.
:::
:::

::: part
answer: (sqrt(E^2 - (P*X)^2) - 1)/X
tolerance: 0.5%

### Most Q at that P?

::: misses
- [any] $(\sqrt{E^2 - (PX_s)^2} - 1)/X_s$.
:::
:::
:::

::: check
kind: parts
given: b = 4.5 | 5.5; c = 0.003 | 0.006; d = 5.5 | 6.5; e = 0.004 | 0.008; D = 400 | 800; x = 15 | 25; y = 40 | 55

## Two units ({b}, {c}) and ({d}, {e}) share {D} MW; separately, a binding triangle with generators at {x} and {y} dollars per MWh.

::: part
answer: (D + b/(2*c) + d/(2*e))/(1/(2*c) + 1/(2*e))
tolerance: 0.5%

### λ, dollars per MWh?

::: misses
- [any] Equal incremental cost.
:::
:::

::: part
answer: 2*y - x
tolerance: 0.5%

### Triangle bus-3 LMP?

::: misses
- [any] $2b - a$.
:::
:::
:::

::: check
kind: parts
given: P = 0.6 | 1.8; S = 30 | 100; H = 2.5 | 5; L = 0.03 | 0.06; R = 0.04 | 0.06; D = 0.5 | 1.5

## A {S} GW system with H = {H} s loses {P} GW; a system with droop {R} and damping {D} loses {L} pu.

::: part
answer: P*60/(2*H*S)
unit: Hz/s
tolerance: 0.5%

### ROCOF?

::: misses
- [any] $\Delta Pf_0/(2HS)$.
:::
:::

::: part
answer: -L/(1/R + D)*60
unit: Hz
tolerance: 0.5%

### Settling deviation in the second?

::: misses
- [any] $-\Delta P/(1/R + D)$.
:::
:::
:::

::: check
kind: parts
given: X = 0.12 | 0.2; T = 0.08 | 0.1; S = 100 | 400; V = 115 | 230; r = 10 | 30

## A {S} MVA generator (X″ = {X}) and transformer (X = {T}) on the same base feed a {V} kV bus; X/R = {r} there.

::: part
answer: 1/(X + T)*S*1e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Three-phase fault current?

::: misses
- [any] $1/(X'' + X_T)$ times $I_\text{base}$.
:::
:::

::: part
answer: sqrt(2)*(1 + exp(-pi/r))/(X + T)*S*1e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Worst first peak?

::: misses
- [any] $\sqrt{2}(1 + e^{-\pi R/X})I$.
:::
:::
:::

::: check
kind: parts
given: a = 0.12 | 0.25; c = 0.06 | 0.35; I = 1.6 | 2.2

## A bus with $Z_1 = Z_2$ = j{a}, $Z_0$ = j{c}.

::: part
answer: 3/(2*a + c)
tolerance: 0.5%

### Line-to-ground current?

::: misses
- [any] $3/(2Z_1 + Z_0)$.
:::
:::

::: part
answer: (3/I - 2*a - c)/3
tolerance: 0.5%

### Neutral reactance for {I} pu?

::: misses
- [any] $(3/I - 2Z_1 - Z_0)/3$.
:::
:::
:::

::: check
kind: parts
given: M = 3 | 8; T = 0.8 | 2; Z = 30 | 90; C = 200 | 400; V = 2000 | 3000

## A very inverse relay (dial {T}) at {M} times pickup; a line of {Z} Ω with CT ratio {C} and VT ratio {V}.

::: part
answer: T*(19.61/(M^2 - 1) + 0.491)
unit: s
tolerance: 0.5%

### Relay time?

::: misses
- [any] IEEE very inverse.
:::
:::

::: part
answer: 0.8*Z*C/V
unit: Ω
tolerance: 0.5%

### Zone 1 (80%) in secondary ohms?

::: misses
- [any] $0.8Z\,\text{CTR}/\text{VTR}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 0.9; M = 1.8 | 2.4; H = 3 | 6

## A machine (H = {H} s) at {P} pu, $P_{max}$ = {M}, zero-transfer fault cleared with the network intact.

::: part
answer: sqrt(2*pi*60*M*cos(asin(P/M))/(2*H))/(2*pi)
unit: Hz
tolerance: 0.5%

### Swing frequency?

::: misses
- [any] $\sqrt{\omega_sP_s/2H}/2\pi$.
:::
:::

::: part
answer: acos((pi - 2*asin(P/M))*(P/M) - cos(asin(P/M)))*180/pi
unit: °
tolerance: 0.5%

### Critical clearing angle?

::: misses
- [any] Equal-area formula.
:::
:::

::: part
answer: sqrt(4*H*(acos((pi - 2*asin(P/M))*(P/M) - cos(asin(P/M))) - asin(P/M))/(2*pi*60*P))
unit: s
tolerance: 0.5%

### Critical clearing time?

::: misses
- [any] $\sqrt{4H(\delta_c - \delta_0)/\omega_sP_m}$.
:::
:::
:::

::: check
kind: parts
given: a = 4 | 40; b = 6 | 60; P = 1 | 2.5; s = 0.15 | 0.5; w = 3 | 6

## Two machines (H = {a}, {b} s), $P_s$ = {P}; a mode at $-\given{s} \pm j\given{w}$.

::: part
answer: sqrt(2*pi*60*P*(a + b)/(2*a*b))/(2*pi)
unit: Hz
tolerance: 0.5%

### Swing frequency?

::: misses
- [any] $\sqrt{\omega_sP_s/2H_{eq}}/2\pi$.
:::
:::

::: part
answer: ln(2)/s
unit: s
tolerance: 0.5%

### Halving time of the mode?

::: misses
- [any] ln 2/σ.
:::
:::
:::

::: check
kind: parts
given: S = 500 | 2000; P = 150 | 400; a = 10 | 30; b = 6 | 15; c = 3 | 8; I = 100 | 200

## A {P} MW inverter plant at a {S} MVA bus; a {I} A fundamental with {a}, {b}, {c} A harmonics.

::: part
answer: S/P
tolerance: 0.5%

### SCR?

::: misses
- [any] $S_{sc}/P$.
:::
:::

::: part
answer: 100*sqrt(a^2 + b^2 + c^2)/I
unit: %
tolerance: 0.5%

### THD?

::: misses
- [any] Root-sum-square over the fundamental.
:::
:::
:::

::: check
kind: parts
given: V = 200 | 250; a = 10 | 15; X = 10 | 14; I = 2 | 3

## An HVDC bipole's rectifiers each have {V} kV RMS on their valve sides, fire at α = {a}° and carry {I} kA through $X_c$ = {X} Ω.

::: part
answer: 3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I
unit: kV
tolerance: 0.5%

### DC voltage of each pole?

::: misses
- [any] $1.35V_{LL}\cos\alpha - (3/\pi)X_cI_d$.
:::
:::

::: part
answer: 2*(3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I)*I
unit: MW
tolerance: 0.5%

### Power sent by the bipole?

::: misses
- [any] Two poles, each $V_dI_d$.
:::
:::
:::

::: check
kind: parts
given: a = 0.6 | 0.8; b = 0.62 | 0.85; s = 0.01 | 0.02; t = 0.02 | 0.04

## A line's flow is metered at both ends: {a} pu (σ = {s}) and {b} pu (σ = {t}), losses neglected.

::: part
answer: (a/s^2 + b/t^2)/(1/s^2 + 1/t^2)
tolerance: 0.1%

### Weighted least-squares estimate of the flow, in per unit?

::: misses
- [any] Weights $1/\sigma^2$.
:::
:::

::: part
answer: (a - b)^2/(s^2 + t^2)
tolerance: 0.5%

### J at the estimate?

::: misses
- [any] $(z_1 - z_2)^2/(\sigma_1^2 + \sigma_2^2)$ for two meters.
:::
:::
:::

::: check
kind: parts
given: p = 0.8 | 1.1; a = 0.5 | 0.8; c = 1 | 2

## Two phases of a line carrying {p} pu break. Across the break $Z_1' = Z_2'$ = j{a} pu and $Z_0'$ = j{c} pu.

::: part
answer: p*a/(2*a + c)
tolerance: 0.5%

### Each sequence current, in per unit?

::: misses
- [any] Networks in series: $IZ_1'/(Z_1' + Z_2' + Z_0')$.
:::
:::

::: part
answer: 3*p*a/(2*a + c)
tolerance: 0.5%

### Current in the phase still closed, in per unit?

::: misses
- [any] $3I_1$.
:::
:::
:::
:::