title: Frequency control
heading: Frequency as the measure of the balance between generation and load, inertia and the rate of change of frequency, governor droop and load damping, the frequency nadir, sharing among units, and automatic generation control with area control error
eyebrow: S10 · Lesson 30 · Frequency control
xp: 50
---

::: hook
There's no storage tank on the grid. Every instant, generation must equal load plus losses, and the only thing that absorbs a mismatch is the kinetic energy of the spinning machines, whose speed is the system frequency. When a large plant trips, frequency starts falling within milliseconds; within seconds, every governor on the system opens its valves a little; within minutes, the control center's automatic generation control restores frequency to 60 Hz. This lesson quantifies each of those layers.
:::

::: play
- The frequency of an interconnection after losing 5% of its load-serving generation, with inertia constant H, governor and turbine time constant T, 5% droop and load damping D = 1.
- Frequency falls at first at a rate set by inertia alone, bottoms out at the **nadir** as the governors catch up, then settles at a lower steady value set by droop.
- Halve H (more inverter-based generation, lesson 46) and the initial fall doubles in speed and the nadir deepens; slower governors deepen it too.
:::

```sim plot
view: graph
x: t = 0..20 s
y: df = -0.8..0.05 Hz
slider: H = 1..8 = 5 s
slider: T = 0.5..8 = 4 s
plot: -0.05*60*((1/21)*(1 - exp(-(2*H + T)/(4*H*T)*t)*(cos(sqrt(21/(2*H*T) - ((2*H + T)/(4*H*T))^2)*t) + (2*H + T)/(4*H*T)/sqrt(21/(2*H*T) - ((2*H + T)/(4*H*T))^2)*sin(sqrt(21/(2*H*T) - ((2*H + T)/(4*H*T))^2)*t))) + T/(2*H*T)*exp(-(2*H + T)/(4*H*T)*t)*sin(sqrt(21/(2*H*T) - ((2*H + T)/(4*H*T))^2)*t)/sqrt(21/(2*H*T) - ((2*H + T)/(4*H*T))^2)) | samples: 800 | label: frequency deviation
plot: -0.05*60/21 + 0*t | dashed | color: ch3 | label: settling value
readout: initial rate of fall, Hz/s = 0.05*60/(2*H) | digits: 3
```

::: predict
## An interconnection with 60 GW of synchronous generation (H = 5 s on that rating) suddenly loses a 1.2 GW plant. How fast does frequency start to fall?

- [ ] 0.012 Hz/s
- [x] 0.12 Hz/s
- [ ] 1.2 Hz/s
- [ ] It doesn't fall until the governors react

::: reveal
Before any control acts, the missing power comes out of the rotors' kinetic energy: $df/dt = \Delta P f_0/(2HS)$ = 1.2 × 60/(2 × 5 × 60) = 0.12 Hz/s. Governors need a second or more to respond, so inertia alone sets the first moments, which is why falling system inertia worries grid operators.
:::
:::

::: nameit
## Inertia

A machine's **inertia constant** H is its stored kinetic energy at synchronous speed divided by its rating (2 to 9 s for turbine generators). For a whole system of rating S with total H, a power deficit ΔP gives

$$\frac{df}{dt} = -\frac{\Delta P}{2HS}f_0$$

the **rate of change of frequency** (ROCOF).

## Primary control: droop

A governor with **droop** R (typically 5%) raises output in proportion to the frequency drop: a fall of R in per-unit frequency drives the unit from no load to full load. Loads also fall a little with frequency, by D percent per percent (**load damping**, about 1 to 2). In steady state after a loss $\Delta P_L$ (per unit on the system base):

$$\Delta f = -\frac{\Delta P_L}{\sum 1/R_i + D}f_0$$

Units share the change in proportion to rating/R. The combined $\beta = \sum 1/R_i + D$ is the **frequency response characteristic**.

## Dynamics and the nadir

With a governor-turbine lag T: $2H\frac{d\Delta f}{dt} = \Delta P_m - \Delta P_L - D\Delta f$ and $T\frac{d\Delta P_m}{dt} = -\Delta f/R - \Delta P_m$ (per unit). The lowest point, the **nadir**, must stay above the threshold where under-frequency load shedding starts (59.3 Hz in much of North America).

## Secondary control: AGC

Droop leaves a frequency error and changes tie-line flows. Each balancing area's **automatic generation control** computes its **area control error**

$$\text{ACE} = (P_\text{tie} - P_\text{tie,sched}) - 10B(f - f_0)$$

with frequency bias B in MW/0.1 Hz (negative), and moves its generators to drive ACE to zero over minutes, restoring 60 Hz and scheduled interchange. Tertiary control (economic dispatch, lesson 27) then reshuffles units for cost.
:::

::: example
## A system rated 10 GW has 5% droop on all its generation and load damping D = 1. It loses 500 MW. Where does frequency settle, and how low does it dip with H = 5 s and T = 4 s?

::: solution
1. **Per unit.** On the 10 GW base, $\Delta P_L$ = 0.05 and
   $$\begin{aligned} \sum 1/R + D &= 20 + 1 \\ &= 21 \end{aligned}$$
2. **Settling frequency.**
   $$\begin{aligned} \Delta f &= -0.05/21 \times 60 \\ &= -0.143\ \text{Hz} \end{aligned}$$
3. **The dip.** The frequency falls at 0.30 Hz/s at first, reaches its nadir of −0.41 Hz at 2.4 s, then recovers to −0.143 Hz.
4. **With half the inertia.** The initial rate doubles and the nadir deepens to −0.54 Hz at 1.6 s.

**Answer:** it settles 0.143 Hz low, after dipping to −0.41 Hz at 2.4 s.
:::
:::

::: example
## A 600 MW unit with 5% droop and a 400 MW unit with 4% droop pick up a 100 MW load increase. How do they share it?

::: solution
1. **Each unit's response.** It's rating/R, in MW per unit frequency:
   $$\begin{aligned} 600/0.05 &= 12{,}000 \\ 400/0.04 &= 10{,}000 \end{aligned}$$
2. **Share the load.** The 600 MW unit takes
   $$\begin{aligned} \Delta P_1 &= 100 \times 12/22 \\ &= 54.5\ \text{MW} \end{aligned}$$
   and the 400 MW unit 45.5 MW.
3. **Frequency drop.** Ignoring load damping:
   $$\begin{aligned} \Delta f &= 100/22{,}000\ \text{pu} \\ &= 0.27\ \text{Hz} \end{aligned}$$

**Answer:** the 600 MW unit takes 54.5 MW and the 400 MW unit 45.5 MW, and the frequency falls 0.27 Hz.
:::
:::

::: example
## A 10 GW system with H = 4 s loses 1 GW. How fast does frequency fall, and how soon would it reach an underfrequency load-shedding threshold of 59.3 Hz if the initial rate held?

::: solution
1. **Initial rate of fall.**
   $$\begin{aligned} \text{ROCOF} &= \frac{\Delta P}{2HS}f_0 \\ &= \frac{1}{2 \times 4 \times 10} \times 60 \\ &= 0.75\ \text{Hz/s} \end{aligned}$$
2. **Time to the threshold.** From 60 Hz, 0.7 Hz of fall at that rate takes
   $$\begin{aligned} t &= 0.7/0.75 \\ &= 0.93\ \text{s} \end{aligned}$$
   before governors have done much.
3. **Less inertia.** Less inertia, as inverter-based generation replaces turbines, makes the fall faster and leaves less time, which is why ROCOF limits and fast frequency response now appear in grid codes.

**Answer:** 0.75 Hz/s, reaching 59.3 Hz in 0.93 s.
:::
:::

::: check
given: P = 0.5 | 1.2 | 3; S = 30 | 100 | 400; H = 3 | 5
answer: P*60/(2*H*S)
unit: Hz/s
tolerance: 0.5%

## A {S} GW system with H = {H} s loses {P} GW of generation. What's the initial rate of change of frequency?

::: right
Right. $\Delta Pf_0/(2HS)$ = {answer} Hz/s.
:::

::: misses
- [P*60/(H*S)] Kinetic energy is $\frac{1}{2}J\omega^2$, so the factor is 2H.
- [any] Not yet. $df/dt = \Delta Pf_0/(2HS)$.
:::
:::

::: check
given: R = 0.04 | 0.05 | 0.06; d = 0.1 | 0.3; S = 100 | 500
answer: (d/60)/R*S
unit: MW
tolerance: 0.5%

## A {S} MW unit with {R} droop sees frequency fall by {d} Hz. How much does its governor raise output?

::: right
Right. $(\Delta f/f_0)/R \times$ rating = {answer} MW.
:::

::: misses
- [d/R*S] Use the per-unit frequency change, Δf/60.
- [any] Not yet. Droop R means a per-unit frequency change of R moves the unit through its full rating.
:::
:::

::: check
given: L = 0.02 | 0.05 | 0.1; R = 0.04 | 0.05; D = 0.5 | 1 | 2
answer: -L/(1/R + D)*60
unit: Hz
tolerance: 0.5%

## A system (all generation at droop {R}) loses {L} pu of generation, with load damping D = {D}. Where does frequency settle?

::: right
Right. $-\Delta P_L/(1/R + D) \times 60$ = {answer} Hz.
:::

::: misses
- [-L*R*60] Include the load damping, $1/R + D$ in the denominator.
- [any] Not yet. $\Delta f = -\Delta P/(\sum 1/R + D)$.
:::
:::

::: check
given: a = 300 | 800; r = 0.04 | 0.05; b = 200 | 600; s = 0.06 | 0.07; P = 50 | 150
answer: P*(a/r)/(a/r + b/s)
unit: MW
tolerance: 0.5%

## A {a} MW unit at {r} droop and a {b} MW unit at {s} droop share a {P} MW load increase. How much does the first take?

::: right
Right. In proportion to rating/R: {answer} MW.
:::

::: misses
- [P*a/(a + b)] Shares go by rating over droop, not rating alone.
- [any] Not yet. Each unit's stiffness is rating/R.
:::
:::

::: check
given: T = -150 | -50 | 80; B = -400 | -150; f = -0.06 | -0.02 | 0.03
answer: T - 10*B*f
unit: MW
tolerance: 0.5%

## An area's tie-line flow is {T} MW from schedule, frequency is {f} Hz from 60, and its bias is {B} MW/0.1 Hz. What's its ACE?

::: right
Right. $\Delta P_\text{tie} - 10B\Delta f$ = {answer} MW. A negative ACE means the area should raise generation.
:::

::: misses
- [T + 10*B*f] B is negative and enters with a minus sign: $-10B\Delta f$.
- [any] Not yet. ACE = $\Delta P_\text{tie} - 10B\Delta f$.
:::
:::

::: check
given: E = 2 | 5 | 10; S = 50 | 400; f = 0.2 | 1
answer: 2*E*S*f/60
unit: MW
tolerance: 0.5%

## A system of {S} MW with H = {E} s is falling at {f} Hz/s just after a disturbance. How large was the power deficit?

::: right
Right. $\Delta P = 2HS(df/dt)/f_0$ = {answer} MW.
:::

::: misses
- [E*S*f/60] Include the factor of 2.
- [any] Not yet. Invert the ROCOF formula.
:::
:::

::: check
kind: parts
given: S = 5 | 20 | 60; H = 2 | 4 | 6; P = 0.5 | 1 | 2; t = 59.5 | 59.3

## A {S} GW system with H = {H} s loses {P} GW. Load shedding begins at {t} Hz.

::: part
answer: P/(2*H*S)*60
unit: Hz/s
tolerance: 0.5%

### What is the initial ROCOF?

::: misses
- [P/(H*S)*60] The kinetic energy is $HS$, and $df/dt = \Delta P f_0/(2HS)$.
- [any] $\Delta Pf_0/(2HS)$.
:::
:::

::: part
answer: (60 - t)/(P/(2*H*S)*60)
unit: s
tolerance: 0.5%

### If that rate held, how soon would shedding begin?

::: misses
- [any] Frequency margin over ROCOF.
:::
:::
:::

::: check
kind: derivation
vars: L = 0.01..0.2, R = 0.03..0.1, D = 0..2, H = 2..8

## A system loses L pu of generation; all generation has droop R and the load damping is D; inertia H.

::: step
answer: L/(2*H)*60

### What is the initial ROCOF, in Hz/s?
:::

::: step
answer: -L/(1/R + D)*60

### Where does frequency settle, in Hz from 60?
:::

::: right
Right. Inertia sets how fast frequency falls; droop and damping set where it stops.
:::
:::

::: explain
## Why does frequency drop at the same rate everywhere in an interconnection after a generator trips?

::: model
All the synchronous machines in an interconnection are locked together electrically: if one tried to slow down relative to the others, the power angle between them would change and synchronizing power would flow to pull it back into step. So after a disturbance the whole interconnection decelerates together, apart from small oscillations between groups of machines, and the power deficit is shared among all the rotors in proportion to their inertia. That's why a plant tripping in one state is seen as a frequency dip by every generator on the continent within a second or two, and why every governor contributes to the recovery.
:::
:::

::: practice

::: check
given: P = 0.3 | 2; S = 20 | 250; H = 2 | 6
answer: P*60/(2*H*S)
unit: Hz/s
tolerance: 0.5%

## ROCOF: lose {P} GW from {S} GW with H = {H} s?

::: misses
- [any] $\Delta Pf_0/(2HS)$.
:::
:::

::: check
given: L = 0.03 | 0.08; R = 0.04 | 0.06; D = 1 | 1.5
answer: -L/(1/R + D)*60
unit: Hz
tolerance: 0.5%

## Settling Δf: loss {L} pu, R = {R}, D = {D}?

::: misses
- [any] $-\Delta P/(1/R + D) \times 60$.
:::
:::

::: check
given: T = -120 | 60; B = -300 | -100; f = -0.04 | 0.02
answer: T - 10*B*f
unit: MW
tolerance: 0.5%

## ACE: tie {T} MW, Δf {f} Hz, B = {B}?

::: misses
- [any] $\Delta P_\text{tie} - 10B\Delta f$.
:::
:::
:::