title: Generator capability and excitation
heading: The capability chart's armature, field, turbine and stability limits, how they move with terminal voltage, voltage regulators and their steady error, and how parallel generators share reactive power
eyebrow: S10 · Lesson 26 · Generator capability and excitation
xp: 50
---

::: hook
Lesson 25 modeled a generator as a voltage behind a reactance. Its operator sees it as a point on a chart: real power across, reactive power up and down, inside a boundary drawn by the machine's heating and stability. Push past the boundary and a winding overheats or the rotor slips. The automatic voltage regulator moves the point up and down as the grid's voltage changes, and when several machines share a bus, something must decide who supplies the vars. This lesson draws the boundary and sets up the controls that keep a generator inside it.
:::

::: play
- The curves bound the reactive power of a generator with $X_s$ = 1.2 pu and a field limit of E = 2.2 pu, rated 1 pu, at the terminal voltage V set by the slider.
- The armature limit (solid) is a circle of radius V·I_max about the origin; the field limit (dashed) a circle about $(0, -V^2/X_s)$ of radius $E_\max V/X_s$. The machine may supply the smaller of the two.
- At rated voltage and 0.8 pu of real power the armature limit binds at 0.6 pu of vars. At 0.95 pu voltage it drops to 0.51, just when the grid needs vars most.
:::

```sim plot
view: graph
x: P = 0..0.99
y: Q = 0..1.2
slider: V = 0.9..1.05 = 1
plot: sqrt(V^2 - P^2) | label: armature limit
plot: -V^2/1.2 + sqrt((2.2*V/1.2)^2 - P^2) | dashed | label: field limit
```

::: predict
## A generator is limited by its armature current, and the grid voltage sags from 1.0 to 0.95 pu. What happens to the reactive power it can supply at the same real power?

- [ ] It rises, since the grid needs more
- [x] It falls: the current limit times the lower voltage is less apparent power
- [ ] It stays the same
- [ ] It drops to zero

::: reveal
The armature limit is a current, so the apparent power available is V × I_max. At 0.8 pu of real power the vars fall from $\sqrt{1 - 0.64} = 0.6$ to $\sqrt{0.9025 - 0.64} = 0.51$ pu. Reactive capability shrinks exactly when voltage support is most needed, one reason voltage problems can snowball.
:::
:::

::: nameit
## The capability chart

In the P–Q plane at the terminals, at terminal voltage V:
- **Armature heating:** $P^2 + Q^2 \le (VI_\max)^2$, a circle about the origin.
- **Field heating:** the field current sets E, and $P^2 + (Q + V^2/X_s)^2 \le (E_\max V/X_s)^2$: a circle about $(0, -V^2/X_s)$. It limits vars at low power factor, when the machine is overexcited.
- **Turbine:** a vertical line at the prime mover's maximum power.
- **Underexcitation:** absorbing vars weakens the field and the machine's grip on the grid. For a machine behind $X_s$ connected through $X_e$ to a stiff bus, the steady-state stability limit is a circle with center $(0, \frac{V^2}{2}(\frac{1}{X_e} - \frac{1}{X_s}))$ and radius $\frac{V^2}{2}(\frac{1}{X_e} + \frac{1}{X_s})$, and the operating point must stay above its lower arc. Practical limits add margin and end-region heating.

## Excitation control

The **automatic voltage regulator** (AVR) compares the terminal voltage with its setpoint and drives the exciter. With a proportional gain $K_A$ around a generator of open-circuit gain 1, the steady error is $1/(1 + K_A)$; modern static exciters reach their **ceiling** voltage (often two to three times rated field voltage) in milliseconds, which helps hold the machine in synchronism after faults. **Over-excitation limiters** let the field run above its continuous limit for tens of seconds, then pull it back.

## Sharing vars

Two machines regulating the same bus voltage with pure integral control would fight over the vars. **Reactive droop** (reactive current compensation) lowers each machine's voltage setpoint in proportion to its vars, $\Delta V = -R_q\Delta Q$, so a change in demand divides in inverse proportion to the droops, just as real power divides under governor droop.
:::

::: example
## The generator above ($X_s$ = 1.2 pu, $E_\max$ = 2.2 pu, rated 1 pu) delivers 0.8 pu. How many vars can it supply at 1.0 and at 0.95 pu terminal voltage, and which limit binds?

::: solution
1. **Armature limit at 1.0 pu.**
   $$\begin{aligned} Q &= \sqrt{1 - 0.64} \\ &= 0.600 \end{aligned}$$
2. **Field limit at 1.0 pu.**
   $$\begin{aligned} Q &= -0.833 + \sqrt{1.833^2 - 0.64} \\ &= 0.816 \end{aligned}$$
   so the armature binds, at 0.60 pu.
3. **Armature limit at 0.95 pu.**
   $$\begin{aligned} Q &= \sqrt{0.9025 - 0.64} \\ &= 0.512 \end{aligned}$$
4. **Field limit at 0.95 pu.** The field circle's center is at $-0.95^2/1.2 = -0.752$ and its radius is $2.2 \times 0.95/1.2 = 1.742$, giving 0.795.
5. **Which binds.** The armature still binds, now at 0.51 pu.

**Answer:** 0.60 pu at 1.0 pu terminal voltage and 0.51 pu at 0.95 pu; the armature limit binds both times.
:::
:::

::: example
## The same machine ($X_s$ = 1.2 pu) connects to a stiff 1 pu bus through $X_e$ = 0.3 pu. How many vars can it absorb at 0.8 pu before reaching the steady-state stability limit, and at no load?

::: solution
1. **Center of the stability circle.**
   $$\begin{aligned} Q_0 &= \tfrac{1}{2}(1/0.3 - 1/1.2) \\ &= 1.25 \end{aligned}$$
2. **Its radius.**
   $$\begin{aligned} r &= \tfrac{1}{2}(1/0.3 + 1/1.2) \\ &= 2.083 \end{aligned}$$
3. **At P = 0.8.** The lower arc sits at
   $$\begin{aligned} Q &= 1.25 - \sqrt{2.083^2 - 0.64} \\ &= -0.674\ \text{pu} \end{aligned}$$
   so it can absorb 0.67 pu.
4. **At no load.**
   $$\begin{aligned} Q &= 1.25 - 2.083 \\ &= -0.833 \\ &= -V^2/X_s \end{aligned}$$
   With no field at all, the machine absorbs $V^2/X_s$ and still holds on.

**Answer:** it can absorb 0.67 pu at P = 0.8, and 0.833 pu ($V^2/X_s$) at no load.
:::
:::

::: example
## Two generators share a bus. One has a reactive droop of 4% and the other 6% (each on its own rating, both 100 MVA). The bus needs 50 Mvar more. How do they share it?

::: solution
1. **Same voltage change.** Both machines see it:
   $$\begin{aligned} \Delta V &= -R_1\Delta Q_1 \\ &= -R_2\Delta Q_2 \end{aligned}$$
2. **Ratio of the shares.**
   $$\begin{aligned} \Delta Q_1/\Delta Q_2 &= R_2/R_1 \\ &= 6/4 \end{aligned}$$
3. **Split the 50 Mvar.** The 4% machine takes 0.6 × 50 = 30 Mvar and the 6% machine 20 Mvar.
4. **Other settings.** Equal droops on equal machines would split it evenly; without droop, small differences in setpoints would drive the two in opposite directions.

**Answer:** the 4% machine supplies 30 Mvar and the 6% machine 20 Mvar.
:::
:::

::: check
kind: parts
given: X = 1 | 1.2 | 1.8; E = 1.8 | 2.2; P = 0.5 | 0.8; V = 0.9 | 0.95 | 1.05

## A generator rated 1 pu with $X_s$ = {X} pu and a field limit of E = {E} pu runs at {P} pu and {V} pu terminal voltage.

::: part
answer: sqrt(V^2 - P^2)
tolerance: 0.5%

### What reactive power does the armature limit allow?

::: misses
- [sqrt(1 - P^2)] The current limit gives an apparent power of V × I_max.
- [any] $\sqrt{(VI_\max)^2 - P^2}$.
:::
:::

::: part
answer: -V^2/X + sqrt((E*V/X)^2 - P^2)
tolerance: 0.5%

### What does the field limit allow?

::: misses
- [any] Circle about $(0, -V^2/X_s)$ of radius $E_\max V/X_s$.
:::
:::
:::

::: check
kind: parts
given: X = 0.9 | 1.2 | 1.6; e = 0.2 | 0.4; P = 0 | 0.5 | 0.9

## A machine with $X_s$ = {X} pu connects to a stiff 1 pu bus through $X_e$ = {e} pu and delivers {P} pu.

::: part
answer: 0.5*(1/e - 1/X) - sqrt((0.5*(1/e + 1/X))^2 - P^2)
tolerance: 0.5%

### At what reactive power (negative is absorbing) does it reach the steady-state stability limit?

::: misses
- [any] Lower arc of the circle with center $\frac12(1/X_e - 1/X_s)$ and radius $\frac12(1/X_e + 1/X_s)$.
:::
:::
:::

::: check
kind: parts
given: a = 3 | 4 | 5; b = 6 | 8 | 10; Q = 20 | 50 | 100

## Two equal generators with reactive droops of {a}% and {b}% share a {Q} Mvar increase in demand.

::: part
answer: Q*b/(a + b)
unit: Mvar
tolerance: 0.5%

### How much does the first one take?

::: misses
- [Q*a/(a + b)] The smaller droop takes the larger share.
- [any] Inverse to droop: $Q R_2/(R_1 + R_2)$.
:::
:::
:::

::: check
kind: parts
given: K = 10 | 20 | 50

## A proportional voltage regulator with gain {K} controls a generator of open-circuit gain 1.

::: part
answer: 100/(1 + K)
unit: %
tolerance: 0.5%

### What steady voltage error does it leave?

::: misses
- [100/K] Exactly, $1/(1 + K_A)$.
- [any] $1/(1 + K_A)$.
:::
:::
:::

::: check
kind: parts
given: S = 100 | 500 | 900; f = 0.85 | 0.9 | 0.95

## A {S} MVA generator is rated to deliver its full apparent power at power factor {f}.

::: part
answer: S*f
unit: MW
tolerance: 0.5%

### What real power does that correspond to?

::: misses
- [any] S cos φ.
:::
:::

::: part
answer: S*sqrt(1 - f^2)
unit: Mvar
tolerance: 0.5%

### How many vars can it supply at that point?

::: misses
- [any] S sin φ.
:::
:::
:::

::: check
kind: parts
given: X = 1 | 1.5 | 2; V = 0.9 | 1 | 1.05

## A generator with $X_s$ = {X} pu runs at no load and {V} pu terminal voltage.

::: part
answer: V^2/X
tolerance: 0.5%

### How many vars can it absorb before the steady-state stability limit, with its field at zero?

::: misses
- [any] $V^2/X_s$.
:::
:::
:::

::: check
kind: choice

## Why does a generator's reactive capability fall when the terminal voltage sags?

- [ ] The field current rises automatically
- [x] Its armature limit is a current limit, so the apparent power it can deliver is proportional to the voltage, and its field limit's circle also shrinks with V; both bring the allowed vars down just when the grid needs more support
- [ ] The turbine slows
- [ ] Reactive power is independent of voltage

::: misses
- [1] The field is limited, not free to rise.
- [3] The turbine sets real power, not vars.
- [4] Both limits scale with V.
:::
:::

::: check
kind: derivation
vars: V = 0.9..1.1, X = 0.8..2.5, E = 1.5..3, P = 0..0.9

## A generator rated 1 pu with $X_s$ = X and field limit E runs at real power P and terminal voltage V.

::: step
answer: sqrt(V^2 - P^2)

### What vars does the armature limit allow?
:::

::: step
answer: -V^2/X + sqrt((E*V/X)^2 - P^2)

### What vars does the field limit allow?
:::

::: right
Right. Near unity power factor the armature binds; at low power factor, high excitation, the field does.
:::
:::

::: check
kind: python

## Write `q_limit(P, V, Xs, Emax, Imax)`: the most reactive power a generator can supply at real power P and terminal voltage V (the smaller of the armature and field limits), and `q_min(P, V, Xs, Xe)`: the steady-state stability limit's reactive power for connection through Xe to a stiff bus.

```python starter
def q_limit(P, V, Xs, Emax, Imax):
    return 0.0

def q_min(P, V, Xs, Xe):
    return 0.0
```

```python solution
import math

def q_limit(P, V, Xs, Emax, Imax):
    qa = math.sqrt((V * Imax) ** 2 - P * P)
    qf = -V * V / Xs + math.sqrt((Emax * V / Xs) ** 2 - P * P)
    return min(qa, qf)

def q_min(P, V, Xs, Xe):
    c = V * V / 2 * (1 / Xe - 1 / Xs)
    r = V * V / 2 * (1 / Xe + 1 / Xs)
    return c - math.sqrt(r * r - P * P)
```

```python tests
assert abs(q_limit(0.8, 1.0, 1.2, 2.2, 1.0) - 0.6) < 1e-12, "Armature-limited at 0.6 pu."
assert abs(q_limit(0.8, 0.95, 1.2, 2.2, 1.0) - 0.5123) < 1e-4, "Lower voltage, fewer vars."
assert abs(q_limit(0.2, 1.0, 1.2, 1.8, 1.0) - (-1 / 1.2 + (1.5 ** 2 - 0.04) ** 0.5)) < 1e-12, "With a weaker field at low power, the field limit binds."
assert abs(q_min(0.8, 1.0, 1.2, 0.3) + 0.6736) < 1e-4 and abs(q_min(0, 1.0, 1.2, 0.3) + 1 / 1.2) < 1e-12, "The stability limit: −0.674 at 0.8 pu, −V²/X_s at no load."
```

::: right
Right. A capability chart is just these circles and a turbine line, and the operating point must sit inside all of them.
:::
:::

::: explain
## Why do grid operators care about generators' reactive reserves, and not just their real power reserves?

::: model
Voltages across the network are held up by reactive power, and that support must come from sources close to where it's needed, because vars travel poorly over long, reactive lines. After a disturbance such as a line trip, the remaining network needs more reactive power, and generators supply it automatically through their voltage regulators until they reach their field or armature limits. A generator at its limit can no longer hold its voltage, which shifts the burden onto others and can cascade into voltage collapse. Tracking how far each machine is from its reactive limits tells operators how much voltage support is left in reserve, which real power reserves don't reveal.
:::
:::

::: practice
::: check
given: P = 0.6 | 0.9; V = 0.95 | 1.05
answer: sqrt(V^2 - P^2)
tolerance: 0.5%

## Armature-limited vars at P = {P}, V = {V} (rated 1 pu)?

::: misses
- [any] $\sqrt{V^2 - P^2}$.
:::
:::

::: check
given: a = 3 | 5; b = 5 | 8; Q = 40 | 90
answer: Q*b/(a + b)
unit: Mvar
tolerance: 0.5%

## Share of {Q} Mvar for droop {a}% against {b}%?

::: misses
- [any] Inverse to droop.
:::
:::

::: check
given: K = 20 | 30 | 50 | 100 | 150 | 200 | 400
answer: 100/(1 + K)
unit: %
tolerance: 0.5%

## AVR steady error with gain {K}?

::: misses
- [any] $1/(1 + K_A)$.
:::
:::
:::