title: Synchronous generators in the power system
heading: The round-rotor generator as an internal voltage behind synchronous reactance, how the turbine sets real power and the field sets reactive power, the steady-state limit, the capability curve, and the reactances used for faults
eyebrow: S10 · Lesson 25 · Synchronous generators in the power system
xp: 50
---

::: hook
A power plant operator has two controls: the turbine's steam or water valve and the generator's field current. Open the valve and the rotor advances a few degrees, pushing out more real power. Raise the field and the internal voltage rises, pushing out more reactive power and propping up the voltage of the surrounding grid. This lesson models the generator just well enough to see both effects, the limits on each, and the different reactances that matter in steady state and in the first cycles of a fault.
:::

::: play
- The phasor diagram of a round-rotor generator connected to a 1 pu bus: terminal voltage V, the drop $jX_sI$ across the synchronous reactance, and the internal voltage $E = V + jX_sI$.
- Raise P with Q fixed and E swings forward: the power angle δ grows. Raise Q with P fixed and E grows longer, nearly in line with V.
- Real power goes with δ and reactive power with |E|, the same decoupling as on a line (lesson 7), since the generator is a voltage behind a reactance.
:::

```sim plot
view: complex
range: 2.6
axes: Re, Im
slider: P = 0..1.2 = 0.8 pu
slider: Q = -0.6..0.8 = 0.6 pu
slider: X = 0.8..2 = 1.2 pu
arrow: 1 | label: V
arrow: X*Q + j*X*P | from: 1 | label: jXₛI
arrow: 1 + X*Q + j*X*P | color: ch3 | label: E
readout: |E|, pu = abs(1 + X*Q + j*X*P) | digits: 4
readout: power angle δ, ° = atan(X*P/(1 + X*Q))*180/pi | digits: 4
```

::: predict
## A generator with $X_s$ = 1.2 pu delivers 0.8 + j0.6 pu at 1 pu terminal voltage. The operator then lowers the field until Q = 0, keeping P at 0.8. What happens to the power angle?

- [ ] It stays at 29°: angle depends only on P
- [x] It rises from 29° to 44°
- [ ] It falls to about 15°
- [ ] The machine loses synchronism

::: reveal
With Q = 0.6, E = 1.72 + j0.96 (|E| = 1.97, δ = 29.2°). With Q = 0, E = 1 + j0.96 (|E| = 1.39, δ = 43.8°). Since $P = EV\sin\delta/X_s$, a smaller E needs a larger angle for the same power, leaving less margin before the 90° limit. Under-excited operation is less stable.
:::
:::

::: nameit
## The model

In steady state a round-rotor generator is an internal voltage E, set by the field current, behind the **synchronous reactance** $X_s$ (typically 1 to 2 pu on its own rating). With terminal voltage V and current I:

$$E = V + jX_sI, \qquad P = \frac{EV}{X_s}\sin\delta, \qquad Q = \frac{EV\cos\delta - V^2}{X_s}$$

δ, the **power angle**, is the angle by which E leads V.

## Controls

- **Turbine (governor)** sets mechanical power and so P and δ (lesson 30).
- **Field (exciter, with an automatic voltage regulator)** sets E and so Q: **over-excited** (E cos δ > V) the machine supplies vars; **under-excited** it absorbs them.

## Limits

- **Steady-state stability:** P can't exceed $EV/X_s$, at δ = 90°.
- **Capability curve** in the P–Q plane: the armature current limit is a circle of radius rated MVA about the origin; the field current limit is a circle centered at $(0, -V^2/X_s)$ with radius $E_\text{max}V/X_s$, which caps Q at high output; an under-excitation limit keeps δ and the core-end heating in check when absorbing vars; the turbine limits P.

## Reactances for faults

Right after a short circuit the field and damper windings resist changes in flux, so the machine looks like a voltage behind a much smaller reactance: **subtransient** X″ (0.1 to 0.25 pu) for the first few cycles, then **transient** X′ (0.2 to 0.4 pu), and finally $X_s$. Breaker duties use X″ (lesson 36); transient stability uses X′ (lesson 43).
:::

::: example
## Find E and δ for $X_s$ = 1.2 pu delivering 0.8 + j0.6 pu at 1 pu, and the steady-state limit at that excitation.

::: solution
1. **Armature current.**
   $$\begin{aligned} I &= (P - jQ)/V^* \\ &= 0.8 - j0.6 \end{aligned}$$
2. **Internal voltage.**
   $$\begin{aligned} E &= 1 + j1.2(0.8 - j0.6) \\ &= 1.72 + j0.96 \end{aligned}$$
   so |E| = 1.970 pu at δ = 29.2°.
3. **Check.**
   $$1.970\sin 29.2°/1.2 = 0.80$$
4. **Steady-state limit.** At this field current it's
   $$\begin{aligned} P_\max &= 1.970/1.2 \\ &= 1.64\ \text{pu} \end{aligned}$$
   about twice the present output.

**Answer:** E = 1.970 pu at δ = 29.2°, and the steady-state limit is 1.64 pu.
:::
:::

::: example
## With $E_\text{max}$ = 2.2 pu and $X_s$ = 1.2, how many vars can the machine supply at P = 0.8?

::: solution
1. **The field limit.**
   $$\begin{aligned} &(EV\cos\delta)^2 + (EV\sin\delta)^2 \\ &\quad = E^2V^2 \end{aligned}$$
   with $EV\sin\delta = PX_s$ = 0.96.
2. **The cosine term.**
   $$\begin{aligned} EV\cos\delta &= \sqrt{2.2^2 - 0.96^2} \\ &= 1.98 \end{aligned}$$
3. **Reactive power.**
   $$\begin{aligned} Q &= \frac{EV\cos\delta - V^2}{X_s} \\ &= 0.816\ \text{pu} \end{aligned}$$
4. **Beyond it.** Asking for more would overheat the field winding.

**Answer:** 0.816 pu.
:::
:::

::: example
## A generator with $X_s$ = 1.2 pu delivers 0.8 pu while absorbing 0.2 pu of vars at 1 pu terminal voltage. Find E, δ and how close it is to its steady-state limit.

::: solution
1. **Armature current.** With Q = −0.2:
   $$\begin{aligned} I &= (P - jQ)/V^* \\ &= 0.8 + j0.2 \end{aligned}$$
2. **Internal voltage.**
   $$\begin{aligned} E &= 1 + j1.2(0.8 + j0.2) \\ &= 0.76 + j0.96 \end{aligned}$$
   so |E| = 1.22 pu at δ = 51.6°.
3. **Steady-state limit.**
   $$\begin{aligned} P_\max &= EV/X_s \\ &= 1.02\ \text{pu} \end{aligned}$$
   only 28% above the 0.8 pu being delivered.
4. **Why it matters.** Running underexcited lowers E, raises δ and eats the stability margin, which is why the capability curve has an underexcitation limit.

**Answer:** E = 1.22 pu at δ = 51.6°, with a limit of 1.02 pu, only 28% above its output.
:::
:::

::: check
given: X = 0.9 | 1.2 | 1.8; P = 0.5 | 0.9; Q = -0.2 | 0.3 | 0.6
answer: sqrt((1 + X*Q)^2 + (X*P)^2)
tolerance: 0.5%

## A generator with $X_s$ = {X} pu delivers {P} + j({Q}) pu at 1 pu. What's its internal voltage magnitude?

::: right
Right. $|1 + X_sQ + jX_sP|$ = {answer} pu.
:::

::: misses
- [sqrt((1 - X*Q)^2 + (X*P)^2)] With $I = P - jQ$, $jX_sI = X_sQ + jX_sP$: Q adds to the real part.
- [any] Not yet. $E = V + jX_sI$.
:::
:::

::: check
given: X = 0.9 | 1.2 | 1.8; P = 0.5 | 0.9; Q = -0.2 | 0.3 | 0.6
answer: atan(X*P/(1 + X*Q))*180/pi
unit: °
tolerance: 0.5%

## For the same machine, what's the power angle?

::: right
Right. $\tan^{-1}\frac{X_sP}{1 + X_sQ}$ = {answer}°.
:::

::: misses
- [any] Not yet. The angle of E.
:::
:::

::: check
given: E = 1.3 | 1.8 | 2.2; X = 1 | 1.6; d = 15 | 30 | 50
answer: E*sin(d*pi/180)/X
tolerance: 0.5%

## A generator with E = {E} pu behind $X_s$ = {X} pu runs at δ = {d}° on a 1 pu bus. How much real power does it deliver?

::: right
Right. $EV\sin\delta/X_s$ = {answer} pu.
:::

::: misses
- [E*cos(d*pi/180)/X] Real power goes with sin δ.
- [any] Not yet. $P = EV\sin\delta/X_s$.
:::
:::

::: check
given: E = 1.3 | 1.8 | 2.2; X = 1 | 1.6; d = 15 | 30 | 50
answer: (E*cos(d*pi/180) - 1)/X
tolerance: 0.5%

## And how much reactive power?

::: right
Right. $(EV\cos\delta - V^2)/X_s$ = {answer} pu.
:::

::: misses
- [(E - 1)/X] Use $E\cos\delta$.
- [any] Not yet. $Q = (EV\cos\delta - V^2)/X_s$.
:::
:::

::: check
given: E = 1.2 | 1.6 | 2.4; X = 0.8 | 1.5
answer: E/X
tolerance: 0.5%

## What's the steady-state power limit of a generator with E = {E} pu behind $X_s$ = {X} pu on an infinite 1 pu bus?

::: right
Right. $EV/X_s$ = {answer} pu, at δ = 90°.
:::

::: misses
- [E*X] Divide by the reactance.
- [any] Not yet. Maximize $EV\sin\delta/X_s$.
:::
:::

::: check
given: E = 1.8 | 2.4; X = 1 | 1.5; P = 0.4 | 0.9
answer: (sqrt(E^2 - (P*X)^2) - 1)/X
tolerance: 0.5%

## A generator's field limits E to {E} pu, with $X_s$ = {X} pu, on a 1 pu bus. What's the most reactive power it can supply at P = {P}?

::: right
Right. $(\sqrt{E^2 - (PX_s)^2} - V)V/X_s$ = {answer} pu.
:::

::: misses
- [(E - 1)/X] At nonzero P part of E is spent on the power angle.
- [any] Not yet. Use $E\cos\delta = \sqrt{E^2 - (PX_s)^2}$.
:::
:::

::: check
kind: parts
given: X = 0.9 | 1.2 | 1.8; P = 0.5 | 0.8; Q = -0.3 | -0.1 | 0.4

## A generator with $X_s$ = {X} pu delivers {P} pu and {Q} pu of vars at 1 pu.

::: part
answer: sqrt((1 + X*Q)^2 + (X*P)^2)
tolerance: 0.5%

### What is |E|?

::: misses
- [any] $E = V + jX_sI$ with $I = P - jQ$.
:::
:::

::: part
answer: atan(X*P/(1 + X*Q))*180/pi
unit: °
tolerance: 0.5%

### What is δ?

::: misses
- [any] The angle of $1 + X_sQ + jX_sP$.
:::
:::
:::

::: check
kind: derivation
vars: E = 0.8..2.5, X = 0.5..2.5, d = 0..1.3

## A generator with internal voltage E behind $X_s$ = X runs at power angle d on a 1 pu bus.

::: step
answer: E/X*sin(d)

### What real power does it deliver?
:::

::: step
answer: (E*cos(d) - 1)/X

### What reactive power?
:::

::: step
answer: E/X

### What's its steady-state limit at this excitation?
:::

::: right
Right. Excitation sets the limit; the turbine sets how close to it the machine runs.
:::
:::

::: explain
## Why does raising a generator's field current increase its reactive output but barely change its real output?

::: model
Real power is set by the turbine: in steady state the electrical output must equal the mechanical input, or the rotor would speed up or slow down. Raising the field increases the internal voltage E, and since $P = EV\sin\delta/X_s$ must stay the same, the power angle shrinks a little to compensate. Meanwhile the reactive output, $(EV\cos\delta - V^2)/X_s$, rises substantially because E cos δ grows. The extra internal voltage drives current nearly in phase with the drop across the synchronous reactance, which is 90° from the terminal voltage, so it shows up as vars. That's why the exciter is the generator's voltage control and the governor its power control.
:::
:::

::: practice

::: check
given: X = 1 | 1.5; P = 0.3 | 1; Q = 0 | 0.5
answer: sqrt((1 + X*Q)^2 + (X*P)^2)
tolerance: 0.5%

## |E| for $X_s$ = {X}, {P} + j{Q}?

::: misses
- [any] $|1 + X_sQ + jX_sP|$.
:::
:::

::: check
given: E = 1.5 | 2; X = 1.1 | 1.7; d = 20 | 40
answer: E*sin(d*pi/180)/X
tolerance: 0.5%

## P for E = {E}, $X_s$ = {X}, δ = {d}°?

::: misses
- [any] $E\sin\delta/X_s$.
:::
:::

::: check
given: E = 1.4 | 2.2; X = 0.9 | 1.8
answer: E/X
tolerance: 0.5%

## Steady-state limit: E = {E}, $X_s$ = {X}?

::: misses
- [any] $E/X_s$.
:::
:::
:::