title: Line ampacity and sag
heading: How much current a line can carry: the conductor's heat balance of resistive and solar heating against convection and radiation, why wind matters so much, and how heating lengthens a span and lowers its sag toward the ground
eyebrow: S10 · Lesson 13 · Line ampacity and sag
xp: 50
---

::: hook
Short lines are limited not by stability or voltage but by heat. Current warms the conductor, sunshine adds more, and the breeze and radiation carry it away. Too hot, and the aluminum anneals and loses strength; long before that, the conductor expands, the span sags, and the line comes too close to the trees or the ground beneath it. A line's rating is the current that keeps it within a temperature limit under assumed weather, and since the weather is rarely that bad, utilities are learning to rate lines by the actual wind.
:::

::: play
- The curve is a Drake ACSR conductor's ampacity (28.1 mm diameter, 0.087 Ω/km at 75 °C) at a 75 °C limit in 25 °C air with full sun, against the convective heat-transfer coefficient h set by the wind.
- In still air (h near 5 W/m²K) it carries under 600 A; in a steady breeze (h = 15) about 890 A; at h = 30, about 1250 A.
- The rating depends far more on the wind than on anything about the conductor, which is why static ratings assume a cautious, light wind.
:::

```sim plot
view: graph
x: h = 3..40
y: I = 0..1600
plot: sqrt((h*pi*0.0281*50 + 0.5*5.67e-8*pi*0.0281*(348.15^4 - 298.15^4) - 0.5*1000*0.0281)/8.7e-5) | label: ampacity, A
```

::: predict
## A line's static rating assumes a light breeze. On a day with twice the convective cooling, about how much more current can it carry at the same temperature?

- [ ] Twice as much
- [x] About 40% more
- [ ] About 10% more
- [ ] None: the rating is fixed by the conductor

::: reveal
Current enters the heat balance squared: $I^2R = q_c + q_r - q_s$. Doubling the convective term, which is most of the cooling, raises the right side by about 1.96 times for the Drake example, and the current by its square root: 1.40 times. Dynamic line ratings that measure the wind routinely find 20 to 50% more capacity than the static rating.
:::
:::

::: nameit
## The heat balance

In steady state, per meter of conductor with diameter D at temperature $T_c$ in air at $T_a$:
$$I^2R(T_c) + q_s = q_c + q_r$$
- **Resistive heating** with the AC resistance at the conductor temperature (aluminum's rises about 0.4% per °C).
- **Solar heating** $q_s = \alpha SD$, with absorptivity α and irradiance S.
- **Convective cooling** $q_c = h\pi D(T_c - T_a)$, with h of 5 to 10 W/m²K in still air and several times that in a breeze.
- **Radiative cooling** $q_r = \epsilon\sigma\pi D(T_c^4 - T_a^4)$, temperatures in kelvin.

So the **ampacity** at a temperature limit is
$$I = \sqrt{\frac{q_c + q_r - q_s}{R(T_c)}}$$
Real ratings (IEEE 738, CIGRE) compute h from wind speed and direction. The conductor's heat capacity gives a thermal time constant of 10 to 20 minutes, which lets operators run above the steady rating for short emergencies.

## Sag

A span L with conductor weight w per meter and horizontal tension H hangs nearly as a parabola, with midspan sag and conductor length
$$d = \frac{wL^2}{8H}, \qquad S = L + \frac{8d^2}{3L}$$
Heating lengthens the conductor by $\alpha_tS\,\Delta T$ ($\alpha_t \approx 19 \times 10^{-6}$ per °C for ACSR), and the sag follows from the length: $d = \sqrt{3L(S - L)/8}$. Because S − L is small, a fraction of a meter of extra length adds meters of sag. Ignoring the conductor's elastic stretch gives an upper estimate; the tension falls as it sags, and the true increase is somewhat less.
:::

::: example
## Find the ampacity of Drake ACSR (D = 28.1 mm, R = 0.087 Ω/km at 75 °C) at 75 °C in 25 °C air, with h = 15 W/m²K, ε = α = 0.5 and 1000 W/m² of sun.

::: solution
1. **Convective cooling.**
   $$\begin{aligned} q_c &= 15\pi(0.0281)(50) \\ &= 66.2\ \text{W/m} \end{aligned}$$
2. **Radiative cooling.**
   $$\begin{aligned} q_r &= 0.5\sigma\pi(0.0281) \\ &\quad \times (348.15^4 - 298.15^4) \\ &= 17.0\ \text{W/m} \end{aligned}$$
3. **Solar heating.**
   $$\begin{aligned} q_s &= 0.5 \times 1000 \times 0.0281 \\ &= 14.1\ \text{W/m} \end{aligned}$$
4. **Ampacity.** The $I^2R$ heating, with R = 8.7 × 10⁻⁵ Ω/m, balances the net cooling:
   $$\begin{aligned} I &= \sqrt{(q_c + q_r - q_s)/R} \\ &= 892\ \text{A} \end{aligned}$$
5. **What does the work.** Convection does most of the work; radiation helps a little and the sun takes some back.

**Answer:** about 892 A.
:::
:::

::: example
## A 300 m span of conductor weighing 15.97 N/m hangs at 28 kN horizontal tension. How much does its sag grow if the conductor heats by 50 °C, ignoring elastic stretch?

::: solution
1. **Sag now.**
   $$\begin{aligned} d &= \frac{15.97 \times 300^2}{8 \times 28\,000} \\ &= 6.42\ \text{m} \end{aligned}$$
2. **Conductor length.**
   $$\begin{aligned} S &= 300 + 8(6.42)^2/900 \\ &= 300.366\ \text{m} \end{aligned}$$
3. **Thermal stretch.** Heating adds
   $$\begin{aligned} \Delta S &= 19 \times 10^{-6} \times 50 \times 300.37 \\ &= 0.285\ \text{m} \end{aligned}$$
   so S − L = 0.651 m.
4. **New sag.**
   $$\begin{aligned} d &= \sqrt{3 \times 300 \times 0.651/8} \\ &= 8.56\ \text{m} \end{aligned}$$
5. **Compare.** That's 2.1 m more sag from a stretch of only 9.5 cm per 100 m.

**Answer:** the sag grows by 2.1 m, from 6.42 m to 8.56 m.
:::
:::

::: example
## On a day when the breeze doubles h to 30 W/m²K, what can the Drake conductor carry at the same 75 °C?

::: solution
1. **Convection doubles.** $q_c$ doubles to 132.4 W/m.
2. **New ampacity.**
   $$\begin{aligned} I &= \sqrt{\frac{132.4 + 17.0 - 14.1}{8.7 \times 10^{-5}}} \\ &= 1247\ \text{A} \end{aligned}$$
   40% more.
3. **Why ratings vary.** The same conductor in still air would be good for less than two-thirds of its breezy rating, which is why a single static number is a compromise.

**Answer:** 1247 A, 40% more than at h = 15 W/m²K.
:::
:::

::: check
kind: parts
given: D = 20 | 28.1 | 40; R = 0.05 | 0.087 | 0.15; h = 8 | 15 | 30; T = 50 | 75 | 100

## A conductor of diameter {D} mm with {R} Ω/km at its {T} °C limit sits in 25 °C air with h = {h} W/m²K, ε = α = 0.5 and 1000 W/m² of sun.

::: part
answer: h*pi*D*1e-3*(T - 25) + 0.5*5.67e-8*pi*D*1e-3*((T + 273.15)^4 - 298.15^4) - 0.5*1000*D*1e-3
unit: W/m
tolerance: 0.5%

### What net cooling is available per meter at the limit?

::: misses
- [h*pi*D*1e-3*(T - 25)] Include radiation, and subtract the sun.
- [any] $q_c + q_r - q_s$.
:::
:::

::: part
answer: sqrt((h*pi*D*1e-3*(T - 25) + 0.5*5.67e-8*pi*D*1e-3*((T + 273.15)^4 - 298.15^4) - 0.5*1000*D*1e-3)/(R*1e-3))
unit: A
tolerance: 0.5%

### What is its ampacity?

::: misses
- [any] $\sqrt{(q_c + q_r - q_s)/R}$ with R in Ω/m.
:::
:::
:::

::: check
kind: parts
given: w = 8 | 16 | 25; L = 150 | 300 | 450; H = 15 | 30 | 50

## A span of {L} m has conductor weighing {w} N/m at a horizontal tension of {H} kN.

::: part
answer: w*L^2/(8*H*1e3)
unit: m
tolerance: 0.5%

### What is its sag?

::: misses
- [w*L^2/(2*H*1e3)] The parabola's sag has 8 in the denominator.
- [any] $wL^2/8H$.
:::
:::

::: part
answer: 8*(w*L^2/(8*H*1e3))^2/(3*L)*100
unit: cm
tolerance: 0.5%

### How much longer than the span is the conductor?

::: misses
- [any] $8d^2/3L$.
:::
:::
:::

::: check
kind: parts
given: L = 200 | 300 | 400; d = 4 | 6 | 9; t = 30 | 50 | 80

## A span of {L} m sags {d} m. Its ACSR conductor ($\alpha_t$ = 19 × 10⁻⁶ per °C) heats by {t} °C; ignore elastic stretch.

::: part
answer: 19e-6*t*(L + 8*d^2/(3*L))*100
unit: cm
tolerance: 0.5%

### How much longer does it get?

::: misses
- [any] $\alpha_tS\Delta T$.
:::
:::

::: part
answer: sqrt(3*L*(8*d^2/(3*L) + 19e-6*t*(L + 8*d^2/(3*L)))/8)
unit: m
tolerance: 0.5%

### What is the new sag?

::: misses
- [d*(1 + 19e-6*t)] The sag grows far faster than the length.
- [any] $\sqrt{3L(S - L)/8}$.
:::
:::
:::

::: check
kind: parts
given: c = 50 | 70; r = 10 | 20; s = 10 | 15; k = 1.5 | 2 | 3

## A conductor at its limit loses {c} W/m by convection and {r} W/m by radiation and gains {s} W/m from the sun. The wind then multiplies convection by {k}.

::: part
answer: sqrt((k*c + r - s)/(c + r - s))
tolerance: 0.5%

### By what factor does its ampacity rise?

::: misses
- [k] Current goes as the square root of the net cooling.
- [any] $\sqrt{(kq_c + q_r - q_s)/(q_c + q_r - q_s)}$.
:::
:::
:::

::: check
kind: parts
given: R = 0.06 | 0.1; a = 0.0039 | 0.004; T = 50 | 100

## A conductor's resistance is {R} Ω/km at 20 °C, rising {a} per °C.

::: part
answer: R*(1 + a*(T - 20))
unit: Ω/km
tolerance: 0.5%

### What is it at {T} °C?

::: misses
- [any] $R_{20}(1 + \alpha(T - 20))$.
:::
:::
:::

::: check
kind: parts
given: m = 1.0 | 1.6 | 2.5; c = 900 | 1000; G = 2 | 4

## A conductor has {m} kg/m of mass with specific heat {c} J/kg·K, and its net cooling rises {G} W/m per kelvin near its operating point.

::: part
answer: m*c/G/60
unit: min
tolerance: 0.5%

### What is its thermal time constant?

::: misses
- [m*c/G] That's in seconds.
- [any] Heat capacity per meter over the cooling slope.
:::
:::
:::

::: check
kind: choice

## Why does a line's sag, rather than the conductor's own temperature limit, often set its rating?

- [ ] Hot conductors break immediately
- [x] Thermal expansion adds conductor length, and because sag grows with the square root of the excess length over the span, a small stretch lowers the midspan by meters, so the clearance to the ground or vegetation is reached before the conductor itself is damaged
- [ ] Sag reduces the conductor's resistance
- [ ] Sag only matters in winter

::: misses
- [1] Annealing takes hours at high temperatures.
- [3] Sag doesn't change resistance.
- [4] Sag is worst when the conductor is hottest, usually in summer.
:::
:::

::: check
kind: derivation
vars: w = 5..30, L = 100..600, H = 10000..60000, a = 0.00001..0.00003, t = 0..100

## A span L (m) has conductor weight w (N/m) at tension H (N); the conductor then heats by t with expansion coefficient a.

::: step
answer: w*L^2/(8*H)

### What is the sag?
:::

::: step
answer: L + 8*(w*L^2/(8*H))^2/(3*L) + a*t*(L + 8*(w*L^2/(8*H))^2/(3*L)) - L

### What is S − L after heating?
:::

::: step
answer: sqrt(3*L*(L + 8*(w*L^2/(8*H))^2/(3*L) + a*t*(L + 8*(w*L^2/(8*H))^2/(3*L)) - L)/8)

### What is the new sag?
:::

::: right
Right. The parabola links sag and excess length through $S - L = 8d^2/3L$, both ways.
:::
:::

::: check
kind: python

## Write `ampacity(D, R, h, Tc, Ta, eps, alpha, S)` from the heat balance (D in m, R in Ω/m at Tc, temperatures in °C), and `conductor_temp(I, D, R20, a, h, Ta, eps, alpha, S)`: the steady temperature for current I with $R = R_{20}(1 + a(T - 20))$, by bisection between Ta and 300 °C.

```python starter
def ampacity(D, R, h, Tc, Ta, eps, alpha, S):
    return 0.0

def conductor_temp(I, D, R20, a, h, Ta, eps, alpha, S):
    return Ta
```

```python solution
import math
SIG = 5.67e-8

def ampacity(D, R, h, Tc, Ta, eps, alpha, S):
    qc = h * math.pi * D * (Tc - Ta)
    qr = eps * SIG * math.pi * D * ((Tc + 273.15) ** 4 - (Ta + 273.15) ** 4)
    qs = alpha * S * D
    return math.sqrt((qc + qr - qs) / R)

def conductor_temp(I, D, R20, a, h, Ta, eps, alpha, S):
    def excess(T):
        heat = I * I * R20 * (1 + a * (T - 20)) + alpha * S * D
        cool = h * math.pi * D * (T - Ta) + eps * SIG * math.pi * D * ((T + 273.15) ** 4 - (Ta + 273.15) ** 4)
        return heat - cool
    lo, hi = Ta, 300.0
    for _ in range(100):
        mid = (lo + hi) / 2
        if excess(mid) > 0:
            lo = mid
        else:
            hi = mid
    return lo
```

```python tests
I = ampacity(0.0281, 8.7e-5, 15, 75, 25, 0.5, 0.5, 1000)
assert abs(I - 891.5) < 1, "Drake at 75 °C: about 892 A."
R20 = 8.7e-5 / (1 + 0.004 * 55)
T = conductor_temp(I, 0.0281, R20, 0.004, 15, 25, 0.5, 0.5, 1000)
assert abs(T - 75) < 0.01, "At its ampacity the conductor sits at its limit."
assert conductor_temp(0.8 * I, 0.0281, R20, 0.004, 15, 25, 0.5, 0.5, 1000) < 60, "At 80% of rating it runs much cooler."
```

::: right
Right. Because heating goes as the current squared, 80% of the rating gives well under 80% of the temperature rise.
:::
:::

::: explain
## Why are dynamic line ratings able to unlock so much transmission capacity?

::: model
A static rating assumes cautious weather, typically a light wind, high air temperature and full sun, so that the conductor stays below its temperature and sag limits nearly all the time. Most of the time the actual weather is more favorable, and convective cooling grows strongly with wind speed, so the current that keeps the conductor at its limit is often 20 to 50% higher than the static number. Measuring the conductor's temperature, tension or sag, or the local wind, lets operators use that real headroom safely, which can relieve congestion without building new lines.
:::
:::

::: practice
::: check
given: w = 10 | 20; L = 200 | 350; H = 20 | 40
answer: w*L^2/(8*H*1e3)
unit: m
tolerance: 0.5%

## Sag: {w} N/m, span {L} m, tension {H} kN?

::: misses
- [any] $wL^2/8H$.
:::
:::

::: check
given: c = 40 | 80; r = 15; s = 12; k = 2 | 3
answer: sqrt((k*c + r - s)/(c + r - s))
tolerance: 0.5%

## Ampacity factor when convection {c} W/m rises {k}-fold (radiation {r}, sun {s})?

::: misses
- [any] Square root of the cooling ratio.
:::
:::

::: check
given: R = 0.07 | 0.12; T = 75 | 90
answer: R*(1 + 0.004*(T - 20))
unit: Ω/km
tolerance: 0.5%

## Resistance at {T} °C if {R} Ω/km at 20 °C, 0.004 per °C?

::: misses
- [any] $R_{20}(1 + 0.004(T - 20))$.
:::
:::
:::