title: Transmission line models
heading: Short, medium and long line models, ABCD parameters, the propagation constant and wavelength at 60 Hz, the Ferranti rise of an open line, charging vars, and how a line's receiving voltage depends on its loading relative to SIL
eyebrow: S10 · Lesson 6 · Transmission line models
xp: 50
---

::: hook
At 60 Hz a wavelength is about 5000 km, so most power lines are electrically short and a lumped model works. But even a 200 km line has enough capacitance that, left open at the far end, its voltage there rises above the sending end: the Ferranti effect, which once surprised the engineers of London's first high-voltage cables. This lesson builds the models of increasing accuracy that power-flow programs use for lines, and shows how a line's voltage profile depends on whether it's loaded above or below its natural loading.
:::

::: play
- The receiving-end voltage of a lossless line held at 1 pu at the sending end, against line length, for a resistive load given as a multiple k of the surge impedance loading.
- At k = 1 (natural loading) the voltage stays at 1 pu at every length: the line's own vars balance.
- Lighter loads let the voltage rise with length (k = 0 is the open line's Ferranti rise); heavier loads make it sag.
:::

```sim plot
view: graph
x: l = 0..1200 km
y: V = 0..2 pu
slider: k = 0..2 = 0.5
plot: 1/sqrt(cos(2*pi*l/4940)^2 + k^2*sin(2*pi*l/4940)^2) | samples: 400 | label: receiving-end voltage
plot: 1 + 0*l | dashed | color: ch3 | label: 1 pu
readout: power delivered, in multiples of SIL, at 300 km = k/(cos(2*pi*300/4940)^2 + k^2*sin(2*pi*300/4940)^2) | digits: 3
```

::: predict
## The 345 kV line of lesson 4 is 200 km long and open at the far end. If the sending end is held at 345 kV, what's the receiving-end voltage?

- [ ] 345 kV: no current, no drop
- [x] About 356 kV
- [ ] About 330 kV
- [ ] About 690 kV

::: reveal
With no load, $V_R = V_S/A$ and $A = \cos\beta l$ for a lossless line. Here βl = 0.0729°/km × 200 km = 14.6°, so $V_R = V_S/\cos 14.6°$ = 1.033 × 345 = 356 kV. The line's capacitive charging current flows through its own inductance and raises the voltage along the way.
:::
:::

::: nameit
## ABCD parameters

Every line model relates sending-end and receiving-end voltage and current as

$$\begin{pmatrix} V_S \\ I_S \end{pmatrix} = \begin{pmatrix} A & B \\ C & D \end{pmatrix}\begin{pmatrix} V_R \\ I_R \end{pmatrix}$$

with total series impedance Z = zl and shunt admittance Y = yl:

- **Short line** (under about 80 km): A = D = 1, B = Z, C = 0.
- **Medium line, nominal π** (80 to 250 km): half of Y at each end. $A = D = 1 + ZY/2$, B = Z, $C = Y(1 + ZY/4)$.
- **Long line**: distributed, with propagation constant $\gamma = \sqrt{zy}$ and $Z_c = \sqrt{z/y}$: $A = D = \cosh\gamma l$, $B = Z_c\sinh\gamma l$, $C = \sinh(\gamma l)/Z_c$.

## Lossless lines

γ = jβ with $\beta = \omega\sqrt{LC}$, about 0.073°/km at 60 Hz (wavelength near 4940 km for overhead lines). Then $A = \cos\beta l$ and $B = jZ_c\sin\beta l$.

- **Open line (Ferranti effect):** $V_R = V_S/\cos\beta l$, 3.3% up at 200 km, 7.7% at 300 km, 38% at 600 km.
- **Charging:** the line generates $V^2B_\text{total}$ vars from its capacitance, about 0.53 Mvar per km for the 345 kV line.
- **Loaded with resistance:** if the load draws k times SIL at 1 pu, $V_R = V_S/\sqrt{\cos^2\beta l + k^2\sin^2\beta l}$, flat at k = 1.

## Regulation

$(|V_{R,\text{no load}}| - |V_{R,\text{full load}}|)/|V_{R,\text{full load}}|$, where the no-load value is $|V_S|/|A|$.
:::

::: example
## A 69 kV line 30 km long has z = 0.17 + j0.45 Ω/km and delivers 20 MW at 0.9 lagging at 69 kV. What sending voltage does it need?

::: solution
1. **Use the short-line model.** Per phase, the receiving voltage and the series impedance are
   $$\begin{aligned} V_R &= 39.84\ \text{kV} \\ Z &= 5.1 + j13.5\ \Omega \end{aligned}$$
2. **Line current.**
   $$\begin{aligned} I &= \frac{20 \times 10^6}{3 \times 39\,840 \times 0.9} \\ &= 185.9\ \text{A} \end{aligned}$$
   at −25.8°.
3. **Sending voltage.**
   $$\begin{aligned} V_S &= V_R + ZI \\ &= 41.83\angle 2.53°\ \text{kV} \end{aligned}$$
   or 72.44 kV line to line.
4. **Compare the ends.** The sending end must be 5.0% higher than the receiving end.

**Answer:** 72.44 kV line to line (41.83 kV per phase at 2.53°), 5.0% above the receiving voltage.
:::
:::

::: example
## Find the nominal-π A constant of the 200 km, 345 kV line (z = 0.03 + j0.363 Ω/km, y = j4.455 µS/km).

::: solution
1. **Totals for the line.**
   $$\begin{aligned} Z &= 6 + j72.6\ \Omega \\ Y &= j891\ \mu\text{S} \end{aligned}$$
2. **Half the ZY product.**
   $$\begin{aligned} \frac{ZY}{2} &= \frac{(6 + j72.6)(j891 \times 10^{-6})}{2} \\ &= -0.0323 + j0.0027 \end{aligned}$$
3. **The A constant.**
   $$\begin{aligned} A &= 1 + ZY/2 \\ &= 0.9677 + j0.0027 \end{aligned}$$
   and |A| = 0.9677.
4. **No-load voltage rise.**
   $$\begin{aligned} V_R &= V_S/|A| \\ &= 1.0334\,V_S \end{aligned}$$
   matching the lossless long-line estimate of 1.0333.
5. **Line charging.** The line generates
   $$\begin{aligned} Q &= 345^2 \times 891\ \mu\text{S} \\ &= 106\ \text{Mvar} \end{aligned}$$

**Answer:** A = 0.9677 + j0.0027, so an open line's far end rises to 1.0334 times the sending voltage; the line generates 106 Mvar.
:::
:::

::: example
## A lossless line is 500 km long (wavelength 4940 km). Compare its exact A constant with the nominal π's, and the open-circuit voltage rise each predicts.

::: solution
1. **Electrical length.**
   $$\begin{aligned} \beta l &= 2\pi \times 500/4940 \\ &= 0.636\ \text{rad} \end{aligned}$$
   which is 36.4°.
2. **Exact A constant.**
   $$\begin{aligned} A &= \cos\beta l \\ &= 0.805 \end{aligned}$$
   so an open line's far end rises to 1/0.805 = 1.243 times the sending voltage.
3. **Nominal-π A constant.**
   $$\begin{aligned} A &= 1 + ZY/2 \\ &= 1 - (\beta l)^2/2 \\ &= 0.798 \end{aligned}$$
   which predicts a rise of 1.253.
4. **Compare.** The two are close at this length, and the nominal π grows increasingly wrong beyond it.

**Answer:** exactly, A = 0.805 and the far end rises to 1.243 times the sending voltage; the nominal π gives A = 0.798 and a rise of 1.253.
:::
:::

::: check
given: l = 150 | 300 | 500 | 800
answer: 1/cos(2*pi*l/4940)
tolerance: 0.5%

## An open overhead line {l} km long (wavelength 4940 km). What's its receiving-end voltage relative to the sending end?

::: right
Right. $1/\cos\beta l$ = {answer}.
:::

::: misses
- [cos(2*pi*l/4940)] The far end rises: divide by the cosine.
- [any] Not yet. $V_R = V_S/A$ with $A = \cos\beta l$.
:::
:::

::: check
given: L = 0.85 | 1.1 | 1.3; C = 9 | 11 | 13
answer: 2*pi*60*sqrt(L*1e-3*C*1e-9)*180/pi
unit: °
tolerance: 0.5%

## A lossless line has L = {L} mH/km and C = {C} nF/km. What's its phase constant per km at 60 Hz?

::: right
Right. $\omega\sqrt{LC}$ = {answer}° per km.
:::

::: misses
- [2*pi*60*sqrt(L*1e-3*C*1e-9)] That's in radians.
- [any] Not yet. $\beta = \omega\sqrt{LC}$.
:::
:::

::: check
given: V = 138 | 345 | 500; B = 3 | 4.5 | 6; l = 50 | 200
answer: V^2*B*1e-6*l
unit: Mvar
tolerance: 0.5%

## A {V} kV line with B = {B} µS/km is {l} km long. About how many vars does its capacitance generate at rated voltage?

::: right
Right. $V^2Bl$ = {answer} Mvar.
:::

::: misses
- [V^2*B*1e-6*l/3] With line-to-line voltage, $V_L^2B$ already counts all three phases.
- [any] Not yet. $Q = V^2B_\text{total}$.
:::
:::

::: check
given: x = 0.3 | 0.5; b = 3 | 5; l = 100 | 250
answer: 1 - x*b*l^2*1e-6/2
tolerance: 0.5%

## A lossless line with x = {x} Ω/km and b = {b} µS/km is {l} km long. What's its nominal-π A constant?

::: right
Right. $1 + ZY/2 = 1 - x b l^2/2$ = {answer}.
:::

::: misses
- [any] Not yet. $A = 1 + ZY/2$.
:::
:::

::: check
given: l = 200 | 400 | 600; k = 0.5 | 1.5
answer: 1/sqrt(cos(2*pi*l/4940)^2 + k^2*sin(2*pi*l/4940)^2)
tolerance: 0.5%

## A lossless {l} km line (wavelength 4940 km) carries a resistive load of {k} times its SIL. What's the receiving voltage in per unit of the sending voltage?

::: right
Right. $1/\sqrt{\cos^2\beta l + k^2\sin^2\beta l}$ = {answer}.
:::

::: misses
- [any] Not yet. Use $V_S = V_R(\cos\beta l + jk\sin\beta l)$.
:::
:::

::: check
given: V = 34.5 | 69; R = 1 | 3; X = 3 | 8; P = 5 | 20
answer: 100*(sqrt((V*1e3/sqrt(3) + (R*P*1e6/(3*V*1e3/sqrt(3)) ))^2 + (X*P*1e6/(3*V*1e3/sqrt(3)))^2)/(V*1e3/sqrt(3)) - 1)
unit: %
tolerance: 0.5%

## A short line with Z = {R} + j{X} Ω delivers {P} MW at unity power factor and {V} kV. How much higher must the sending voltage be?

::: right
Right. Add ZI to $V_R$ per phase: {answer}% higher.
:::

::: misses
- [any] Not yet. $V_S = V_R + ZI$ with I in phase with $V_R$.
:::
:::

::: check
kind: parts
given: l = 200 | 400 | 600

## A lossless overhead line is {l} km long (wavelength 4940 km).

::: part
answer: cos(2*pi*l/4940)
tolerance: 0.5%

### What is its exact A constant?

::: misses
- [any] $\cos\beta l$.
:::
:::

::: part
answer: 1 - (2*pi*l/4940)^2/2
tolerance: 0.5%

### What does the nominal π give?

::: misses
- [any] $1 + ZY/2 = 1 - (\beta l)^2/2$.
:::
:::

::: part
answer: 1/cos(2*pi*l/4940)
tolerance: 0.5%

### How far does the open far end rise, as a multiple of the sending voltage?

::: misses
- [any] 1/A.
:::
:::
:::

::: check
kind: derivation
vars: R = 0.1..50, X = 0.5..200, P = 1..500, Q = -200..200, V = 10..800

## A short line (R + jX ohms) delivers P MW and Q Mvar at V kV.

::: step
answer: (R*P + X*Q)/V

### About how many kV does the voltage drop along the line?
:::

::: step
answer: (P^2 + Q^2)*R/V^2

### How many MW does it lose?
:::

::: right
Right. Real power drops voltage through R and reactive power through X, and X is usually the larger: that's why voltage follows vars.
:::
:::

::: explain
## Why does an open-ended line's voltage rise along its length?

::: model
Even with nothing connected at the far end, the line's shunt capacitance draws a charging current that leads the voltage by 90°. That current flows through the line's series inductance, and the voltage across an inductance carrying a leading current points opposite to the source voltage's direction of drop: it adds to the voltage instead of subtracting. Each section of the line therefore raises the voltage a little more, so the far end ends up highest. At 60 Hz this is a few percent on a 200 km line and grows quickly with length, which is why long lines carry shunt reactors that absorb the charging vars when lightly loaded.
:::
:::

::: practice

::: check
given: l = 100 | 400 | 700
answer: 1/cos(2*pi*l/4940)
tolerance: 0.5%

## Ferranti rise of a {l} km open line?

::: misses
- [any] $1/\cos\beta l$.
:::
:::

::: check
given: V = 230 | 765; B = 3.5 | 5; l = 80 | 300
answer: V^2*B*1e-6*l
unit: Mvar
tolerance: 0.5%

## Charging vars: {V} kV, {B} µS/km, {l} km?

::: misses
- [any] $V^2Bl$.
:::
:::

::: check
given: L = 0.9 | 1.2; C = 10 | 12
answer: 360/(2*pi*60*sqrt(L*1e-3*C*1e-9)*180/pi)
unit: km
tolerance: 0.5%

## Wavelength at 60 Hz for L = {L} mH/km, C = {C} nF/km?

::: misses
- [any] $2\pi/\beta$.
:::
:::
:::