title: Transmission line parameters
heading: Series resistance, inductance from geometric mean radius and distance, transposition, bundled conductors, shunt capacitance, and the surge impedance and surge impedance loading that follow from them
eyebrow: S10 · Lesson 4 · Transmission line parameters
xp: 50
---

::: hook
An overhead line is three bare conductors hung meters apart in air, and its behavior is set almost entirely by geometry. The magnetic flux between the conductors gives the line its series inductance, the electric field gives it shunt capacitance, and both depend only logarithmically on spacing and conductor size. That's why lines from 69 to 765 kV all have reactances within a factor of two of each other, and why splitting each phase into a bundle of conductors is the main lever designers have.
:::

::: play
- A three-phase line's inductance and capacitance per kilometer against the geometric mean spacing between phases, for a chosen conductor radius.
- Both depend on the logarithm of spacing over size: doubling the spacing raises L by only 0.14 mH/km.
- Bundling acts like a much fatter conductor, cutting L and raising C, which lowers the surge impedance and raises how much power the line carries naturally.
:::

```sim plot
view: graph
x: D = 2..20 m log
y: v = 0..20
slider: r = 5..80 = 14.07 mm log
plot: 0.2*ln(D/(0.7788*r/1000))*10 | samples: 400 | label: L, in 0.1 mH/km
plot: 55.63/ln(D/(r/1000)) | samples: 400 | color: ch3 | label: C, nF/km
readout: surge impedance at 8.82 m, Ω = sqrt(0.2e-3*ln(8.82/(0.7788*r/1000))/(55.63e-12*1000/ln(8.82/(r/1000)))) | digits: 4
```

::: predict
## A 345 kV line's single conductors (radius 14 mm) are replaced by two-conductor bundles 45 cm apart. What happens to the series reactance?

- [ ] It halves, since two conductors share the current
- [x] It falls by about 28%
- [ ] It's unchanged; only resistance falls
- [ ] It rises, because there are more conductors

::: reveal
Inductance depends on $\ln(D_m/D_s)$. The bundle's effective GMR is $\sqrt{D_sd} = \sqrt{0.01137 \times 0.45}$ = 71.5 mm instead of 11.4 mm, and with $D_m$ = 8.82 m the logarithm drops from 6.65 to 4.81: X falls from 0.502 to 0.363 Ω/km, 28%. Bundling also reduces corona at high voltage.
:::
:::

::: nameit
## Resistance

$R = \rho l/A$ at DC, raised a few percent by skin effect at 60 Hz and by temperature (aluminum: about 0.4% per °C).

## Inductance

For a transposed three-phase line (each phase takes each position for a third of the length):

$$L = 2 \times 10^{-7}\ln\frac{D_m}{D_s}\ \text{H/m}, \qquad D_m = \sqrt[3]{D_{12}D_{23}D_{31}}$$

$D_m$ is the **geometric mean distance** between phases and $D_s$ the conductor's **geometric mean radius**: $re^{-1/4}$ = 0.7788r for a solid round conductor, and listed in tables for stranded ones.

## Bundles

n conductors on a circle, spacing d, act like one with GMR $\sqrt{D_sd}$ (two), $\sqrt[3]{D_sd^2}$ (three) or $1.091\sqrt[4]{D_sd^3}$ (four).

## Capacitance

$$C = \frac{2\pi\varepsilon_0}{\ln(D_m/r)} = \frac{55.63}{\ln(D_m/r)}\ \text{pF/m (to neutral)}$$

with the outer radius r (or $\sqrt{rd}$ for a two-conductor bundle, and so on).

## Surge impedance and SIL

A lossless line has $Z_c = \sqrt{L/C}$, typically 250 to 400 Ω for overhead lines and 30 to 60 Ω for cables. Loaded with $Z_c$, a line neither absorbs nor produces net vars: its **surge impedance loading** is $\text{SIL} = V_L^2/Z_c$.
:::

::: example
## A 345 kV line has phases in a flat row 7 m apart, two-conductor bundles 0.45 m apart, and conductors of radius 14.07 mm and GMR 11.37 mm. Find its parameters.

::: solution
1. **Mean phase spacing.**
   $$\begin{aligned} D_m &= \sqrt[3]{7 \times 7 \times 14} \\ &= 8.82\ \text{m} \end{aligned}$$
2. **Inductance.** The bundle's GMR is $\sqrt{0.01137 \times 0.45}$ = 71.5 mm, so
   $$\begin{aligned} L &= 0.2 \ln(8.82/0.0715) \\ &= 0.963\ \text{mH/km} \end{aligned}$$
   and X = 0.363 Ω/km at 60 Hz.
3. **Capacitance.** For capacitance the bundle radius is $\sqrt{0.01407 \times 0.45}$ = 79.6 mm, so
   $$\begin{aligned} C &= \frac{55.63}{\ln(8.82/0.0796)} \\ &= 11.8\ \text{nF/km} \end{aligned}$$
   and B = 4.45 µS/km.
4. **Surge impedance and SIL.**
   $$\begin{aligned} Z_c &= \sqrt{L/C} \\ &= 285\ \Omega \\ \text{SIL} &= 345^2/285 \\ &= 417\ \text{MW} \end{aligned}$$

**Answer:** L = 0.963 mH/km (X = 0.363 Ω/km), C = 11.8 nF/km (B = 4.45 µS/km), $Z_c$ = 285 Ω and SIL = 417 MW.
:::
:::

::: example
## What would the same line be with single conductors?

::: solution
1. **Inductance.**
   $$\begin{aligned} L &= 0.2 \ln(8.82/0.01137) \\ &= 1.33\ \text{mH/km} \end{aligned}$$
   which is 0.502 Ω/km.
2. **Capacitance.**
   $$\begin{aligned} C &= \frac{55.63}{\ln(8.82/0.01407)} \\ &= 8.64\ \text{nF/km} \end{aligned}$$
3. **Surge impedance and SIL.** These come to $Z_c$ = 393 Ω and SIL = 303 MW.
4. **Compare with the bundle.** The bundle raises the natural loading by 38% on the same towers.

**Answer:** L = 1.33 mH/km (0.502 Ω/km), C = 8.64 nF/km, $Z_c$ = 393 Ω and SIL = 303 MW; the bundled line's SIL is 38% higher.
:::
:::

::: example
## A 500 kV line has a geometric mean distance of 12 m, and its bundles have an effective GMR of 0.15 m and an effective radius of 0.17 m. Find L, C, the surge impedance and the SIL.

::: solution
1. **Inductance.**
   $$\begin{aligned} L &= 2 \times 10^{-7}\ln(12/0.15) \\ &= 0.876\ \text{mH/km} \end{aligned}$$
2. **Capacitance.**
   $$\begin{aligned} C &= \frac{2\pi\epsilon_0}{\ln(12/0.17)} \\ &= 13.07\ \text{nF/km} \end{aligned}$$
3. **Surge impedance.**
   $$\begin{aligned} Z_c &= \sqrt{L/C} \\ &= 259\ \Omega \end{aligned}$$
4. **Surge impedance loading.**
   $$\begin{aligned} \text{SIL} &= 500^2/259 \\ &= 965\ \text{MW} \end{aligned}$$
5. **Why bundles help.** Bundling lowers L and raises C together, which is how extra-high-voltage lines reach SILs near 1000 MW.

**Answer:** L = 0.876 mH/km, C = 13.07 nF/km, $Z_c$ = 259 Ω and SIL = 965 MW.
:::
:::

::: check
given: a = 4 | 7 | 10; b = 5 | 8; c = 9 | 15
answer: (a*b*c)^(1/3)
unit: m
tolerance: 0.5%

## Phase spacings are {a}, {b} and {c} m. What's the geometric mean distance?

::: right
Right. $\sqrt[3]{D_{12}D_{23}D_{31}}$ = {answer} m.
:::

::: misses
- [any] Not yet. The cube root of the product.
:::
:::

::: check
given: D = 4 | 8 | 12; s = 8 | 12 | 30
answer: 0.2*ln(D/(s/1000))
unit: mH
tolerance: 0.5%

## A transposed line has $D_m$ = {D} m and conductor GMR {s} mm. What's its inductance per kilometer?

::: right
Right. $0.2\ln(D_m/D_s)$ = {answer} mH per km.
:::

::: misses
- [0.2*log(D/(s/1000))] Use the natural logarithm.
- [any] Not yet. $L = 2 \times 10^{-7}\ln(D_m/D_s)$ H/m.
:::
:::

::: check
given: s = 8 | 12; d = 0.3 | 0.45 | 0.6
answer: sqrt(s*d*1000)
unit: mm
tolerance: 0.5%

## A two-conductor bundle uses conductors of GMR {s} mm spaced {d} m. What's its effective GMR?

::: right
Right. $\sqrt{D_sd}$ = {answer} mm.
:::

::: misses
- [s*d*1000/2] It's the geometric mean of $D_s$ and d.
- [any] Not yet. $\sqrt{D_sd}$.
:::
:::

::: check
given: D = 4 | 9 | 14; r = 10 | 15 | 40
answer: 55.63/ln(D/(r/1000))
unit: nF
tolerance: 0.5%

## A line has $D_m$ = {D} m and conductor radius {r} mm. What's its capacitance to neutral per kilometer?

::: right
Right. $55.63/\ln(D_m/r)$ = {answer} nF per km.
:::

::: misses
- [55.63/ln(D/(0.7788*r/1000))] Capacitance uses the outer radius, not the GMR.
- [any] Not yet. $C = 2\pi\varepsilon_0/\ln(D_m/r)$.
:::
:::

::: check
given: L = 0.8 | 1.0 | 1.3; C = 9 | 12 | 14; V = 230 | 500
answer: V^2/sqrt(L*1e-3/(C*1e-9))
unit: MW
tolerance: 0.5%

## A {V} kV line has L = {L} mH/km and C = {C} nF/km. What's its surge impedance loading?

::: right
Right. $Z_c = \sqrt{L/C}$, then $V^2/Z_c$ = {answer} MW.
:::

::: misses
- [V^2/(L*1e-3/(C*1e-9))] Take the square root for $Z_c$.
- [any] Not yet. SIL = $V_L^2/Z_c$.
:::
:::

::: check
given: D = 5 | 10; r = 10 | 20
answer: 2*pi*60*0.2e-3*ln(D/(0.7788*r/1000))
unit: Ω
tolerance: 0.5%

## A line of solid round conductors, radius {r} mm, has $D_m$ = {D} m. What's its 60 Hz series reactance per km?

::: right
Right. GMR = 0.7788r, then $\omega L$ = {answer} Ω per km.
:::

::: misses
- [2*pi*60*0.2e-3*ln(D/(r/1000))] For inductance use the GMR, $re^{-1/4}$.
- [any] Not yet. $X = 2\pi f \times 0.2\ln(D_m/D_s)$ mΩ per m.
:::
:::

::: check
kind: parts
given: D = 7 | 12 | 16; s = 0.1 | 0.15 | 0.2; r = 0.12 | 0.18

## A line has a geometric mean distance of {D} m, effective bundle GMR {s} m and effective radius {r} m, at 500 kV.

::: part
answer: 2e-7*ln(D/s)*1e6
unit: mH/km
tolerance: 0.5%

### What is its inductance per kilometer?

::: misses
- [any] $2 \times 10^{-7}\ln(D_m/D_s)$ H/m.
:::
:::

::: part
answer: sqrt(2e-7*ln(D/s)/(2*pi*8.854e-12/ln(D/r)))
unit: Ω
tolerance: 0.5%

### What is its surge impedance?

::: misses
- [any] $\sqrt{L/C}$ with $C = 2\pi\epsilon_0/\ln(D_m/r)$.
:::
:::

::: part
answer: 500^2/sqrt(2e-7*ln(D/s)/(2*pi*8.854e-12/ln(D/r)))
unit: MW
tolerance: 0.5%

### What is its SIL?

::: misses
- [any] $V^2/Z_c$.
:::
:::
:::

::: check
kind: derivation
vars: D = 1..20, s = 0.005..0.3, r = 0.006..0.4

## A transposed line has GMD D, GMR s and radius r, all in meters.

::: step
answer: 2e-7*ln(D/s)

### What is L per meter?
:::

::: step
answer: 2*pi*8.854e-12/ln(D/r)

### What is C per meter?
:::

::: step
answer: 1/sqrt(2e-7*ln(D/s)*2*pi*8.854e-12/ln(D/r))

### What is the wave speed?
:::

::: right
Right. With s close to r, the speed is close to that of light, as it must be for a line in air.
:::
:::

::: explain
## Why do transmission lines of very different voltages have similar reactances per kilometer?

::: model
A line's inductance and capacitance depend on the logarithm of the spacing between phases divided by the conductor size. Higher-voltage lines need more spacing for insulation, but they also use bigger conductors and bundles, so the ratio changes far less than either dimension does, and its logarithm changes less still. A tenfold change in the ratio only changes the logarithm by 2.3. As a result series reactance stays near 0.3 to 0.5 Ω/km across voltage classes, while the surge impedance loading, which goes as the voltage squared, rises steeply. That's why higher voltage, not different line design, is how utilities move more power.
:::
:::

::: practice

::: check
given: a = 3 | 6; b = 6 | 10; c = 8 | 18
answer: (a*b*c)^(1/3)
unit: m
tolerance: 0.5%

## GMD for spacings {a}, {b}, {c} m?

::: misses
- [any] $\sqrt[3]{D_{12}D_{23}D_{31}}$.
:::
:::

::: check
given: D = 6 | 15; s = 10 | 60
answer: 0.2*ln(D/(s/1000))
unit: mH
tolerance: 0.5%

## L per km for $D_m$ = {D} m, $D_s$ = {s} mm?

::: misses
- [any] $0.2\ln(D_m/D_s)$.
:::
:::

::: check
given: D = 5 | 12; r = 12 | 70
answer: 55.63/ln(D/(r/1000))
unit: nF
tolerance: 0.5%

## C per km for $D_m$ = {D} m, r = {r} mm?

::: misses
- [any] $55.63/\ln(D_m/r)$.
:::
:::
:::