title: Midterm exam
heading: "Midterm exam: power system modeling and power flow"
eyebrow: S10 · Midterm exam
type: problems
---

::: hook
Twelve problems from the first half of the course: three-phase and complex power, per unit, transformers, line parameters, ampacity and models, power transfer, voltage stability and compensation, surges, network matrices and their reduction, power flow by Gauss–Seidel, Newton–Raphson and the DC approximation, and contingency analysis. Give yourself two hours and work without the lessons open. "Another set" deals a different exam.
:::

::: pool
pick: 12

::: check
kind: parts
given: P = 60 | 250; V = 138 | 230; f = 0.8 | 0.9; b = 0.95 | 0.98

## A {P} MW load at {f} power factor lagging is served at {V} kV.

::: part
answer: P*1e6/(sqrt(3)*V*1e3*f)
unit: A
tolerance: 0.5%

### Line current?

::: misses
- [any] $P/(\sqrt{3}V_L\cos\phi)$.
:::
:::

::: part
answer: P*(tan(acos(f)) - tan(acos(b)))
unit: Mvar
tolerance: 0.5%

### Capacitor to reach {b}?

::: misses
- [any] $P(\tan\phi_1 - \tan\phi_2)$.
:::
:::
:::

::: check
kind: parts
given: X = 0.1 | 0.25; a = 40 | 300; b = 13.2 | 22; c = 13.8 | 24; Z = 40 | 150; V = 230 | 345

## A machine ({a} MVA, {b} kV, X = {X} pu) and a {V} kV line of j{Z} Ω, on 100 MVA with {c} kV on the machine's side.

::: part
answer: X*(b/c)^2*(100/a)
tolerance: 0.5%

### Machine's X?

::: misses
- [any] Change of base.
:::
:::

::: part
answer: Z/(V^2/100)
tolerance: 0.5%

### Line's X?

::: misses
- [any] $Z/Z_\text{base}$.
:::
:::

::: part
answer: 1/(X*(b/c)^2*(100/a) + Z/(V^2/100))*100e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Current on the line for a bolted fault at its far end (1 pu source)?

::: misses
- [any] 1 over the total, times $I_\text{base}$.
:::
:::
:::

::: check
kind: parts
given: V = 400 | 700; I = 4 | 10; P = 200 | 600; r = 0.008 | 0.015; x = 0.06 | 0.1; f = 0.8 | 0.9

## A short-circuit test reads {V} V, {I} A, {P} W; and a transformer with R = {r}, X = {x} pu at full load, {f} lagging.

::: part
answer: sqrt((V/I)^2 - (P/I^2)^2)
unit: Ω
tolerance: 0.5%

### Leakage reactance from the test?

::: misses
- [any] $\sqrt{Z^2 - R^2}$.
:::
:::

::: part
answer: 100*(sqrt((1 + r*f + x*sqrt(1 - f^2))^2 + (x*f - r*sqrt(1 - f^2))^2) - 1)
unit: %
tolerance: 0.5%

### Regulation of the second transformer?

::: misses
- [any] $|1 + IZ| - 1$.
:::
:::
:::

::: check
kind: parts
given: a = 6 | 9; b = 7 | 10; c = 12 | 18; s = 10 | 13; d = 0.4 | 0.5; r = 13 | 16

## Phases spaced {a}, {b}, {c} m; two-conductor bundles {d} m apart; conductor GMR {s} mm, radius {r} mm.

::: part
answer: 0.2*ln((a*b*c)^(1/3)/sqrt(s/1000*d))
unit: mH
tolerance: 0.5%

### L per km?

::: misses
- [any] $0.2\ln(D_m/\sqrt{D_sd})$.
:::
:::

::: part
answer: 55.63/ln((a*b*c)^(1/3)/sqrt(r/1000*d))
unit: nF
tolerance: 0.5%

### C per km?

::: misses
- [any] $55.63/\ln(D_m/\sqrt{rd})$.
:::
:::
:::

::: check
kind: parts
given: L = 0.9 | 1.2; C = 10 | 12.5; V = 345 | 500; l = 250 | 500

## A {V} kV line with L = {L} mH/km and C = {C} nF/km, {l} km long.

::: part
answer: V^2/sqrt(L*1e-3/(C*1e-9))
unit: MW
tolerance: 0.5%

### SIL?

::: misses
- [any] $V^2/Z_c$.
:::
:::

::: part
answer: 1/cos(2*pi*60*sqrt(L*1e-3*C*1e-9)*l)
tolerance: 0.5%

### Open-end voltage rise?

::: misses
- [any] $1/\cos\beta l$.
:::
:::
:::

::: check
kind: parts
given: V = 0.98 | 1.03; W = 0.96 | 1; X = 0.2 | 0.35; d = 10 | 28

## Buses at {V} and {W} pu, {d}° apart, across X = {X} pu.

::: part
answer: V*W*sin(d*pi/180)/X
tolerance: 0.5%

### Real power?

::: misses
- [any] $V_1V_2\sin\delta/X$.
:::
:::

::: part
answer: (V^2 - V*W*cos(d*pi/180))/X
tolerance: 0.5%

### Reactive power leaving bus 1?

::: misses
- [any] $(V_1^2 - V_1V_2\cos\delta)/X$.
:::
:::
:::

::: check
kind: parts
given: X = 0.2 | 0.4; P = 0.4 | 0.9

## A 1 pu source feeds a unity-pf load of {P} pu through X = {X} pu.

::: part
answer: sqrt((1 + sqrt(1 - 4*X^2*P^2))/2)
tolerance: 0.5%

### Load voltage?

::: misses
- [any] Upper root.
:::
:::

::: part
answer: 1/(2*X)
tolerance: 0.5%

### Maximum deliverable?

::: misses
- [any] $1/2X$.
:::
:::
:::

::: check
kind: parts
given: X = 0.35 | 0.6; k = 0.3 | 0.5; Q = 40 | 120; V = 0.85 | 0.92

## A line of X = {X} pu with {k} series compensation; a {Q} Mvar capacitor at {V} pu.

::: part
answer: 1/(X*(1 - k))
tolerance: 0.5%

### Transfer limit between 1 pu buses?

::: misses
- [any] $1/(X(1 - k))$.
:::
:::

::: part
answer: Q*V^2
unit: Mvar
tolerance: 0.5%

### Capacitor output?

::: misses
- [any] $QV^2$.
:::
:::
:::

::: check
kind: parts
given: g = 0.15 | 0.25; p = 0.1 | 0.2; q = 0.1 | 0.15; x = 0.2 | 0.35; B = 0.1 | 0.4

## Generator j\given{g} at bus 1; bus 3 fed directly by j\given{p} and via bus 2 by j\given{q} + j\given{x}; the j\given{p} line has total charging {B} pu.

::: part
answer: g + p*(q + x)/(p + q + x)
tolerance: 0.5%

### $Z_{33}$?

::: misses
- [any] Series–parallel reduction.
:::
:::

::: part
answer: 1/p - B/2
tolerance: 0.5%

### Net susceptance the j\given{p} line adds to bus 3's diagonal?

::: misses
- [any] $1/x - B/2$.
:::
:::
:::

::: check
kind: parts
given: n = 118 | 2000; f = 0.1 | 0.2; let m = round(n*f); X = 0.15 | 0.25; P = 0.5 | 1

## A {n}-bus case with {m} PV buses; and a two-bus case with X = {X} and a {P} pu load.

::: part
answer: 2*(n - 1) - m
tolerance: 0

### Unknowns in the first?

::: misses
- [any] $2(n - 1) - n_{PV}$.
:::
:::

::: part
answer: -P*X*180/pi
unit: °
tolerance: 0.5%

### Angle after Newton's first step in the second?

::: misses
- [any] $-PX$.
:::
:::
:::

::: check
kind: parts
given: X = 0.15 | 0.3; P = 0.5 | 1; Q = 0.2 | 0.4

## Two-bus: X = {X}, load {P} + j{Q}, flat start.

::: part
answer: sqrt((1 - X*Q)^2 + (X*P)^2)
tolerance: 0.5%

### First Gauss–Seidel iterate's magnitude?

::: misses
- [any] $|(1 - XQ) - jXP|$.
:::
:::

::: part
answer: sqrt(((1 - 2*Q*X) + sqrt((1 - 2*Q*X)^2 - 4*X^2*(P^2 + Q^2)))/2)
tolerance: 0.5%

### Converged magnitude?

::: misses
- [any] Upper root.
:::
:::
:::

::: check
kind: parts
given: a = 0.1 | 0.2; b = 0.15 | 0.25; c = 0.12 | 0.35; T = 80 | 250

## A triangle with $x_{12}$ = {a}, $x_{23}$ = {b}, $x_{13}$ = {c} pu carrying {T} MW from bus 1 to bus 3.

::: part
answer: T*(a + b)/(a + b + c)
unit: MW
tolerance: 0.5%

### Flow on line 1–3?

::: misses
- [any] Inverse-reactance share.
:::
:::

::: part
answer: T/100*c*(a)/(a + b + c)*180/pi
unit: °
tolerance: 0.5%

### Angle drop across line 1–2 (100 MVA base)?

::: misses
- [any] Flow on 1–2 in pu times $x_{12}$.
:::
:::
:::

::: check
kind: parts
given: s = 100 | 200 | 400; Z = 300 | 400; l = 150 | 300; u = 290 | 295

## A stiff 1 pu source closes, through a resistance of {s} Ω, onto an unloaded lossless line {l} km long with $Z_c$ = {Z} Ω and wave speed {u} km/ms.

::: part
answer: Z/(s + Z)
tolerance: 0.5%

### Size of the first wave launched, in per unit?

::: misses
- [any] The source resistance and $Z_c$ divide the step.
:::
:::

::: part
answer: l/u
unit: ms
tolerance: 0.5%

### When does it reach the far end?

::: misses
- [any] Length over speed.
:::
:::

::: part
answer: 2*Z/(s + Z)
tolerance: 0.5%

### Far-end voltage just after it arrives, in per unit?

::: misses
- [any] The open end doubles the arriving wave.
:::
:::

::: part
answer: 2*Z/(s + Z)*(1 + (s - Z)/(s + Z))
tolerance: 0.5%

### Far-end voltage after the second arrival, at three travel times, in per unit?

::: misses
- [any] The reflection returns, reflects at the source with $\rho_s = (R_s - Z_c)/(R_s + Z_c)$, and doubles again at the open end; add it to the first step.
:::
:::
:::

::: check
kind: parts
given: f = 0.5 | 0.8; g = 0.7 | 1; p = 0.2 | 0.35; k = 0.55 | 0.75; a = 0.3 | 0.5

## Line ℓ carries {f} pu and line k carries {g} pu. Line k carries {k} of any transfer between its own ends, and line ℓ carries {p} of it. A generator's shift factor on line ℓ is −{a} with line k in service (100 MVA base).

::: part
answer: p/(1 - k)
tolerance: 0.5%

### Line ℓ's outage distribution factor for line k?

::: misses
- [any] $\text{PTDF}_\ell/(1 - \text{PTDF}_k)$.
:::
:::

::: part
answer: 100*(f + p/(1 - k)*g)
unit: MW
tolerance: 0.5%

### Line ℓ's flow after line k trips?

::: misses
- [any] $f_\ell + d_{\ell k}f_k$.
:::
:::

::: part
answer: 100*(f + p/(1 - k)*g - 0.8)/a
unit: MW
tolerance: 0.5%

### Line ℓ is rated 80 MW. Ignoring the outage's effect on the shift factor, how much must that generator raise its output beforehand to keep line ℓ within its rating after the outage?

::: misses
- [any] The post-outage overload divided by the shift factor's magnitude.
:::
:::
:::

::: check
kind: parts
given: D = 22 | 30; R = 0.07 | 0.12; h = 12 | 25

## A conductor of {D} mm with {R} Ω/km at 75 °C sits in 25 °C air with h = {h} W/m²K, ε = α = 0.5 and 1000 W/m² of sun.

::: part
answer: sqrt((h*pi*D*1e-3*50 + 0.5*5.67e-8*pi*D*1e-3*(348.15^4 - 298.15^4) - 0.5*1000*D*1e-3)/(R*1e-3))
unit: A
tolerance: 0.5%

### What is its 75 °C ampacity?

::: misses
- [any] $\sqrt{(q_c + q_r - q_s)/R}$.
:::
:::
:::

::: check
kind: parts
given: X = 0.2 | 0.3; f = 0.9 | 0.95; P = 0.6 | 0.9

## A 1 pu source feeds {P} pu at power factor {f} lagging through X = {X} pu.

::: part
answer: (f/(2*X*(1 + sqrt(1 - f^2)))/P - 1)*100
unit: %
tolerance: 0.5%

### What is the loadability margin?

::: misses
- [any] $(P_\max - P)/P$.
:::
:::
:::
:::