title: The per-unit system
heading: Choosing power and voltage bases, base current and impedance, converting impedances between bases, why per-unit values pass straight through transformers, and solving a generator-transformer-line circuit in per unit
eyebrow: S10 · Lesson 2 · The per-unit system
xp: 50
---

::: hook
A power system mixes 13.8 kV generators, 345 kV lines and 480 V motors, so the same fault current is thousands of amperes on one side of a transformer and hundreds on the other. Engineers sidestep the bookkeeping by expressing every quantity as a fraction of a chosen base. In per unit, transformers vanish from the circuit, the impedances of machines of very different sizes fall in narrow, familiar ranges, and mistakes stand out: a generator reactance of 15 pu is obviously wrong. Every later lesson works in per unit.
:::

::: play
- The base impedance $Z_\text{base} = V_\text{base}^2/S_\text{base}$ against the base voltage, for a chosen power base.
- On a 100 MVA base it's 1.9 Ω at 13.8 kV and 1190 Ω at 345 kV. A per-unit impedance is the ohmic value divided by the base at its own voltage level.
- That's why a 345 kV line of 200 Ω and a generator of 0.38 Ω can both be about 0.17 to 0.2 pu.
:::

```sim plot
view: graph
x: V = 0.4..800 kV log
y: Z = 0.001..10000 Ω log
slider: S = 1..1000 = 100 MVA log
plot: V^2/S | samples: 400 | label: base impedance
point: 13.8, 13.8^2/S | label: 13.8 kV
point: 345, 345^2/S | label: 345 kV
readout: base current at 345 kV, A = S*1e6/(sqrt(3)*345e3) | digits: 4
```

::: predict
## A generator's nameplate says X'' = 0.2 pu on its own 50 MVA, 13.8 kV rating. What is it on a 100 MVA, 13.8 kV system base?

- [ ] 0.1 pu
- [x] 0.4 pu
- [ ] 0.2 pu
- [ ] 0.8 pu

::: reveal
The base impedance is $V^2/S$, so doubling the power base halves it, and the same ohms become twice as many per-unit: $0.2 \times (100/50)$ = 0.4 pu. Equipment ratings and the system base rarely match, so this conversion is the first step of every study.
:::
:::

::: nameit
## Bases

Choose a three-phase power base $S_\text{base}$ (MVA, one value for the whole system) and a line-to-line voltage base $V_\text{base}$ (kV) in one zone. Then

$$I_\text{base} = \frac{S_\text{base}}{\sqrt{3}V_\text{base}}, \qquad Z_\text{base} = \frac{V_\text{base}^2}{S_\text{base}}$$

and any quantity in per unit is its actual value divided by its base.

## Across transformers

Each transformer's rated voltages set the voltage bases on its two sides, in the ratio of its turns. With bases chosen this way, a transformer's per-unit impedance is the same seen from either side, and the ideal transformer becomes 1:1: it disappears from the per-unit circuit.

## Changing base

Equipment data come on the equipment's own rating. To move to the system base:

$$Z_\text{new} = Z_\text{old}\left(\frac{V_\text{old}}{V_\text{new}}\right)^2\frac{S_\text{new}}{S_\text{old}}$$

## Typical values (on own rating)

Generator subtransient reactance 0.1 to 0.3 pu, transformer leakage reactance 0.05 to 0.15 pu, and a line's series impedance a few tenths of a per unit on 100 MVA at its voltage for a long line.
:::

::: example
## A 13.8 kV generator (X'' = 0.4 pu on 100 MVA) feeds a 13.8/345 kV transformer (X = 0.1 pu) and a 345 kV line of 40 + j200 Ω. Find the current for a three-phase short at the line's far end.

::: solution
1. **Line in per unit.** On 100 MVA the 345 kV base impedance is
   $$\begin{aligned} Z_\text{base} &= 345^2/100 \\ &= 1190.25\ \Omega \end{aligned}$$
   so the line is 0.0336 + j0.168 pu.
2. **Total impedance.** Adding the generator's j0.4 and the transformer's j0.1:
   $$\begin{aligned} Z &= 0.0336 + j0.668 \\ |Z| &= 0.669\ \text{pu} \end{aligned}$$
3. **Fault current in per unit.** With the generator's internal voltage at 1 pu:
   $$\begin{aligned} I_f &= 1/0.669 \\ &= 1.495\ \text{pu} \end{aligned}$$
4. **Line side in amperes.** On the 345 kV side, $I_\text{base}$ = 167.3 A:
   $$\begin{aligned} I &= 1.495 \times 167.3 \\ &= 250\ \text{A} \end{aligned}$$
5. **Generator side in amperes.** On the generator side, $I_\text{base}$ = 4,184 A:
   $$\begin{aligned} I &= 1.495 \times 4184 \\ &= 6.25\ \text{kA} \end{aligned}$$
   One per-unit current, two very different amperes.

**Answer:** 1.495 pu, which is 250 A on the 345 kV line and 6.25 kA in the generator.
:::
:::

::: example
## A 25 MVA transformer has X = 0.08 pu on its rating at 13.2 kV. What is it on 100 MVA and 13.8 kV?

::: solution
1. **Change both bases.**
   $$\begin{aligned} X &= 0.08 \left(\frac{13.2}{13.8}\right)^2 \frac{100}{25} \\ &= 0.293\ \text{pu} \end{aligned}$$
2. **What each correction does.** Both corrections matter: the larger power base quadruples it, and the slightly higher voltage base trims it by 8.5%.

**Answer:** 0.293 pu.
:::
:::

::: example
## A 10 MW induction motor at 0.85 power factor runs at its rated 4.16 kV. On a 100 MVA base, what is its current in per unit, and in amperes?

::: solution
1. **Apparent power.**
   $$\begin{aligned} S &= 10/0.85 \\ &= 11.76\ \text{MVA} \\ &= 0.1176\ \text{pu} \end{aligned}$$
   on 100 MVA.
2. **Per-unit current.** At 1 pu voltage the per-unit current equals the per-unit apparent power: 0.1176 pu.
3. **Base current at 4.16 kV.**
   $$\begin{aligned} I_\text{base} &= \frac{100 \times 10^6}{\sqrt3 \times 4160} \\ &= 13\,880\ \text{A} \end{aligned}$$
4. **Current in amperes.**
   $$\begin{aligned} I &= I_\text{pu}I_\text{base} \\ &= 1633\ \text{A} \end{aligned}$$
5. **Check.** Computing it directly gives the same:
   $$\begin{aligned} I &= \frac{S}{\sqrt3 \times 4160\ \text{V}} \\ &= 1633\ \text{A} \end{aligned}$$

**Answer:** 0.1176 pu, which is 1633 A.
:::
:::

::: check
given: V = 0.48 | 13.8 | 138 | 500; S = 10 | 100
answer: V^2/S
unit: Ω
tolerance: 0.5%

## What's the base impedance at {V} kV on a {S} MVA base?

::: right
Right. $V^2/S$ = {answer} Ω.
:::

::: misses
- [V^2/(3*S)] The three-phase power base with line-to-line voltage gives $V^2/S$ directly.
- [V/S] Square the voltage.
- [any] Not yet. $Z_\text{base} = V_\text{base}^2/S_\text{base}$.
:::
:::

::: check
given: V = 4.16 | 34.5 | 230; S = 10 | 100
answer: S*1e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

## What's the base current at {V} kV on {S} MVA?

::: right
Right. $S/(\sqrt{3}V)$ = {answer} A.
:::

::: misses
- [S*1e6/(V*1e3)] Include $\sqrt{3}$.
- [any] Not yet. $I_\text{base} = S_\text{base}/(\sqrt{3}V_\text{base})$.
:::
:::

::: check
given: X = 0.06 | 0.15 | 0.25; a = 25 | 50 | 200; b = 12.5 | 13.2; c = 13.8 | 14.4
answer: X*(b/c)^2*(100/a)
tolerance: 0.5%

## Equipment rated {a} MVA at {b} kV has X = {X} pu on its rating. What is it on 100 MVA at {c} kV?

::: right
Right. $X(V_\text{old}/V_\text{new})^2(S_\text{new}/S_\text{old})$ = {answer} pu.
:::

::: misses
- [X*100/a] Correct for the voltage base too.
- [X*(c/b)^2*(100/a)] The voltage ratio is old over new.
- [any] Not yet. Convert to ohms and back.
:::
:::

::: check
given: Z = 5 | 40 | 120; V = 115 | 230 | 345
answer: Z/(V^2/100)
tolerance: 0.5%

## A {V} kV line has a series reactance of {Z} Ω. What is it in per unit on 100 MVA?

::: right
Right. $Z/Z_\text{base}$ = {answer} pu.
:::

::: misses
- [Z*(V^2/100)] Divide by the base, don't multiply.
- [any] Not yet. $Z_\text{base} = V^2/S$.
:::
:::

::: check
given: X = 0.05 | 0.1; V = 4.16 | 13.8; W = 69 | 138
answer: X*W^2/100
unit: Ω
tolerance: 0.5%

## A {V}/{W} kV transformer has X = {X} pu on 100 MVA. How many ohms is that seen from the {W} kV side?

::: right
Right. The per-unit value is the same on both sides; in ohms, multiply by the base impedance on the {W} kV side: {answer} Ω.
:::

::: misses
- [X*V^2/100] That's the reactance seen from the low-voltage side.
- [any] Not yet. Use the base impedance on the side you're asked about.
:::
:::

::: check
given: X = 0.3 | 0.6 | 1.2; V = 13.8 | 138
answer: 1/X*100e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

## A source of 1 pu behind a total of {X} pu (100 MVA base) is shorted. What's the current in kA at {V} kV?

::: right
Right. 1/{X} pu times $I_\text{base}$ = {answer} kA.
:::

::: misses
- [X*100e6/(sqrt(3)*V*1e3)/1000] The per-unit current is $1/X$, not X.
- [any] Not yet. $I_{pu} = E/X$, then multiply by $I_\text{base}$.
:::
:::

::: check
kind: parts
given: P = 2 | 10 | 50; f = 0.8 | 0.9; V = 4.16 | 13.8 | 69

## A load takes {P} MW at power factor {f} and its rated {V} kV. Work on a 100 MVA base.

::: part
answer: P/f/100
tolerance: 0.5%

### What is its current in per unit, at 1 pu voltage?

::: misses
- [P/100] Per-unit current equals per-unit apparent power, not real power.
- [any] S/S_base at 1 pu voltage.
:::
:::

::: part
answer: P/f/100*100e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

### What is that in amperes?

::: misses
- [any] Multiply by $I_\text{base} = S_\text{base}/(\sqrt3V_\text{base})$.
:::
:::
:::

::: check
kind: derivation
vars: S = 1..1000, V = 0.1..1000, X = 0.01..1000

## A system uses base power S MVA and base voltage V kV; a line has X ohms.

::: step
answer: V^2/S

### What is the base impedance in ohms?
:::

::: step
answer: X*S/V^2

### What is X in per unit?
:::

::: step
answer: S*1e6/(sqrt(3)*V*1e3)

### What is the base current in amperes?
:::

::: right
Right. Two bases fix all the others, and the per-unit system takes the transformer ratios out of the circuit.
:::
:::

::: explain
## Why does choosing voltage bases in the ratio of a transformer's turns make the transformer disappear from the per-unit circuit?

::: model
An ideal transformer multiplies voltage by its turns ratio and divides current by it. If the voltage bases on its two sides are in that same ratio, then the per-unit voltage, the actual voltage divided by its base, is the same on both sides, and so is the per-unit current, since the current bases are in the inverse ratio for a common power base. A device whose per-unit voltage and current are identical on both sides is just a wire, so in the per-unit circuit only the transformer's leakage impedance and magnetizing branch remain. The impedance base changes as the square of the voltage base, which is why the same per-unit impedance corresponds to different ohms on the two sides.
:::
:::

::: practice

::: check
given: V = 2.4 | 69 | 765; S = 10 | 100 | 1000
answer: V^2/S
unit: Ω
tolerance: 0.5%

## Base impedance at {V} kV, {S} MVA?

::: misses
- [any] $V^2/S$.
:::
:::

::: check
given: X = 0.1 | 0.2; a = 30 | 500; b = 12.5 | 22; c = 13.2 | 24
answer: X*(b/c)^2*(100/a)
tolerance: 0.5%

## {X} pu on {a} MVA, {b} kV to 100 MVA, {c} kV?

::: misses
- [any] $X(V_o/V_n)^2(S_n/S_o)$.
:::
:::

::: check
given: Z = 10 | 80; V = 69 | 500
answer: Z/(V^2/100)
tolerance: 0.5%

## {Z} Ω at {V} kV in pu on 100 MVA?

::: misses
- [any] $Z/Z_\text{base}$.
:::
:::
:::