title: The power system and complex power
heading: How electricity gets from generators to loads, why transmission runs at hundreds of kilovolts, balanced three-phase power, complex power and power factor, and correcting power factor with capacitors
eyebrow: S10 · Lesson 1 · The power system and complex power
xp: 50
---

::: hook
The interconnected grid is the largest machine people have built: thousands of generators spinning in lockstep at 60 Hz across a continent, feeding millions of loads through lines that run at up to 765 kV. Everything in this course, from the per-unit system to power flow, fault currents and stability, is a tool for predicting how that machine behaves and keeping it running. This lesson lays out its structure and the quantity that every power engineer reasons in: complex power.
:::

::: play
- The loss on a three-phase line with 10 Ω per phase carrying 100 MW at 0.95 power factor, against the line-to-line voltage.
- Loss goes as $I^2R$, and for a fixed power the current goes as 1/V, so the loss falls as $1/V^2$: 23% of the power at 69 kV, under 1% at 345 kV.
- That's the whole reason for transmission voltages: doubling the voltage cuts the loss to a quarter, for the same conductors.
:::

```sim plot
view: graph
x: V = 30..800 kV log
y: loss = 0..50 %
slider: P = 20..500 = 100 MW
slider: R = 1..30 = 10 Ω
plot: 100*3*(P*1e6/(sqrt(3)*V*1e3*0.95))^2*R/(P*1e6) | samples: 400 | label: loss as a share of the power sent
readout: line current at 345 kV, A = P*1e6/(sqrt(3)*345e3*0.95) | digits: 4
```

::: predict
## A utility moves a line from 138 kV to 345 kV, carrying the same 100 MW on the same conductors. What happens to the line's resistive loss?

- [ ] It falls by 2.5 times
- [x] It falls by about 6 times
- [ ] It stays the same
- [ ] It rises, because the voltage is higher

::: reveal
The current falls by 345/138 = 2.5 times, and the loss goes as the current squared: (2.5)² = 6.25 times less, from 5.82 MW to 0.93 MW. The price is bigger insulators, taller towers and wider rights-of-way.
:::
:::

::: nameit
## Structure

Generators produce power at 13.8 to 25 kV. Step-up transformers raise it to transmission voltages (115, 138, 230, 345, 500 and 765 kV in North America), substations step it down to subtransmission (34.5 to 138 kV) and distribution (4 to 35 kV), and pole or pad transformers deliver 120/240 V or 480 V. All of it is three-phase except the last few hundred meters to homes.

## Balanced three-phase power

A balanced system is analyzed one phase at a time, line to neutral. With line-to-line voltage $V_L$ and line current $I_L$:

$$S_{3\phi} = \sqrt{3}V_LI_L, \qquad P = \sqrt{3}V_LI_L\cos\phi, \qquad Q = \sqrt{3}V_LI_L\sin\phi$$

where φ is the angle by which the current lags the voltage. The line-to-neutral voltage is $V_L/\sqrt{3}$.

## Complex power

For one phase with phasors V and I, $S = VI^* = P + jQ$. P (watts) is the average power; Q (vars) measures energy sloshing back and forth, positive for inductive loads that absorb it. **Power factor** is $\cos\phi = P/|S|$, lagging for inductive loads.

## Power-factor correction

Shunt capacitors supply vars locally so the line doesn't have to carry them. To raise a load P from power factor $\cos\phi_1$ to $\cos\phi_2$:

$$Q_C = P(\tan\phi_1 - \tan\phi_2)$$

Less reactive current means less line loss, less voltage drop and more capacity for real power.
:::

::: example
## A plant draws 50 MW at 0.8 power factor lagging. How large a capacitor bank brings it to 0.95?

::: solution
1. **Reactive power now.** At 0.8 power factor:
   $$\begin{aligned} Q_1 &= 50 \tan(\cos^{-1} 0.8) \\ &= 37.5\ \text{Mvar} \end{aligned}$$
   and |S| = 62.5 MVA.
2. **Reactive power at 0.95.**
   $$\begin{aligned} Q_2 &= 50 \tan(\cos^{-1} 0.95) \\ &= 16.4\ \text{Mvar} \end{aligned}$$
3. **Bank size.** The bank must supply the difference:
   $$\begin{aligned} Q_C &= 37.5 - 16.4 \\ &= 21.1\ \text{Mvar} \end{aligned}$$
4. **What it saves.** The apparent power falls to 52.6 MVA, so the line current falls by 16% and the line loss by 29%.

**Answer:** a 21.1 Mvar bank, which cuts the line current by 16% and the line loss by 29%.
:::
:::

::: example
## A 20 MVA generator runs at 13.8 kV. What's its rated current?

::: solution
1. **Rated current.**
   $$\begin{aligned} I &= \frac{S}{\sqrt{3}V_L} \\ &= \frac{20 \times 10^6}{1.732 \times 13\,800} \\ &= 837\ \text{A} \end{aligned}$$
   per phase.
2. **Why so modest a voltage.** Generators are built at modest voltages because insulating a rotating winding is hard; the step-up transformer next to the generator takes the voltage up to transmission level.

**Answer:** 837 A per phase.
:::
:::

::: example
## A balanced Δ-connected load has 30 + j40 Ω in each phase and sits across a 480 V three-phase supply. Find its current, its complex power and its power factor.

::: solution
1. **Phase current.** Each phase sees the full 480 V line voltage across |Z| = 50 Ω:
   $$\begin{aligned} I_\phi &= 480/50 \\ &= 9.6\ \text{A} \end{aligned}$$
   The line current is √3 times that, 16.6 A.
2. **Power per phase.**
   $$\begin{aligned} P &= 9.6^2 \times 30 \\ &= 2765\ \text{W} \\ Q &= 9.6^2 \times 40 \\ &= 3686\ \text{var} \end{aligned}$$
3. **All three phases.** Three phases give 8.29 kW and 11.06 kvar, 13.82 kVA in all.
4. **Power factor.**
   $$\begin{aligned} \text{pf} &= 30/50 \\ &= 0.6 \end{aligned}$$
   lagging.

**Answer:** 9.6 A in each phase (16.6 A in each line), a complex power of 8.29 kW + j11.06 kvar (13.82 kVA), and a power factor of 0.6 lagging.
:::
:::

::: check
given: P = 50 | 200 | 800; V = 69 | 230 | 500; f = 0.85 | 0.95
answer: P*1e6/(sqrt(3)*V*1e3*f)
unit: A
tolerance: 0.5%

## A three-phase line carries {P} MW at {V} kV, power factor {f}. What's the line current?

::: right
Right. $P/(\sqrt{3}V_L\cos\phi)$ = {answer} A.
:::

::: misses
- [P*1e6/(V*1e3*f)] Include $\sqrt{3}$ for a three-phase line with line-to-line voltage.
- [P*1e6/(3*V*1e3*f)] $V_L$ is line to line, so the factor is $\sqrt{3}$, not 3.
- [any] Not yet. $P = \sqrt{3}V_LI_L\cos\phi$.
:::
:::

::: check
given: P = 100 | 400; V = 138 | 345; R = 5 | 15
answer: 100*3*(P*1e6/(sqrt(3)*V*1e3*0.95))^2*R/(P*1e6)
unit: %
tolerance: 0.5%

## A line with {R} Ω per phase carries {P} MW at {V} kV and 0.95 power factor. What fraction of the power is lost in it?

::: right
Right. $3I^2R/P$ = {answer}%.
:::

::: misses
- [100*(P*1e6/(sqrt(3)*V*1e3*0.95))^2*R/(P*1e6)] There are three phases, each with $I^2R$.
- [any] Not yet. Find I, then $3I^2R$.
:::
:::

::: check
given: P = 10 | 40 | 120; f = 0.7 | 0.8 | 0.9
answer: P*tan(acos(f))
unit: Mvar
tolerance: 0.5%

## A load takes {P} MW at {f} power factor lagging. How many vars does it absorb?

::: right
Right. $Q = P\tan\phi$ = {answer} Mvar.
:::

::: misses
- [P*sin(acos(f))] That's $|S|\sin\phi$ only if you use |S|, not P.
- [P/f] That's |S|, the apparent power, in MVA.
- [any] Not yet. $Q = P\tan(\cos^{-1}\text{pf})$.
:::
:::

::: check
given: P = 5 | 30 | 80; a = 0.7 | 0.8; b = 0.95 | 0.98
answer: P*(tan(acos(a)) - tan(acos(b)))
unit: Mvar
tolerance: 0.5%

## How much capacitive compensation raises a {P} MW load from {a} to {b} power factor?

::: right
Right. $P(\tan\phi_1 - \tan\phi_2)$ = {answer} Mvar.
:::

::: misses
- [P*tan(acos(a))] That would bring the power factor all the way to 1.
- [any] Not yet. The vars before minus the vars after.
:::
:::

::: check
given: V = 7.2 | 13.8 | 120; I = 100 | 400; a = 10 | 35 | 60
answer: V*I*cos(a*pi/180)/1000
unit: MW
tolerance: 0.5%

## One phase carries {I} A at {V} kV line to neutral, with the current lagging the voltage by {a}°. What real power does that phase carry?

::: right
Right. $|V||I|\cos\phi$ = {answer} MW.
:::

::: misses
- [V*I*sin(a*pi/180)/1000] That's the reactive power.
- [any] Not yet. $P = \text{Re}(VI^*)$.
:::
:::

::: check
given: a = 69 | 115 | 138; b = 230 | 345 | 765
answer: (b/a)^2
tolerance: 0.5%

## A line's voltage is raised from {a} kV to {b} kV for the same power and conductors. By what factor does the resistive loss fall?

::: right
Right. $(V_2/V_1)^2$ = {answer}.
:::

::: misses
- [b/a] The loss goes as current squared.
- [any] Not yet. $I \propto 1/V$ and loss ∝ $I^2$.
:::
:::

::: check
kind: parts
given: V = 208 | 480 | 4160; R = 8 | 30; X = 6 | 40

## A balanced Y-connected load of {R} + j{X} Ω per phase is supplied at {V} V line to line.

::: part
answer: V/sqrt(3)/sqrt(R^2 + X^2)
unit: A
tolerance: 0.5%

### What is the line current?

::: misses
- [V/sqrt(R^2 + X^2)] In Y, each phase sees the line-to-neutral voltage.
- [any] $(V_L/\sqrt3)/|Z|$.
:::
:::

::: part
answer: 3*(V/sqrt(3)/sqrt(R^2 + X^2))^2*R/1e3
unit: kW
tolerance: 0.5%

### What real power does it take?

::: misses
- [any] $3I^2R$.
:::
:::

::: part
answer: R/sqrt(R^2 + X^2)
tolerance: 0.5%

### At what power factor?

::: misses
- [any] R/|Z|.
:::
:::
:::

::: check
kind: derivation
vars: V = 100..1000000, Z = 0.1..1000, a = 0..1.5

## A balanced Δ load has impedance of magnitude Z and angle a (radians) per phase, across line voltage V.

::: step
answer: V/Z

### What is the phase current?
:::

::: step
answer: 3*V^2/Z

### What is the total apparent power?
:::

::: step
answer: 3*V^2/Z*cos(a)

### And the real power?
:::

::: right
Right. In Δ each phase sees the full line voltage; in Y it would see $V_L/\sqrt3$ and take a third of the power.
:::
:::

::: explain
## Why does a load with poor power factor cost the utility money even though reactive power does no net work?

::: model
A load with poor power factor draws more current for the same real power, because part of its current is out of phase with the voltage and just shuttles energy back and forth each cycle. The utility's generators, transformers and lines must still carry that extra current, so they heat up as if they were delivering more power, the line loss grows with the square of the current, and the voltage drop along the lines grows too. Equipment is sized by current and apparent power, not real power, so the reactive part uses up capacity that could otherwise sell real energy. That's why industrial customers pay for low power factor and install capacitors to supply their vars locally.
:::
:::

::: practice

::: check
given: P = 30 | 600; V = 34.5 | 345; f = 0.8 | 0.98
answer: P*1e6/(sqrt(3)*V*1e3*f)
unit: A
tolerance: 0.5%

## Line current: {P} MW, {V} kV, pf {f}?

::: misses
- [any] $P/(\sqrt{3}V_L\cos\phi)$.
:::
:::

::: check
given: P = 2 | 25; a = 0.65 | 0.75; b = 0.92 | 1
answer: P*(tan(acos(a)) - tan(acos(b)))
unit: Mvar
tolerance: 0.5%

## Capacitor to raise {P} MW from {a} to {b} pf?

::: misses
- [any] $P(\tan\phi_1 - \tan\phi_2)$.
:::
:::

::: check
given: P = 15 | 90; f = 0.75 | 0.85
answer: P/f
unit: MVA
tolerance: 0.5%

## Apparent power of {P} MW at pf {f}?

::: misses
- [any] $|S| = P/\cos\phi$.
:::
:::
:::