title: Power transfer and voltage
heading: Real power flow set by the angle across a line, reactive power flow set by voltage magnitudes, the voltage-drop approximation, the steady-state transfer limit, and the nose curve that marks voltage collapse
eyebrow: S10 · Lesson 7 · Power transfer and voltage
xp: 50
---

::: hook
Two facts govern how power moves on a grid. Real power flows from the bus whose voltage leads to the one that lags, in proportion to the sine of the angle between them. Reactive power flows from the higher voltage magnitude to the lower. Almost everything an operator does follows from these: generators push real power by advancing their rotors, capacitors and generators hold voltages up by supplying vars, and a line asked to carry too much reaches a point where the voltage at its end collapses.
:::

::: play
- The nose curve of a lossless line: the receiving-end voltage against the power delivered, with the sending end held at 1 pu, for series reactance X and a load whose Q/P ratio you set.
- At light load the voltage barely falls. Push P up and the voltage drops faster and faster until the curve turns back at the nose: no more power can be delivered, and the lower branch is unstable.
- A lagging load (positive Q/P) lowers the nose; a leading one (negative Q/P, local capacitors) raises it.
:::

```sim plot
view: graph
x: P = 0..2.5 pu
y: V = 0..1.4 pu
slider: X = 0.2..1 = 0.5
slider: t = -0.5..0.75 = 0
plot: sqrt(((1 - 2*P*t*X) + sqrt((1 - 2*P*t*X)^2 - 4*X^2*(P^2 + (P*t)^2)))/2) | samples: 800 | label: upper branch
plot: sqrt(((1 - 2*P*t*X) - sqrt((1 - 2*P*t*X)^2 - 4*X^2*(P^2 + (P*t)^2)))/2) | samples: 800 | dashed | color: ch3 | label: lower branch
readout: unity-pf maximum, pu = 1/(2*X) | digits: 3
```

::: predict
## Two buses at 1 pu are joined by a line of reactance 0.5 pu, with bus 1 leading by 30°. How much real power flows, and who supplies the line's vars?

- [ ] 2 pu; bus 1 supplies all the vars
- [x] 1 pu; both ends supply vars to the line equally
- [ ] 0.5 pu; no vars flow
- [ ] 1 pu; bus 2 supplies all the vars

::: reveal
$P = V_1V_2\sin\delta/X$ = sin 30°/0.5 = 1 pu. Each end sends $(1 - \cos 30°)/0.5$ = 0.268 pu of vars into the line, which absorbs $I^2X$ = 0.536 pu in its reactance. With equal voltage magnitudes, the var demand splits evenly.
:::
:::

::: nameit
## Flow on a lossless line

For buses at $V_1\angle\delta_1$ and $V_2\angle\delta_2$ joined by reactance X, with $\delta = \delta_1 - \delta_2$:

$$P_{12} = \frac{V_1V_2}{X}\sin\delta, \qquad Q_{12} = \frac{V_1^2 - V_1V_2\cos\delta}{X}$$

Real power follows angle; it peaks at $V_1V_2/X$ at δ = 90°, the **steady-state stability limit**. Reactive power follows voltage magnitude: with small δ, $Q_{12} \approx V_1(V_1 - V_2)/X$.

## Voltage drop

On a line with R + jX carrying P + jQ to a bus at about 1 pu,

$$\Delta V \approx RP + XQ \text{ (per unit)}$$

On transmission lines X ≫ R, so voltage is controlled by reactive power; on distribution feeders R matters too.

## The nose curve

With the sending end at $V_S$ and a load P + jQ at the receiving end,

$$V_R^2 = \frac{(V_S^2 - 2QX) \pm \sqrt{(V_S^2 - 2QX)^2 - 4X^2(P^2 + Q^2)}}{2}$$

Real solutions exist only up to a maximum P. At unity power factor that's $V_S^2/2X$, reached at $V_R = V_S/\sqrt{2}$. Lagging loads lower it; local var support raises it. Operating near the nose risks **voltage collapse**, which caused major blackouts in France in 1978 and Tokyo in 1987.
:::

::: example
## A line of X = 0.5 pu from a 1 pu source feeds a unity-power-factor load. What's the receiving voltage at 0.8 pu load, and how much can it deliver at most?

::: solution
1. **Receiving voltage at 0.8 pu.** From the nose-curve formula with Q = 0:
   $$\begin{aligned} V_R^2 &= \frac{1 + \sqrt{1 - 4 \times 0.25 \times 0.64}}{2} \\ &= 0.8 \end{aligned}$$
   so $V_R$ = 0.894 pu.
2. **Maximum power.**
   $$\begin{aligned} P_\max &= \frac{1}{2 \times 0.5} \\ &= 1\ \text{pu} \end{aligned}$$
   at $V_R$ = 0.707.
3. **At 0.9 power factor lagging.** The maximum falls to 0.627 pu, at a voltage of only 0.59 pu.

**Answer:** $V_R$ = 0.894 pu at 0.8 pu of load, and the line can deliver at most 1 pu (at 0.707 pu voltage).
:::
:::

::: example
## A feeder has R = 0.02 pu and X = 0.1 pu and carries 0.8 + j0.4 pu. Estimate the voltage drop.

::: solution
1. **Estimate the drop.**
   $$\begin{aligned} \Delta V &\approx 0.02 \times 0.8 + 0.1 \times 0.4 \\ &= 0.056\ \text{pu} \end{aligned}$$
   which is 5.6%.
2. **Where it comes from.** Most of it, 4 of the 5.6 points, comes from the reactive power.
3. **Supply the vars locally.** A capacitor supplying 0.4 pu at the load would cut the drop to 1.6%.

**Answer:** about 0.056 pu, a 5.6% drop.
:::
:::

::: example
## A 1 pu source feeds a load through X = 0.5 pu. How much power can it deliver at unity power factor, at 0.9 lagging and at 0.9 leading?

::: solution
1. **The limit.** For a load of power factor angle φ the maximum, at the nose of the P–V curve, is
   $$P_\max = \frac{E^2\cos\phi}{2X(1 + \sin\phi)}$$
2. **Unity power factor.**
   $$\begin{aligned} P_\max &= 1/(2 \times 0.5) \\ &= 1.0\ \text{pu} \end{aligned}$$
3. **0.9 lagging.** Here sin φ = 0.436:
   $$\begin{aligned} P_\max &= \frac{0.9}{1 \times 1.436} \\ &= 0.63\ \text{pu} \end{aligned}$$
4. **0.9 leading.** Here sin φ = −0.436:
   $$\begin{aligned} P_\max &= 0.9/0.564 \\ &= 1.60\ \text{pu} \end{aligned}$$
5. **Why lagging loads are worst.** Lagging loads drain vars from the line and collapse the voltage sooner, which is why reactive support sets how much a weak line can carry.

**Answer:** 1.0 pu at unity power factor, 0.63 pu at 0.9 lagging and 1.60 pu at 0.9 leading.
:::
:::

::: check
given: V = 0.95 | 1 | 1.05; W = 0.98 | 1.02; X = 0.2 | 0.5; d = 10 | 25 | 40
answer: V*W*sin(d*pi/180)/X
tolerance: 0.5%

## Buses at {V} pu and {W} pu are joined by X = {X} pu, with a {d}° angle between them. How much real power flows?

::: right
Right. $V_1V_2\sin\delta/X$ = {answer} pu.
:::

::: misses
- [V*W*cos(d*pi/180)/X] Real power goes with the sine of the angle.
- [any] Not yet. $P = V_1V_2\sin\delta/X$.
:::
:::

::: check
given: P = 0.3 | 0.6 | 1.2; X = 0.15 | 0.4
answer: asin(P*X)*180/pi
unit: °
tolerance: 0.5%

## Two 1 pu buses joined by X = {X} pu must transfer {P} pu. What angle does that take?

::: right
Right. $\sin^{-1}(PX/V_1V_2)$ = {answer}°.
:::

::: misses
- [any] Not yet. Invert $P = V_1V_2\sin\delta/X$.
:::
:::

::: check
given: V = 1 | 1.05; W = 0.95 | 1; X = 0.2 | 0.4; d = 15 | 30
answer: (V^2 - V*W*cos(d*pi/180))/X
tolerance: 0.5%

## Bus 1 at {V} pu leads bus 2 at {W} pu by {d}° across X = {X} pu. How much reactive power leaves bus 1 into the line?

::: right
Right. $(V_1^2 - V_1V_2\cos\delta)/X$ = {answer} pu.
:::

::: misses
- [V*W*sin(d*pi/180)/X] That's the real power.
- [any] Not yet. $Q_{12} = (V_1^2 - V_1V_2\cos\delta)/X$.
:::
:::

::: check
given: R = 0.01 | 0.05; X = 0.08 | 0.2; P = 0.5 | 1; Q = 0.1 | 0.4
answer: 100*(R*P + X*Q)
unit: %
tolerance: 0.5%

## A line with R = {R}, X = {X} pu carries {P} + j{Q} pu. Estimate the voltage drop.

::: right
Right. $RP + XQ$ = {answer}%.
:::

::: misses
- [100*(X*P + R*Q)] R goes with P and X with Q.
- [any] Not yet. $\Delta V \approx RP + XQ$.
:::
:::

::: check
given: V = 0.95 | 1 | 1.05; X = 0.25 | 0.6
answer: V^2/(2*X)
tolerance: 0.5%

## A source of {V} pu feeds a unity-power-factor load through X = {X} pu. What's the most power it can deliver?

::: right
Right. $V_S^2/2X$ = {answer} pu, at the nose.
:::

::: misses
- [V^2/X] That's the transfer limit between two held voltages. With the load voltage free to sag, the limit is half that.
- [any] Not yet. Find where the nose curve's discriminant vanishes.
:::
:::

::: check
given: X = 0.2 | 0.4; P = 0.4 | 0.8 | 1.1
answer: sqrt((1 + sqrt(1 - 4*X^2*P^2))/2)
tolerance: 0.5%

## A 1 pu source feeds {P} pu at unity power factor through X = {X} pu. What's the receiving voltage (upper branch)?

::: right
Right. $V_R^2 = (1 + \sqrt{1 - 4X^2P^2})/2$, so $V_R$ = {answer} pu.
:::

::: misses
- [sqrt((1 - sqrt(1 - 4*X^2*P^2))/2)] That's the unstable lower branch.
- [any] Not yet. Solve the nose-curve equation with Q = 0.
:::
:::

::: check
kind: parts
given: E = 1 | 1.05; X = 0.2 | 0.5 | 1; f = 0.8 | 0.9 | 0.95

## A source of {E} pu feeds a load at power factor {f} lagging through X = {X} pu.

::: part
answer: E^2*f/(2*X*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### What is the most real power it can deliver?

::: misses
- [E^2/(2*X)] That's for a unity-power-factor load.
- [any] $E^2\cos\phi/(2X(1 + \sin\phi))$.
:::
:::

::: part
answer: E^2/(2*X)
tolerance: 0.5%

### And at unity power factor?

::: misses
- [any] $E^2/(2X)$.
:::
:::
:::

::: check
kind: derivation
vars: V = 0.9..1.1, W = 0.9..1.1, X = 0.05..1, d = 0..1.2

## Buses at V and W pu, with V leading by d radians, are joined by reactance X.

::: step
answer: V*W/X*sin(d)

### What real power flows from V to W?
:::

::: step
answer: (V^2 - V*W*cos(d))/X

### What reactive power leaves the first bus?
:::

::: step
answer: (W^2 - V*W*cos(d))/X

### What reactive power leaves the second bus?
:::

::: right
Right. The two reactive flows differ by the line's own $I^2X$ absorption.
:::
:::

::: explain
## Why does real power follow voltage angle while reactive power follows voltage magnitude on a transmission line?

::: model
A transmission line is mostly reactance, so the current through it is the voltage difference across it divided by jX, which turns it 90° from that difference. When the two ends differ mainly in angle, the difference phasor is nearly perpendicular to the bus voltages, and the current it drives through jX comes out nearly in phase with them: real power. When they differ mainly in magnitude, the difference points along the voltages, and the current comes out 90° behind them: reactive power. That decoupling is why operators control real power flows with generator output and angles, and voltages with vars, nearly independently.
:::
:::

::: practice

::: check
given: X = 0.1 | 0.3; d = 5 | 20 | 35
answer: sin(d*pi/180)/X
tolerance: 0.5%

## Power across X = {X} pu at {d}°, both buses at 1 pu?

::: misses
- [any] $\sin\delta/X$.
:::
:::

::: check
given: R = 0.03 | 0.1; X = 0.05 | 0.15; P = 0.3 | 0.9; Q = 0.2 | 0.6
answer: 100*(R*P + X*Q)
unit: %
tolerance: 0.5%

## Voltage drop for {P} + j{Q} on {R} + j{X}?

::: misses
- [any] $RP + XQ$.
:::
:::

::: check
given: X = 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.8
answer: 1/(2*X)
tolerance: 0.5%

## Unity-pf transfer limit through X = {X} pu from 1 pu?

::: misses
- [any] $1/2X$.
:::
:::
:::