title: "Problem set 1: power, per unit, transformers and line parameters"
heading: "Problem set 1: three-phase and complex power, the per-unit system, transformer models and transmission line parameters"
eyebrow: S10 · Problem set 1
type: problems
---

::: hook
These problems cover lessons 1 to 4: three-phase currents, losses and power-factor correction, per-unit bases and base changes, transformer tests, regulation and connections, and the inductance, capacitance and natural loading of overhead lines.
:::

::: pool
pick: 12

::: check
kind: parts
given: P = 80 | 300; V = 115 | 345; f = 0.85 | 0.95; R = 4 | 12

## A three-phase line ({R} Ω per phase) carries {P} MW at {V} kV, power factor {f}.

::: part
answer: P*1e6/(sqrt(3)*V*1e3*f)
unit: A
tolerance: 0.5%

### Line current?

::: misses
- [any] $P/(\sqrt{3}V_L\cos\phi)$.
:::
:::

::: part
answer: 3*(P*1e6/(sqrt(3)*V*1e3*f))^2*R/1e6
unit: MW
tolerance: 0.5%

### Line loss?

::: misses
- [any] $3I^2R$.
:::
:::

::: part
answer: P*tan(acos(f))
unit: Mvar
tolerance: 0.5%

### Vars carried?

::: misses
- [any] $P\tan\phi$.
:::
:::
:::

::: check
kind: parts
given: P = 8 | 60; a = 0.7 | 0.78; b = 0.93 | 0.97

## A {P} MW load at {a} power factor lagging, corrected to {b}.

::: part
answer: P*(tan(acos(a)) - tan(acos(b)))
unit: Mvar
tolerance: 0.5%

### Capacitor needed?

::: misses
- [any] $P(\tan\phi_1 - \tan\phi_2)$.
:::
:::

::: part
answer: 100*(1 - (a/b)^2)
unit: %
tolerance: 0.5%

### Percentage cut in line loss?

::: misses
- [any] Current scales as 1/pf, loss as its square.
:::
:::
:::

::: check
kind: parts
given: V = 4.16 | 34.5 | 230; S = 10 | 100

## Bases of {S} MVA and {V} kV.

::: part
answer: V^2/S
unit: Ω
tolerance: 0.5%

### Base impedance?

::: misses
- [any] $V^2/S$.
:::
:::

::: part
answer: S*1e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

### Base current?

::: misses
- [any] $S/(\sqrt{3}V)$.
:::
:::
:::

::: check
kind: parts
given: X = 0.08 | 0.2; a = 20 | 150; b = 12.5 | 13.2; c = 13.8 | 14.4; Z = 20 | 90; V = 138 | 230

## A machine rated {a} MVA, {b} kV with X = {X} pu; a {V} kV line of {Z} Ω. System base: 100 MVA, {c} kV on the machine's side.

::: part
answer: X*(b/c)^2*(100/a)
tolerance: 0.5%

### Machine's X on the system base?

::: misses
- [any] Change of base.
:::
:::

::: part
answer: Z/(V^2/100)
tolerance: 0.5%

### Line in per unit?

::: misses
- [any] $Z/Z_\text{base}$.
:::
:::
:::

::: check
kind: parts
given: G = 0.25 | 0.4; T = 0.08 | 0.12; Z = 30 | 120; V = 138 | 345

## A generator (X'' = {G} pu) and transformer (X = {T} pu) feed a {V} kV line of j{Z} Ω, all on 100 MVA. A three-phase short occurs at the line's far end.

::: part
answer: 1/(G + T + Z/(V^2/100))
tolerance: 0.5%

### Fault current in per unit?

::: misses
- [any] 1 over the total reactance.
:::
:::

::: part
answer: 1/(G + T + Z/(V^2/100))*100e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### In kA on the line?

::: misses
- [any] Times $I_\text{base}$ at {V} kV.
:::
:::
:::

::: check
kind: parts
given: V = 350 | 600; I = 3 | 8; P = 120 | 400; B = 8000 | 13800; S = 25 | 75

## A {S} kVA transformer's short-circuit test on its {B} V side reads {V} V, {I} A and {P} W.

::: part
answer: P/I^2/(B^2/(S*1000))
tolerance: 0.5%

### Per-unit resistance?

::: misses
- [any] $R = P/I^2$ over the base.
:::
:::

::: part
answer: sqrt((V/I)^2 - (P/I^2)^2)/(B^2/(S*1000))
tolerance: 0.5%

### Per-unit reactance?

::: misses
- [any] $\sqrt{Z^2 - R^2}$ over the base.
:::
:::
:::

::: check
kind: parts
given: r = 0.006 | 0.015; x = 0.05 | 0.1; f = 0.75 | 0.9

## A transformer with R = {r} pu, X = {x} pu at full load.

::: part
answer: 100*(sqrt((1 + r*f + x*sqrt(1 - f^2))^2 + (x*f - r*sqrt(1 - f^2))^2) - 1)
unit: %
tolerance: 0.5%

### Regulation at {f} lagging?

::: misses
- [any] $|1 + IZ| - 1$.
:::
:::

::: part
answer: 100*(sqrt((1 + r*f - x*sqrt(1 - f^2))^2 + (x*f + r*sqrt(1 - f^2))^2) - 1)
unit: %
tolerance: 0.5%

### Regulation at {f} leading?

::: misses
- [any] Current at +φ.
:::
:::
:::

::: check
kind: parts
given: S = 40 | 250; L = 66 | 132; d = 11 | 33; P = 25 | 80; c = 120 | 350; u = 300 | 900; k = 0.6 | 1

## A {S} kVA transformer rewired as an autotransformer from {L} kV to {L} + {d} kV; and a {P} kW transformer with core loss {c} W and full-load copper loss {u} W, at {k} of full load.

::: part
answer: S*(L + d)/d
unit: kVA
tolerance: 0.5%

### Autotransformer rating?

::: misses
- [any] $SV_H/(V_H - V_L)$.
:::
:::

::: part
answer: 100*P*k/(P*k + c/1000 + u/1000*k^2)
unit: %
tolerance: 0.1%

### Second transformer's efficiency?

::: misses
- [any] Output over output plus losses.
:::
:::
:::

::: check
kind: parts
given: a = 5 | 8; b = 6 | 9; c = 11 | 16; s = 9 | 12; d = 0.4 | 0.5

## Phases spaced {a}, {b} and {c} m; two-conductor bundles {d} m apart with conductor GMR {s} mm.

::: part
answer: (a*b*c)^(1/3)
unit: m
tolerance: 0.5%

### GMD?

::: misses
- [any] Cube root of the product.
:::
:::

::: part
answer: sqrt(s/1000*d)*1000
unit: mm
tolerance: 0.5%

### Bundle GMR?

::: misses
- [any] $\sqrt{D_sd}$.
:::
:::

::: part
answer: 0.2*ln((a*b*c)^(1/3)/sqrt(s/1000*d))
unit: mH
tolerance: 0.5%

### Inductance per km?

::: misses
- [any] $0.2\ln(D_m/D_s)$.
:::
:::
:::

::: check
kind: parts
given: D = 6 | 11; r = 12 | 18; d = 0.4 | 0.6

## Two-conductor bundles {d} m apart, conductor radius {r} mm, $D_m$ = {D} m.

::: part
answer: 55.63/ln(D/sqrt(r/1000*d))
unit: nF
tolerance: 0.5%

### Capacitance per km?

::: misses
- [any] Use $\sqrt{rd}$ as the radius.
:::
:::

::: part
answer: 55.63/ln(D/(r/1000))
unit: nF
tolerance: 0.5%

### Capacitance per km without bundling?

::: misses
- [any] $55.63/\ln(D_m/r)$.
:::
:::
:::

::: check
kind: parts
given: L = 0.85 | 1.25; C = 9.5 | 13; V = 138 | 345 | 765

## A {V} kV line with L = {L} mH/km and C = {C} nF/km.

::: part
answer: sqrt(L*1e-3/(C*1e-9))
unit: Ω
tolerance: 0.5%

### Surge impedance?

::: misses
- [any] $\sqrt{L/C}$.
:::
:::

::: part
answer: V^2/sqrt(L*1e-3/(C*1e-9))
unit: MW
tolerance: 0.5%

### SIL?

::: misses
- [any] $V^2/Z_c$.
:::
:::
:::

::: check
kind: parts
given: a = 69 | 138; b = 2 | 2.5; V = 230 | 500

## A line's voltage rises from {a} kV to {b} times that; separately, a Y bank serves {V} kV.

::: part
answer: b^2
tolerance: 0.5%

### Factor by which the loss falls?

::: misses
- [any] Voltage ratio squared.
:::
:::

::: part
answer: V/sqrt(3)
unit: kV
tolerance: 0.5%

### Voltage across each Y unit?

::: misses
- [any] $V_L/\sqrt{3}$.
:::
:::
:::

::: check
kind: parts
given: V = 208 | 480 | 600; R = 12 | 24; X = 9 | 32

## A balanced Δ load has {R} + j{X} Ω per phase across {V} V.

::: part
answer: sqrt(3)*V/sqrt(R^2 + X^2)
unit: A
tolerance: 0.5%

### What is the line current?

::: misses
- [V/sqrt(R^2 + X^2)] That's the phase current; the line current is √3 times it.
- [any] $\sqrt3V_L/|Z|$.
:::
:::

::: part
answer: 3*V^2/(R^2 + X^2)*X/1e3
unit: kvar
tolerance: 0.5%

### How many vars does it absorb?

::: misses
- [any] $3I_\phi^2X$.
:::
:::
:::

::: check
kind: parts
given: S = 25 | 100 | 1000; c = 0.15 | 0.3 | 0.6; u = 0.8 | 1.2 | 2

## A {S} kVA transformer has {c}% core loss and {u}% full-load copper loss.

::: part
answer: sqrt(c/u)*100
unit: %
tolerance: 0.5%

### At what load is it most efficient?

::: misses
- [any] Where copper loss equals core loss.
:::
:::

::: part
answer: 100/(100 + c + u)*100
unit: %
tolerance: 0.1%

### What is its full-load efficiency at unity power factor?

::: misses
- [any] Output over output plus both losses.
:::
:::
:::

::: check
kind: parts
given: P = 3 | 10 | 40; f = 0.8 | 0.9; V = 4.16 | 13.8

## A {P} MW load at power factor {f} runs at its rated {V} kV. Use a 100 MVA base.

::: part
answer: P/f/100
tolerance: 0.5%

### What is its current in per unit?

::: misses
- [P/100] Use apparent power.
- [any] S/S_base at 1 pu.
:::
:::

::: part
answer: P/f*1e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

### And in amperes?

::: misses
- [any] $S/(\sqrt3V)$.
:::
:::
:::
:::