title: "Problem set 10: power systems across the course"
heading: "Problem set 10: problems that combine per unit, lines, power flow, generators, markets, frequency, faults, protection and stability"
eyebrow: S10 · Problem set 10
type: problems
---

::: hook
These problems draw on the whole course, and most chain several ideas: a line's parameters turned into a transfer limit, a per-unit fault current turned into a relay setting, a generator's operating point turned into a stability margin, an inertia loss turned into a frequency nadir requirement. Work them as a review before the final.
:::

::: pool
pick: 12

::: check
kind: parts
given: a = 7 | 10; b = 8 | 12; c = 14 | 20; s = 11 | 14; d = 0.4 | 0.45; V = 345 | 500; l = 150 | 300

## A {V} kV line, {l} km: phases spaced {a}, {b}, {c} m; two-conductor bundles {d} m apart, conductor GMR {s} mm.

::: part
answer: 2*pi*60*0.2e-3*ln((a*b*c)^(1/3)/sqrt(s/1000*d))*l
unit: Ω
tolerance: 0.5%

### Total series reactance?

::: misses
- [any] $\omega \cdot 0.2\ln(D_m/D_s)$ mΩ per m times length.
:::
:::

::: part
answer: V^2/(2*pi*60*0.2e-3*ln((a*b*c)^(1/3)/sqrt(s/1000*d))*l)
unit: MW
tolerance: 0.5%

### Transfer limit between buses held at rated voltage?

::: misses
- [any] $V^2/X$.
:::
:::
:::

::: check
kind: parts
given: X = 0.15 | 0.25; T = 0.1 | 0.12; Z = 30 | 80; V = 138 | 230; R = 100 | 150; f = 0.5 | 0.8

## A generator (X″ = {X}) and transformer (X = {T}, 100 MVA) feed a {V} kV line of j{Z} Ω, faulted at its far end; the line's relay uses a {R}:5 CT and very inverse curve, dial 1, pickup {f} × 5 A.

::: part
answer: 1/(X + T + Z/(V^2/100))*100e6/(sqrt(3)*V*1e3)
unit: A
tolerance: 0.5%

### Fault current on the line?

::: misses
- [any] Total per-unit reactance, then $I_\text{base}$.
:::
:::

::: part
answer: 1/(X + T + Z/(V^2/100))*100e6/(sqrt(3)*V*1e3)*5/R/(f*5)
tolerance: 0.5%

### Multiple of pickup?

::: misses
- [any] CT secondary over pickup.
:::
:::

::: part
answer: 19.61/((1/(X + T + Z/(V^2/100))*100e6/(sqrt(3)*V*1e3)*5/R/(f*5))^2 - 1) + 0.491
unit: s
tolerance: 0.5%

### Relay time?

::: misses
- [any] IEEE very inverse.
:::
:::
:::

::: check
kind: parts
given: X = 0.15 | 0.3; P = 0.6 | 0.9; Q = 0.35 | 0.5

## A slack at 1∠0° serves {P} + j{Q} pu through X = {X}.

::: part
answer: sqrt(((1 - 2*Q*X) + sqrt((1 - 2*Q*X)^2 - 4*X^2*(P^2 + Q^2)))/2)
tolerance: 0.5%

### Load voltage?

::: misses
- [any] Upper root.
:::
:::

::: part
answer: Q - P*tan(acos(0.95))
tolerance: 0.5%

### Capacitor (pu) to bring the load to 0.95 lagging?

::: misses
- [any] $Q - P\tan(\cos^{-1}0.95)$.
:::
:::
:::

::: check
kind: parts
given: X = 1 | 1.5; P = 0.7 | 0.9; Q = 0.2 | 0.5

## A generator ($X_s$ = {X}) delivers {P} + j{Q} at 1 pu; in a transient stability study its $P_{max}$ is 2.2 pu.

::: part
answer: sqrt((1 + X*Q)^2 + (X*P)^2)
tolerance: 0.5%

### Internal voltage |E|?

::: misses
- [any] $|1 + X_sQ + jX_sP|$.
:::
:::

::: part
answer: acos((pi - 2*asin(P/2.2))*(P/2.2) - cos(asin(P/2.2)))*180/pi
unit: °
tolerance: 0.5%

### Critical clearing angle for a zero-transfer fault?

::: misses
- [any] Equal-area formula.
:::
:::
:::

::: check
kind: parts
given: b = 5 | 6; c = 0.003 | 0.005; d = 5.5 | 6.5; e = 0.004 | 0.008; D = 300 | 700; s = 0.03 | 0.07

## Two units ({b}, {c}) and ({d}, {e}) share {D} MW; unit 1's loss sensitivity is {s}.

::: part
answer: (D + b/(2*c) + d/(2*e))/(1/(2*c) + 1/(2*e))
tolerance: 0.5%

### λ ignoring losses, dollars per MWh?

::: misses
- [any] Equal incremental cost.
:::
:::

::: part
answer: (b + 2*c*((D + b/(2*c) + d/(2*e))/(1/(2*c) + 1/(2*e)) - b)/(2*c))/(1 - s)
tolerance: 0.5%

### Unit 1's effective incremental cost at that dispatch?

::: misses
- [any] IC/(1 − s).
:::
:::
:::

::: check
kind: parts
given: S = 40 | 90; H = 3 | 5; s = 0.3 | 0.6; P = 1.5 | 3; R = 0.04 | 0.05

## A {S} GW system (synchronous H = {H} s, {s} inverter-based, droop {R}, D = 1) loses {P} GW.

::: part
answer: P*60/(2*H*(1 - s)*S)
unit: Hz/s
tolerance: 0.5%

### Initial ROCOF?

::: misses
- [any] $\Delta Pf_0/(2HS)$ with the reduced H.
:::
:::

::: part
answer: -(P/S)/(1/R + 1)*60
unit: Hz
tolerance: 0.5%

### Settling frequency deviation?

::: misses
- [any] $-\Delta P/(1/R + D)$.
:::
:::
:::

::: check
kind: parts
given: a = 0.15 | 0.25; c = 0.1 | 0.4; V = 69 | 138

## A {V} kV bus (100 MVA base) with $Z_1 = Z_2$ = j{a}, $Z_0$ = j{c}.

::: part
answer: 3/(2*a + c)*100e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Line-to-ground fault current?

::: misses
- [any] $3/(2Z_1 + Z_0)$ times $I_\text{base}$.
:::
:::

::: part
answer: sqrt(3)/(2*a)*100e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Line-to-line fault current?

::: misses
- [any] $\sqrt{3}/(2Z_1)$ times $I_\text{base}$.
:::
:::
:::

::: check
kind: parts
given: x = 0.1 | 0.2; y = 0.15 | 0.3; z = 0.2 | 0.35; T = 100 | 250; L = 120 | 180

## A triangle ($x_{12}$ = {x}, $x_{23}$ = {y}, $x_{13}$ = {z} pu) carries {T} MW from bus 1 to bus 3; line 1–3 is rated {L} MW.

::: part
answer: T*(x + y)/(x + y + z)
unit: MW
tolerance: 0.5%

### Flow on line 1–3?

::: misses
- [any] Inverse-reactance share.
:::
:::

::: part
answer: L*(x + y + z)/(x + y)
unit: MW
tolerance: 0.5%

### Largest transfer before line 1–3 overloads?

::: misses
- [any] Rating over the PTDF.
:::
:::
:::

::: check
kind: parts
given: a = 3 | 30; b = 5 | 50; E = 1.05 | 1.15; X = 0.4 | 0.8; d = 15 | 30

## Two machines (H = {a} and {b} s) with E = {E} pu each, joined by X = {X} pu, {d}° apart.

::: part
answer: E^2*cos(d*pi/180)/X
tolerance: 0.5%

### Synchronizing coefficient?

::: misses
- [any] $E_1E_2\cos\delta/X$.
:::
:::

::: part
answer: sqrt(2*pi*60*E^2*cos(d*pi/180)/X*(a + b)/(2*a*b))/(2*pi)
unit: Hz
tolerance: 0.5%

### Swing frequency?

::: misses
- [any] $\sqrt{\omega_sP_s/2H_{eq}}/2\pi$.
:::
:::
:::

::: check
kind: parts
given: L = 4 | 10; r = 0.2 | 0.35; x = 0.3 | 0.45; P = 2 | 5; V = 12.47 | 24.9; Q = 1 | 4; S = 60 | 200

## A {V} kV feeder {L} km long (z = {r} + j{x} Ω/km) with {P} MW of evenly spread unity-pf load; a {Q} Mvar capacitor at a {S} MVA bus.

::: part
answer: 50*sqrt(3)*P*1e6/(sqrt(3)*V*1e3)*r*L/(V*1e3)
unit: %
tolerance: 0.5%

### Voltage drop at the end?

::: misses
- [any] Half the lumped drop.
:::
:::

::: part
answer: sqrt(S/Q)
tolerance: 0.5%

### Capacitor's resonant harmonic?

::: misses
- [any] $\sqrt{S_{sc}/Q}$.
:::
:::
:::

::: check
kind: parts
given: Z = 30 | 70; C = 200 | 400; V = 2000 | 3000; L = 0.85 | 1.2; c = 10 | 12.5; l = 200 | 400

## A line of {Z} Ω (CT ratio {C}, VT ratio {V}), with L = {L} mH/km and C = {c} nF/km over {l} km.

::: part
answer: 0.8*Z*C/V
unit: Ω
tolerance: 0.5%

### Zone 1 setting at 80%, secondary ohms?

::: misses
- [any] $0.8Z\,\text{CTR}/\text{VTR}$.
:::
:::

::: part
answer: 1/cos(2*pi*60*sqrt(L*1e-3*c*1e-9)*l)
tolerance: 0.5%

### Open-end Ferranti rise?

::: misses
- [any] $1/\cos\beta l$.
:::
:::
:::

::: check
kind: parts
given: n = 118 | 2383; f = 0.1 | 0.2; let m = round(n*f); X = 0.1 | 0.2; P = 0.6 | 1.2; Q = 0.2 | 0.5

## A {n}-bus case with {m} PV buses; and a two-bus case with X = {X}, load {P} + j{Q}.

::: part
answer: 2*(n - 1) - m
tolerance: 0

### Jacobian size?

::: misses
- [any] $2(n - 1) - n_{PV}$.
:::
:::

::: part
answer: -P*X*180/pi
unit: °
tolerance: 0.5%

### Angle after Newton's first step?

::: misses
- [any] $-PX$.
:::
:::

::: part
answer: 1 - Q*X
tolerance: 0.5%

### Voltage after Newton's first step?

::: misses
- [any] $1 - QX$.
:::
:::
:::

::: check
kind: parts
given: X = 0.1 | 0.25 | 0.4; f = 0.85 | 0.92 | 0.98

## A 1 pu source feeds a load at power factor {f} lagging through X = {X} pu.

::: part
answer: f/(2*X*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### What is the most it can deliver?

::: misses
- [any] $\cos\phi/(2X(1 + \sin\phi))$.
:::
:::

::: part
answer: 1/sqrt(2*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### At what voltage?

::: misses
- [any] $1/\sqrt{2(1 + \sin\phi)}$.
:::
:::
:::

::: check
kind: parts
given: X = 1.1 | 1.5; E = 2 | 2.4; P = 0.5 | 0.85; V = 0.9 | 1

## A generator rated 1 pu ($X_s$ = {X}, field limit {E} pu) runs at {P} pu and {V} pu.

::: part
answer: sqrt(V^2 - P^2)
tolerance: 0.5%

### What vars does its armature limit allow?

::: misses
- [any] $\sqrt{V^2 - P^2}$.
:::
:::

::: part
answer: -V^2/X + sqrt((E*V/X)^2 - P^2)
tolerance: 0.5%

### And its field limit?

::: misses
- [any] $-V^2/X_s + \sqrt{(E_\max V/X_s)^2 - P^2}$.
:::
:::
:::

::: check
kind: parts
given: q = 0.04 | 0.08; r = 0.05 | 0.1

## Two 100 MW units with outage rates {q} and {r} serve a 150 MW load.

::: part
answer: q + r - q*r
tolerance: 0.5%

### What is the loss-of-load probability?

::: misses
- [q*r] One unit alone can't carry 150 MW.
- [any] Any outage causes a shortfall.
:::
:::
:::
:::