title: "Problem set 2: line models, power transfer, compensation and network matrices"
heading: "Problem set 2: short, medium and long lines, real and reactive power flow, compensation, surges and HVDC, and the bus admittance and impedance matrices"
eyebrow: S10 · Problem set 2
type: problems
---

::: hook
These problems cover lessons 6 to 11: line models with the Ferranti rise and charging vars, power transfer, voltage drop and the nose curve, series and shunt compensation, surges on lines and cables and HVDC converters, and building, reducing and using the bus admittance and impedance matrices.
:::

::: pool
pick: 12

::: check
kind: parts
given: l = 120 | 350 | 600; V = 230 | 500; B = 4 | 5.5

## An overhead line {l} km long (wavelength 4940 km), {V} kV, B = {B} µS/km.

::: part
answer: 1/cos(2*pi*l/4940)
tolerance: 0.5%

### Open-end voltage rise factor?

::: misses
- [any] $1/\cos\beta l$.
:::
:::

::: part
answer: V^2*B*1e-6*l
unit: Mvar
tolerance: 0.5%

### Charging vars at rated voltage?

::: misses
- [any] $V^2Bl$.
:::
:::
:::

::: check
kind: parts
given: L = 0.9 | 1.25; C = 9.5 | 12.5; l = 200 | 450; k = 0.6 | 1.4

## A lossless line, L = {L} mH/km, C = {C} nF/km, {l} km, loaded resistively at {k} times SIL.

::: part
answer: 2*pi*60*sqrt(L*1e-3*C*1e-9)*l*180/pi
unit: °
tolerance: 0.5%

### Electrical length βl?

::: misses
- [any] $\omega\sqrt{LC}\,l$.
:::
:::

::: part
answer: 1/sqrt(cos(2*pi*60*sqrt(L*1e-3*C*1e-9)*l)^2 + k^2*sin(2*pi*60*sqrt(L*1e-3*C*1e-9)*l)^2)
tolerance: 0.5%

### Receiving voltage relative to sending?

::: misses
- [any] $1/\sqrt{\cos^2\beta l + k^2\sin^2\beta l}$.
:::
:::
:::

::: check
kind: parts
given: x = 0.35 | 0.5; b = 3.5 | 5; l = 100 | 220

## A medium line: x = {x} Ω/km, b = {b} µS/km, {l} km, lossless.

::: part
answer: 1 - x*b*l^2*1e-6/2
tolerance: 0.5%

### Nominal-π A?

::: misses
- [any] $1 + ZY/2$.
:::
:::

::: part
answer: 1/(1 - x*b*l^2*1e-6/2)
tolerance: 0.5%

### No-load $V_R/V_S$?

::: misses
- [any] $1/A$.
:::
:::
:::

::: check
kind: parts
given: V = 0.97 | 1.03; W = 0.95 | 1; X = 0.15 | 0.4; d = 12 | 30

## Buses at {V} and {W} pu, angle {d}° apart, across X = {X} pu.

::: part
answer: V*W*sin(d*pi/180)/X
tolerance: 0.5%

### Real power?

::: misses
- [any] $V_1V_2\sin\delta/X$.
:::
:::

::: part
answer: (V^2 - V*W*cos(d*pi/180))/X
tolerance: 0.5%

### Reactive power leaving bus 1?

::: misses
- [any] $(V_1^2 - V_1V_2\cos\delta)/X$.
:::
:::

::: part
answer: V*W/X
tolerance: 0.5%

### Steady-state transfer limit?

::: misses
- [any] $V_1V_2/X$.
:::
:::
:::

::: check
kind: parts
given: X = 0.2 | 0.45; P = 0.3 | 0.7 | 1; R = 0.02 | 0.06; Q = 0.1 | 0.35

## A 1 pu source feeds a unity-pf load of {P} pu through X = {X} pu; separately, a feeder R = {R}, X = {X} carries {P} + j{Q} pu.

::: part
answer: sqrt((1 + sqrt(1 - 4*X^2*P^2))/2)
tolerance: 0.5%

### Receiving voltage on the upper branch?

::: misses
- [any] Nose-curve formula.
:::
:::

::: part
answer: 1/(2*X)
tolerance: 0.5%

### Maximum deliverable power at unity pf?

::: misses
- [any] $1/2X$.
:::
:::

::: part
answer: 100*(R*P + X*Q)
unit: %
tolerance: 0.5%

### Feeder voltage drop estimate?

::: misses
- [any] $RP + XQ$.
:::
:::
:::

::: check
kind: parts
given: X = 0.3 | 0.6; k = 0.3 | 0.55; P = 1 | 1.5

## A line of X = {X} pu between 1 pu buses, with {k} series compensation, carries {P} pu.

::: part
answer: 1/(X*(1 - k))
tolerance: 0.5%

### Transfer limit?

::: misses
- [any] $1/(X(1 - k))$.
:::
:::

::: part
answer: asin(P*X*(1 - k))*180/pi
unit: °
tolerance: 0.5%

### Angle needed?

::: misses
- [any] $\sin^{-1}(PX_\text{eff})$.
:::
:::

::: part
answer: asin(P*X)*180/pi
unit: °
tolerance: 0.5%

### Angle without compensation?

::: misses
- [any] $\sin^{-1}(PX)$.
:::
:::
:::

::: check
kind: parts
given: Q = 25 | 100; V = 0.8 | 0.9; S = 800 | 4000

## A {Q} Mvar capacitor and a {Q} Mvar STATCOM at a bus of {S} MVA short-circuit level.

::: part
answer: Q*V^2
unit: Mvar
tolerance: 0.5%

### Capacitor's output at {V} pu?

::: misses
- [any] $QV^2$.
:::
:::

::: part
answer: Q*V
unit: Mvar
tolerance: 0.5%

### STATCOM's output at {V} pu?

::: misses
- [any] QV.
:::
:::

::: part
answer: 100*Q/S
unit: %
tolerance: 0.5%

### Voltage rise when the capacitor is switched on at 1 pu?

::: misses
- [any] $Q/S_{sc}$.
:::
:::
:::

::: check
kind: parts
given: X = 0.3 | 0.7; V = 0.98 | 1.04

## A line of X = {X} pu between buses held at {V} pu.

::: part
answer: V^2/X
tolerance: 0.5%

### Transfer limit?

::: misses
- [any] $V^2/X$.
:::
:::

::: part
answer: 2*V^2/X
tolerance: 0.5%

### Limit with the midpoint held at {V} pu?

::: misses
- [any] $2V^2/X$.
:::
:::
:::

::: check
kind: parts
given: a = 0.06 | 0.12; b = 0.1 | 0.3; g = 0.15 | 0.25; B = 0.05 | 0.3

## Bus 1 has lines of j\given{a} and j\given{b} pu (the first with total charging {B} pu) and a generator of j\given{g}.

::: part
answer: 1/a + 1/b + 1/g
tolerance: 0.5%

### $|B_{11}|$ ignoring charging?

::: misses
- [any] Sum of $1/x$.
:::
:::

::: part
answer: 1/a + 1/b + 1/g - B/2
tolerance: 0.5%

### Including the first line's charging?

::: misses
- [any] Subtract B/2.
:::
:::

::: part
answer: 1/a
tolerance: 0.5%

### Off-diagonal magnitude to the first line's far bus?

::: misses
- [any] $1/x$.
:::
:::
:::

::: check
kind: parts
given: x = 0.06 | 0.1; a = 0.95 | 1.025

## A transformer j\given{x} pu with tap a = {a} on bus i's side.

::: part
answer: 1/(a^2*x)
tolerance: 0.5%

### Its contribution to $|Y_{ii}|$?

::: misses
- [any] $y/a^2$.
:::
:::

::: part
answer: 1/(a*x)
tolerance: 0.5%

### $|Y_{ij}|$?

::: misses
- [any] $y/a$.
:::
:::
:::

::: check
kind: parts
given: g = 0.12 | 0.2; p = 0.15 | 0.25; q = 0.1 | 0.2; x = 0.15 | 0.5; V = 1 | 1.05

## Generator j\given{g} at bus 1; bus 3 fed directly by j\given{p} and via bus 2 by j\given{q} + j\given{x}. Prefault {V} pu.

::: part
answer: g + p*(q + x)/(p + q + x)
tolerance: 0.5%

### $Z_{33}$?

::: misses
- [any] Series-parallel reduction.
:::
:::

::: part
answer: V/(g + p*(q + x)/(p + q + x))
tolerance: 0.5%

### Fault current at bus 3?

::: misses
- [any] $V/Z_{33}$.
:::
:::
:::

::: check
kind: parts
given: n = 2000 | 20000; k = 2.5 | 3.5

## A {n}-bus network with {k} connections per bus on average.

::: part
answer: n*(1 + k)
tolerance: 0.5%

### Nonzeros in $Y_\text{bus}$?

::: misses
- [any] n(1 + k).
:::
:::

::: part
answer: 100*(1 + k)/n
unit: %
tolerance: 0.5%

### Fraction of entries that are nonzero?

::: misses
- [any] $(1 + k)/n$.
:::
:::
:::

::: check
kind: parts
given: V = 400 | 600 | 900; Z = 350 | 450; K = 30 | 50

## A {V} kV surge on an overhead line ($Z_c$ = {Z} Ω) enters a substation through a short cable ($Z_c$ = {K} Ω) that ends at an open breaker.

::: part
answer: 2*K/(K + Z)*V
unit: kV
tolerance: 0.5%

### Voltage entering the cable?

::: misses
- [any] $(1 + \rho)V$, with ρ for the cable's surge impedance.
:::
:::

::: part
answer: 4*K/(K + Z)*V
unit: kV
tolerance: 0.5%

### Voltage at the open breaker when that wave first arrives?

::: misses
- [2*K/(K + Z)*V] The open end doubles the wave that reaches it.
- [any] The open end doubles the wave in the cable.
:::
:::

::: part
answer: (Z - K)/(Z + K)
tolerance: 0.5%

### Reflection coefficient, at the cable–line junction, for the wave returning up the cable?

::: misses
- [(K - Z)/(Z + K)] Now the wave travels in the cable and meets the line: $Z_R$ is the line's.
- [any] $(Z_R - Z_c)/(Z_R + Z_c)$ with the cable as $Z_c$.
:::
:::
:::

::: check
kind: parts
given: V = 180 | 220 | 260; a = 12 | 18; X = 8 | 12; I = 1.5 | 2.5

## A rectifier has {V} kV RMS on its valve side, fires at α = {a}° and carries {I} kA through $X_c$ = {X} Ω.

::: part
answer: 3*sqrt(2)/pi*V
unit: kV
tolerance: 0.5%

### Ideal no-load DC voltage $V_{d0}$?

::: misses
- [any] $(3\sqrt2/\pi)V_{LL}$.
:::
:::

::: part
answer: 3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I
unit: kV
tolerance: 0.5%

### DC voltage at this operating point?

::: misses
- [any] $V_{d0}\cos\alpha - (3/\pi)X_cI_d$.
:::
:::

::: part
answer: (3*sqrt(2)/pi*V*cos(a*pi/180) - 3/pi*X*I)*I
unit: MW
tolerance: 0.5%

### Power sent by this pole?

::: misses
- [any] $V_dI_d$.
:::
:::
:::

::: check
kind: parts
given: g = 0.1 | 0.2; p = 0.1 | 0.15; q = 0.15 | 0.25; x = 0.2 | 0.4

## Build $Z_\text{bus}$ branch by branch: a generator of j{g} pu at bus 1, a line of j{p} from bus 1 to new bus 2, a line of j{q} from bus 1 to new bus 3, then a line of j{x} between buses 2 and 3.

::: part
answer: g + p
tolerance: 0.5%

### $Z_{22}$ before the 2–3 line is added, in per unit?

::: misses
- [any] Rule 2: bus 1's diagonal plus the new branch.
:::
:::

::: part
answer: g + q - q^2/(p + q + x)
tolerance: 0.5%

### $Z_{33}$ after the 2–3 line, in per unit?

::: misses
- [g + q] The new line closes a loop and lowers $Z_{33}$: use rule 4.
- [any] Rule 4: the denominator is $Z_{22} + Z_{33} - 2Z_{23} + x$ = p + q + x.
:::
:::

::: part
answer: 1/(g + q - q^2/(p + q + x))
tolerance: 0.5%

### Bolted three-phase fault current at bus 3, in per unit?

::: misses
- [any] $1/Z_{33}$ with 1 pu prefault voltage.
:::
:::
:::

::: check
kind: parts
given: a = 0.05 | 0.1; b = 0.1 | 0.2; c = 0.15 | 0.3

## Bus 2 has no load or generation and connects only to bus 1 (j{a} pu) and bus 3 (j{b} pu). Buses 1 and 3 are also joined directly by j{c} pu. Bus 2 is eliminated by Kron reduction.

::: part
answer: 1/c + 1/(a + b)
tolerance: 0.5%

### Magnitude of the reduced network's susceptance between buses 1 and 3?

::: misses
- [1/c] Eliminating bus 2 adds the path through it in parallel.
- [any] The direct line plus the path through bus 2, in parallel.
:::
:::

::: part
answer: c*(a + b)/(a + b + c)
tolerance: 0.5%

### Equivalent reactance between buses 1 and 3, in per unit?

::: misses
- [any] The inverse of that susceptance.
:::
:::
:::
:::