title: "Problem set 3: ampacity, voltage stability and line computations"
heading: "Problem set 3: conductor heat balances and dynamic ratings, sag and clearance, P–V noses and reactive margins, load recovery under tap changers, exact long-line constants and traveling-wave lattices"
eyebrow: S10 · Problem set 3
type: problems
---

::: hook
These problems cover lessons 13 to 15: the thermal limits of lines and the sag that comes with heat, how far a network can be loaded before its voltage collapses and how to measure the margin, and the computations of the line lab, from parameters and exact ABCD constants to surges bouncing between the ends.
:::

::: pool
pick: 12

::: check
kind: parts
given: D = 18 | 28 | 36; R = 0.06 | 0.1; h = 10 | 20; T = 75 | 100

## A conductor of diameter {D} mm with {R} Ω/km at {T} °C is rated in 35 °C air with h = {h} W/m²K, ε = α = 0.5 and 900 W/m² of sun.

::: part
answer: sqrt((h*pi*D*1e-3*(T - 35) + 0.5*5.67e-8*pi*D*1e-3*((T + 273.15)^4 - 308.15^4) - 0.5*900*D*1e-3)/(R*1e-3))
unit: A
tolerance: 0.5%

### What is its ampacity?

::: misses
- [any] $\sqrt{(q_c + q_r - q_s)/R}$.
:::
:::

::: part
answer: h*pi*D*1e-3*(T - 35)/(h*pi*D*1e-3*(T - 35) + 0.5*5.67e-8*pi*D*1e-3*((T + 273.15)^4 - 308.15^4))*100
unit: %
tolerance: 0.5%

### What share of the cooling is convective?

::: misses
- [any] $q_c/(q_c + q_r)$.
:::
:::
:::

::: check
kind: parts
given: c = 40 | 60 | 90; r = 12 | 20; s = 8 | 15; k = 0.5 | 2 | 3

## At its rating a conductor sheds {c} W/m by convection and {r} W/m by radiation and absorbs {s} W/m of sun. The wind changes convection by a factor of {k}.

::: part
answer: sqrt((k*c + r - s)/(c + r - s))*100
unit: %
tolerance: 0.5%

### What fraction of its static rating may it now carry?

::: misses
- [k*100] Current goes as the square root of the net cooling.
- [any] $\sqrt{(kq_c + q_r - q_s)/(q_c + q_r - q_s)}$.
:::
:::
:::

::: check
kind: parts
given: w = 10 | 16 | 22; L = 250 | 400; H = 20 | 35; t = 40 | 70

## A span of {L} m carries a conductor of {w} N/m at {H} kN tension; it then heats by {t} °C ($\alpha_t$ = 19 × 10⁻⁶/°C, ignore elastic stretch).

::: part
answer: w*L^2/(8*H*1e3)
unit: m
tolerance: 0.5%

### What is the initial sag?

::: misses
- [any] $wL^2/8H$.
:::
:::

::: part
answer: sqrt(3*L*(8*(w*L^2/(8*H*1e3))^2/(3*L) + 19e-6*t*(L + 8*(w*L^2/(8*H*1e3))^2/(3*L)))/8) - w*L^2/(8*H*1e3)
unit: m
tolerance: 1%

### How much does the sag grow?

::: misses
- [any] New $\sqrt{3L(S - L)/8}$ minus the old sag.
:::
:::
:::

::: check
kind: parts
given: E = 1 | 1.05; X = 0.15 | 0.3; f = 0.85 | 0.9 | 0.95; P = 0.5 | 0.8

## A source of {E} pu feeds {P} pu at power factor {f} lagging through X = {X} pu.

::: part
answer: (E^2*f/(2*X*(1 + sqrt(1 - f^2)))/P - 1)*100
unit: %
tolerance: 0.5%

### What is the loadability margin?

::: misses
- [any] $(P_\max - P)/P$ with $P_\max = E^2\cos\phi/(2X(1 + \sin\phi))$.
:::
:::

::: part
answer: E/sqrt(2*(1 + sqrt(1 - f^2)))
tolerance: 0.5%

### At what voltage would collapse occur?

::: misses
- [any] $E/\sqrt{2(1 + \sin\phi)}$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 1 | 1.5; Q = 0.1 | 0.3; X = 0.1 | 0.15

## A 1 pu slack feeds {P} + j{Q} pu through lossless X = {X} pu.

::: part
answer: sqrt((1 - 2*Q*X + sqrt((2*Q*X - 1)^2 - 4*X^2*(P^2 + Q^2)))/2)
tolerance: 0.5%

### What is the operating voltage?

::: misses
- [any] Larger root of $V^4 + (2QX - 1)V^2 + X^2(P^2 + Q^2) = 0$.
:::
:::

::: part
answer: asin(P*X/sqrt((1 - 2*Q*X + sqrt((2*Q*X - 1)^2 - 4*X^2*(P^2 + Q^2)))/2))*180/pi
unit: °
tolerance: 0.5%

### What angle does the load bus sit behind the slack?

::: misses
- [any] $\sin\delta = PX/V$.
:::
:::
:::

::: check
kind: parts
given: P = 0.5 | 1 | 2; X = 0.05 | 0.1 | 0.2

## A 1 pu source supplies {P} pu at unity power factor through X = {X} pu.

::: part
answer: (0.25 - P^2*X^2)/X
tolerance: 0.5%

### What reactive margin does its Q–V curve show?

::: misses
- [any] $(1/4 - P^2X^2)/X$.
:::
:::

::: part
answer: (1 - sqrt(1 - P^2*X^2))/X
tolerance: 1%

### How many vars must be supplied at the bus to hold it at 1 pu?

::: misses
- [any] $Q_c(1) = (1 - \sqrt{1 - P^2X^2})/X$.
:::
:::
:::

::: check
kind: parts
given: v = 0.85 | 0.9 | 0.95; n = 1 | 2

## After a disturbance a distribution bus sags to {v} pu; its load's power varies as $V^n$ with n = {n}. Tap changers then restore it to 1 pu.

::: part
answer: (1 - v^n)*100
unit: %
tolerance: 0.5%

### By what percentage did the sag cut the load's power?

::: misses
- [any] $1 - v^n$.
:::
:::

::: part
answer: (1/v^n - 1)*100
unit: %
tolerance: 0.5%

### By what percentage does restoring the voltage raise it again from the sagged level?

::: misses
- [any] $1/v^n - 1$.
:::
:::
:::

::: check
kind: parts
given: a = 6 | 8; b = 6 | 8; c = 12 | 16; s = 0.008 | 0.012; d = 0.4 | 0.45

## A transposed line has phase spacings {a}, {b} and {c} m and two-conductor bundles {d} m apart, each conductor with GMR {s} m.

::: part
answer: (a*b*c)^(1/3)
unit: m
tolerance: 0.5%

### What is the geometric mean distance?

::: misses
- [any] $\sqrt[3]{D_{12}D_{23}D_{31}}$.
:::
:::

::: part
answer: 2e-7*ln((a*b*c)^(1/3)/sqrt(s*d))*1e6
unit: mH/km
tolerance: 0.5%

### What is its inductance?

::: misses
- [2e-7*ln((a*b*c)^(1/3)/s)*1e6] The bundle's GMR is $\sqrt{D_sd}$.
- [any] $2 \times 10^{-7}\ln(D_m/\sqrt{D_sd})$.
:::
:::
:::

::: check
kind: parts
given: l = 300 | 500 | 700; x = 0.35 | 0.5; b = 3 | 4.5

## A lossless line with x = {x} Ω/km and b = {b} µS/km is {l} km long.

::: part
answer: sqrt(x*b*1e-6)*l*180/pi
unit: °
tolerance: 0.5%

### What is βl?

::: misses
- [any] $\beta = \sqrt{xb}$ per km.
:::
:::

::: part
answer: 1/cos(sqrt(x*b*1e-6)*l)
tolerance: 0.5%

### How much does its open far end rise?

::: misses
- [any] $1/\cos\beta l$.
:::
:::
:::

::: check
kind: parts
given: Z = 300 | 400; R = 0 | 50 | 200

## A step of 1 pu through source resistance {R} Ω energizes an open-ended line with $Z_c$ = {Z} Ω.

::: part
answer: 2*Z/(Z + R)
tolerance: 0.5%

### What voltage first appears at the far end?

::: misses
- [Z/(Z + R)] The open end doubles the arriving wave.
- [any] $2VZ_c/(Z_c + R_S)$.
:::
:::

::: part
answer: (R - Z)/(R + Z)
tolerance: 0.5%

### What is the source's reflection coefficient?

::: misses
- [any] $(R_S - Z_c)/(R_S + Z_c)$.
:::
:::
:::

::: check
kind: parts
given: Z = 250 | 400; L = 50 | 400; v = 290 | 300; I = 10 | 30

## A {I} kA lightning stroke hits a phase conductor of a {L} km line ($Z_c$ = {Z} Ω, wave speed {v} m/µs) and splits both ways.

::: part
answer: 2*L*1e3/v
unit: µs
tolerance: 0.5%

### How long does a surge take to travel the line's length and back?

::: misses
- [L*1e3/v] That's one way.
- [any] $2l/v$.
:::
:::

::: part
answer: I*Z/2/1e3
unit: MV
tolerance: 0.5%

### What voltage does the stroke raise on the conductor?

::: misses
- [I*Z/1e3] The current divides between two directions: it sees $Z_c/2$.
- [any] $IZ_c/2$.
:::
:::
:::

::: check
kind: parts
given: V = 230 | 345 | 500; l = 100 | 250; b = 3.5 | 4.5; f = 0.6 | 0.8

## A {V} kV line of {l} km (b = {b} µS/km) is energized unloaded, and shunt reactors absorb {f} of its charging.

::: part
answer: V^2*b*l*1e-6*(1 - f)
unit: Mvar
tolerance: 0.5%

### How many vars does the source still have to absorb?

::: misses
- [any] The uncompensated part of $V^2B$.
:::
:::
:::

::: check
kind: parts
given: m = 1 | 1.6 | 2.4; c = 900 | 960; G = 1.5 | 3

## A conductor with {m} kg/m (specific heat {c} J/kg·K) gains {G} W/m of net cooling per kelvin near its operating point.

::: part
answer: m*c/G/60
unit: min
tolerance: 0.5%

### What is its thermal time constant?

::: misses
- [any] Heat capacity per meter over the cooling slope.
:::
:::

::: part
answer: (1 - exp(-10*60*G/(m*c)))*100
unit: %
tolerance: 0.5%

### What fraction of its final temperature rise does a step in current produce after 10 minutes?

::: misses
- [any] $1 - e^{-t/\tau}$.
:::
:::
:::

::: check
kind: choice

## Two buses look alike in a power flow: both at 0.97 pu. One has mostly motor loads and little reactive reserve nearby; the other has resistive loads and a large synchronous condenser. Which is closer to voltage collapse, and how would you show it?

- [ ] They're equally close: the voltages match
- [x] The first: constant-power motor loads and scarce reactive support leave a small reactive margin; computing each bus's Q–V curve or loading it toward the nose would show it
- [ ] The second, because condensers absorb vars
- [ ] Neither can collapse above 0.9 pu

::: misses
- [1] Voltage alone doesn't measure the margin.
- [3] A condenser supplies vars when the voltage sags.
- [4] Compensated buses can collapse near normal voltage.
:::
:::
:::