title: "Problem set 7: faults and protection"
heading: "Problem set 7: three-phase faults, symmetrical components, unsymmetrical and open-conductor faults, and protective relaying"
eyebrow: S10 · Problem set 7
type: problems
---

::: hook
These problems cover lessons 36 to 40: subtransient fault currents, DC offset and short-circuit levels, fault calculations with the bus impedance matrix, sequence components, the four fault types and neutral grounding, faults seen through delta–wye transformers, open conductors, and setting overcurrent, distance and differential relays.
:::

::: pool
pick: 12

::: check
kind: parts
given: X = 0.12 | 0.22; T = 0.08 | 0.12; S = 100 | 300; V = 13.8 | 18; W = 138 | 230

## A {S} MVA, {V} kV generator (X″ = {X} pu) with a {V}/{W} kV transformer (X = {T} pu on {S} MVA).

::: part
answer: 1/X*S*1e6/(sqrt(3)*V*1e3)/1000
unit: kA
tolerance: 0.5%

### Terminal fault current?

::: misses
- [any] $(1/X'')I_\text{base}$.
:::
:::

::: part
answer: 1/(X + T)*S*1e6/(sqrt(3)*W*1e3)/1000
unit: kA
tolerance: 0.5%

### Fault current on the {W} kV side?

::: misses
- [any] $1/(X'' + X_T)$ at the high-side base.
:::
:::

::: part
answer: S/(X + T)
unit: MVA
tolerance: 0.5%

### Short-circuit level there?

::: misses
- [any] $S/Z_{th}$.
:::
:::
:::

::: check
kind: parts
given: k = 0.25 | 0.4; i = 0.1 | 0.18; j = 0.06 | 0.15

## A fault at bus k ($Z_{kk}$ = j{k}) with $Z_{ik}$ = j{i} and $Z_{jk}$ = j{j}, prefault 1 pu.

::: part
answer: 1/k
tolerance: 0.5%

### Fault current?

::: misses
- [any] $1/Z_{kk}$.
:::
:::

::: part
answer: 1 - i/k
tolerance: 0.5%

### Bus i voltage?

::: misses
- [any] $1 - Z_{ik}/Z_{kk}$.
:::
:::

::: part
answer: (i - j)/k
tolerance: 0.5%

### Voltage difference between buses j and i?

::: misses
- [any] $V_j - V_i = (Z_{ik} - Z_{jk})/Z_{kk}$.
:::
:::
:::

::: check
kind: parts
given: r = 8 | 20 | 40; I = 15 | 50; a = 0.15 | 0.3; b = 0.2 | 0.5

## A {I} kA symmetrical fault where X/R = {r}; and a bus fed by sources of {a} and {b} pu.

::: part
answer: sqrt(2)*(1 + exp(-pi/r))*I
unit: kA
tolerance: 0.5%

### Worst first peak?

::: misses
- [any] $\sqrt{2}I(1 + e^{-\pi R/X})$.
:::
:::

::: part
answer: 1/a + 1/b
tolerance: 0.5%

### Fault current at the bus in pu?

::: misses
- [any] Parallel sources.
:::
:::
:::

::: check
kind: parts
given: A = 90 | 130; B = 60 | 100; C = 70 | 120; I = 8 | 60

## Phase currents {A}∠0°, {B}∠−120°, {C}∠120° A; and a line-to-line load of {I} A.

::: part
answer: abs(A + B*exp(-j*2*pi/3) + C*exp(j*2*pi/3))
unit: A
tolerance: 0.5%

### Neutral current?

::: misses
- [any] $|I_a + I_b + I_c|$.
:::
:::

::: part
answer: (A + B + C)/3
unit: A
tolerance: 0.5%

### Positive-sequence magnitude?

::: misses
- [any] $(A + B + C)/3$ here.
:::
:::

::: part
answer: I/sqrt(3)
unit: A
tolerance: 0.5%

### Line-to-line load's negative-sequence current?

::: misses
- [any] $I/\sqrt{3}$.
:::
:::
:::

::: check
kind: parts
given: m = 0.75 | 0.88 | 0.95; x = 0.15 | 0.4; t = -30 | 10

## Phase b sags to {m} pu; separately, $V_1$ = 1 and $V_2$ = {x} pu; and a negative-sequence voltage at {t}° on a Y–Δ low side.

::: part
answer: 100*(1 - m)/(2 + m)
unit: %
tolerance: 0.5%

### Unbalance from the sag?

::: misses
- [any] $(1 - m)/(2 + m)$.
:::
:::

::: part
answer: abs(exp(-j*2*pi/3) + x*exp(j*2*pi/3))
tolerance: 0.5%

### |V_b| for the second case?

::: misses
- [any] $|a^2 + ax|$.
:::
:::

::: part
answer: t - 30
unit: °
tolerance: 0.5%

### Its angle on the high side?

::: misses
- [any] Negative sequence: −30°.
:::
:::
:::

::: check
kind: parts
given: a = 0.12 | 0.2 | 0.3; c = 0.08 | 0.25 | 0.5

## A bus with $Z_1 = Z_2$ = j{a} and $Z_0$ = j{c} pu.

::: part
answer: 1/a
tolerance: 0.5%

### Three-phase fault current?

::: misses
- [any] $1/Z_1$.
:::
:::

::: part
answer: 3/(2*a + c)
tolerance: 0.5%

### Line-to-ground?

::: misses
- [any] $3/(Z_1 + Z_2 + Z_0)$.
:::
:::

::: part
answer: sqrt(3)/(2*a)
tolerance: 0.5%

### Line-to-line?

::: misses
- [any] $\sqrt{3}/(Z_1 + Z_2)$.
:::
:::
:::

::: check
kind: parts
given: a = 0.15 | 0.25; c = 0.15 | 0.4; r = 0.05 | 0.15

## A bus with $Z_1 = Z_2$ = j{a}, $Z_0$ = j{c}.

::: part
answer: 3*(1/(a + a*c/(a + c)))*a/(a + c)
tolerance: 0.5%

### Ground current for a double line-to-ground fault?

::: misses
- [any] $3|I_{a0}|$.
:::
:::

::: part
answer: 3/sqrt((2*a + c)^2 + (3*r)^2)
tolerance: 0.5%

### Line-to-ground current through {r} pu of fault resistance?

::: misses
- [any] $3/|j(2Z_1 + Z_0) + 3R_f|$.
:::
:::
:::

::: check
kind: parts
given: a = 0.15 | 0.2; c = 0.1 | 0.3; I = 1.2 | 2

## Neutral grounding for a bus with $Z_1 = Z_2$ = j{a}, $Z_0$ = j{c}.

::: part
answer: (3/I - 2*a - c)/3
tolerance: 0.5%

### Reactance limiting ground faults to {I} pu?

::: misses
- [any] $(3/I - Z_1 - Z_2 - Z_0)/3$.
:::
:::

::: part
answer: 3/(2*a + c)/(1/a)
tolerance: 0.5%

### Ground-to-three-phase ratio when solidly grounded?

::: misses
- [any] $3Z_1/(2Z_1 + Z_0)$.
:::
:::
:::

::: check
kind: parts
given: I = 2500 | 9000; R = 300 | 800; s = 5 | 1; f = 0.8 | 1.2; let P = f*s

## A {R}:{s} CT on a feeder with a very inverse relay (dial 1.5) picking up at {P} A secondary; fault current {I} A.

::: part
answer: I*s/R
unit: A
tolerance: 0.5%

### CT secondary current?

::: misses
- [any] $I\,s/R$.
:::
:::

::: part
answer: I*s/R/P
tolerance: 0.5%

### Multiple of pickup?

::: misses
- [any] Secondary current over pickup.
:::
:::

::: part
answer: 1.5*(19.61/((I*s/R/P)^2 - 1) + 0.491)
unit: s
tolerance: 0.5%

### Operating time?

::: misses
- [any] IEEE very inverse.
:::
:::
:::

::: check
kind: parts
given: M = 4 | 8; d = 0.25 | 0.5; c = 0.3 | 0.4

## A downstream relay operates in {d} s; an upstream very inverse relay sees {M} times pickup for the same fault; coordination interval {c} s.

::: part
answer: d + c
unit: s
tolerance: 0.5%

### Required upstream time?

::: misses
- [any] Downstream plus interval.
:::
:::

::: part
answer: (d + c)/(19.61/(M^2 - 1) + 0.491)
tolerance: 0.5%

### Upstream time dial?

::: misses
- [any] Time over the curve value at M.
:::
:::
:::

::: check
kind: parts
given: Z = 25 | 80; C = 200 | 400; V = 2000 | 3000; k = 0.8 | 0.85; w = 1.2 | 1.3

## A line of {Z} Ω, CT ratio {C}, VT ratio {V}.

::: part
answer: Z*C/V
unit: Ω
tolerance: 0.5%

### Line in secondary ohms?

::: misses
- [any] $Z\,\text{CTR}/\text{VTR}$.
:::
:::

::: part
answer: k*Z*C/V
unit: Ω
tolerance: 0.5%

### Zone 1 setting ({k} of the line), secondary?

::: misses
- [any] k times that.
:::
:::

::: part
answer: w*Z*C/V
unit: Ω
tolerance: 0.5%

### Zone 2 setting ({w} of the line), secondary?

::: misses
- [any] w times that.
:::
:::
:::

::: check
kind: parts
given: a = 8 | 30; b = 7 | 26; s = 0.2 | 0.35

## A differential relay with slope {s} sees {a} A in and {b} A out.

::: part
answer: abs(a - b)
unit: A
tolerance: 0.5%

### Operating current?

::: misses
- [any] $|I_1 - I_2|$.
:::
:::

::: part
answer: 100*abs(a - b)/((a + b)/2)
unit: %
tolerance: 0.5%

### As a percentage of the restraint?

::: misses
- [any] Difference over average.
:::
:::
:::

::: check
kind: parts
given: p = 0.8 | 1 | 1.2; a = 0.6 | 0.9; c = 1.2 | 2 | 3

## One phase of a line carrying {p} pu breaks. Across the break $Z_1' = Z_2'$ = j{a} pu and $Z_0'$ = j{c} pu.

::: part
answer: p*a/(a + a*c/(a + c))
tolerance: 0.5%

### Positive-sequence current, in per unit?

::: misses
- [any] Networks in parallel: $I Z_1'/(Z_1' + Z_2' \parallel Z_0')$.
:::
:::

::: part
answer: p*a/(a + a*c/(a + c))*(a*c/(a + c))/a
tolerance: 0.5%

### Negative-sequence current magnitude, in per unit?

::: misses
- [any] The voltage across the break over $Z_2'$.
:::
:::

::: part
answer: 3*p*a/(a + a*c/(a + c))*(a*c/(a + c))/c
tolerance: 0.5%

### Current returning through the ground, in per unit?

::: misses
- [any] $3|I_0|$, with $I_0$ the voltage across the break over $Z_0'$.
:::
:::
:::

::: check
kind: parts
given: z1 = 0.15 | 0.25; z0 = 0.1 | 0.2 | 0.4; S = 100 | 200; V = 13.8 | 34.5

## A bolted line-to-ground fault occurs on the grounded-wye low side ({V} kV) of a delta–wye transformer, where $Z_1 = Z_2$ = j{z1} pu and $Z_0$ = j{z0} pu on {S} MVA.

::: part
answer: 3/(2*z1 + z0)
tolerance: 0.5%

### Fault current in per unit?

::: misses
- [any] $3/(Z_1 + Z_2 + Z_0)$.
:::
:::

::: part
answer: 3/(2*z1 + z0)*S/(sqrt(3)*V)
unit: kA
tolerance: 0.5%

### Fault current in kiloamperes?

::: misses
- [any] Multiply by the base current $S/(\sqrt3 V)$.
:::
:::

::: part
answer: 3/(2*z1 + z0)/sqrt(3)
tolerance: 0.5%

### Current in each of the two faulted phases on the delta side, in per unit?

::: misses
- [any] The ±30° shifts give $I_f/\sqrt3$ in two phases.
:::
:::
:::

::: check
kind: parts
given: r = 6 | 12 | 25; c = 1.5 | 3 | 5; I = 20 | 40

## A {I} kA symmetrical fault with X/R = {r} (60 Hz) is interrupted after {c} cycles.

::: part
answer: r/(2*pi*60)*1000
unit: ms
tolerance: 0.5%

### What is the DC time constant?

::: misses
- [any] $(X/R)/\omega$.
:::
:::

::: part
answer: I*sqrt(1 + 2*exp(-2*c/60/(r/(2*pi*60))))
unit: kA
tolerance: 0.5%

### What worst-case RMS current must the breaker interrupt?

::: misses
- [any] $I\sqrt{1 + 2e^{-2t/\tau}}$.
:::
:::
:::
:::